| 2005-12-01 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED FLORIDA PRODUCT APPROVAL OR |
| | APPLY FOR LOCAL PRODUCT APPROVAL FOR |
| | SHUTTERS AS REQUIRED BY RULE 9B-72 OF |
| | DCA (COMPLYING WITH FBC 2004). GO TO |
| | WWW.FLORIDABUILDING.ORG FOR PRODUCT |
| | APPROVAL INFORMATION. |
| | ***NOTE: DADE COUNTY NOA ALONE IS NOT |
| | AUTOMATICALLY AN STATEWIDE FLORIDA |
| | PRODUCT APPROVAL. IF MANUFACTURER HASN'T |
| | APPLIED FOR FLORIDA PRODUCT APPROVAL, |
| | THEN, MANUFACTURER MAY APPLY FOR LOCAL |
| | PRODUCT APPROVAL USING THE DADE COUNTY |
| | NOA AND COMPLETING THE LOCAL PRODUCT |
| | APPROVAL FORM DOWNLOADED FROM WEBSITE |
| | WWW.FLORIDABUILDING.ORG. |
| | |
| | 2- ACCORDING TO NOA NO 02-1216.12 SHEET |
| | 1 OF 1 OF DWG 02-561 GENERAL NOTE 2(A) |
| | THE MAX. SHUTTER SPAN IS 8'-0". PROPOSED |
| | SHUTTER IS 9'-0", THEREFORE, IT CAN'T BE |
| | USED. |
| | |
| | 3- PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE (SEE ATTACHED SAMPLE) AS REQ'D |
| | BY CITY IMPLEMENTATION STANDARD FOR |
| | HURRICANE MISSILE IMPACT PROTECTION AND |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 |
| | |
| | 4- NOTICE OF COMMENCEMENT IS EXPIRED |
| | AFTER 90 DAYS OF RECORDING IF WORK IS |
| | NOT STARTED. SEC. 713.13(2) OF FLORIDA |
| | STATUTES. NEED RE-RECORDED NOTICE OF |
| | COMMENCEMENT. |
| | |