2005-12-01 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED FLORIDA PRODUCT APPROVAL OR
 APPLY FOR LOCAL PRODUCT APPROVAL FOR
 SHUTTERS AS REQUIRED BY RULE 9B-72 OF
 DCA (COMPLYING WITH FBC 2004). GO TO
 WWW.FLORIDABUILDING.ORG FOR PRODUCT
 APPROVAL INFORMATION.
 ***NOTE: DADE COUNTY NOA ALONE IS NOT
 AUTOMATICALLY AN STATEWIDE FLORIDA
 PRODUCT APPROVAL. IF MANUFACTURER HASN'T
 APPLIED FOR FLORIDA PRODUCT APPROVAL,
 THEN, MANUFACTURER MAY APPLY FOR LOCAL
 PRODUCT APPROVAL USING THE DADE COUNTY
 NOA AND COMPLETING THE LOCAL PRODUCT
 APPROVAL FORM DOWNLOADED FROM WEBSITE
 WWW.FLORIDABUILDING.ORG.
  
 2- ACCORDING TO NOA NO 02-1216.12 SHEET
 1 OF 1 OF DWG 02-561 GENERAL NOTE 2(A)
 THE MAX. SHUTTER SPAN IS 8'-0". PROPOSED
 SHUTTER IS 9'-0", THEREFORE, IT CAN'T BE
 USED.
  
 3- PROVIDE COMPLETE INSTALLATION
 SCHEDULE (SEE ATTACHED SAMPLE) AS REQ'D
 BY CITY IMPLEMENTATION STANDARD FOR
 HURRICANE MISSILE IMPACT PROTECTION AND
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
  
 4- NOTICE OF COMMENCEMENT IS EXPIRED
 AFTER 90 DAYS OF RECORDING IF WORK IS
 NOT STARTED. SEC. 713.13(2) OF FLORIDA
 STATUTES. NEED RE-RECORDED NOTICE OF
 COMMENCEMENT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712