| 2007-09-04 12:19:49 | PERMIT: 05100089 |
| | ADD: 1552 PALM BEACH LAKES |
| | CONT: KUEBLER BUILDERS |
| | TEL: (419)467-6624 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | WINDOW & DOOR SHOP DRAWING REVIEW: |
| | |
| | ACTION: DENIED |
| | REVISION: |
| | YKK AP |
| | |
| | YES 45 FS STOREFRONT SYSTEM |
| | 03-0801.04 MISSLE IMPACT RATING: NONE |
| | |
| | 1) THIS REVISION INDICATES THE USE OF A STOREFRONT |
| | SYSTEM WITH NO LARGE MISSILE WILL REQUIRESTORM |
| | SHUTTERS |
| | |
| | THE FOLLOWING IS TAKEN FROM THE BUILDING OFFICIALS |
| | IMPLEMENTATION STANDARDS FOR HIGH WIND-BORNE DEBRIS |
| | IMPACT PROTECTIONSTANDARD. |
| | 104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR WIND-BORNE |
| | DEBRIS IMPACT PROTECTION |
| | QUESTION# 13 RECOGNIZING SUCH CONCERNS AS ABSENTEE |
| | OWNERS, OR CASES WHERE LONGER TIME & EFFORT IS |
| | NECESSARY TO SECURE SHUTTERS ON LARGE OR MULTI-STORY |
| | BUILDINGS, WHAT MEASURES ARE BEING RECOMMENDED OR |
| | IMPLEMENTED TO ENSURE THAT COMPLETE INSTALLATION OR |
| | SECURING IS DONE SUFFICIENTLY IN ADVANCE OF THE |
| | HURRICANE? |
| | |
| | IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE |
| | GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE, |
| | SECTION 104.6 OF THE FLORIDA BUILDING CODE,BUILDING, |
| | CHAPTER 1, |
| | ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY |
| | OF WEST PALM BEACH, PROVDES THE ABILITY FOR THE |
| | BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR |
| | ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION |
| | OF EXISTING BUILDINGS. |
| | |
| | IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR |
| | MULTI-STORY BUILDINGS, OR MULTIPLE BUILDINGS ON THE |
| | SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST BE |
| | SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS FOR |
| | REVIEW BY THE CONSTRUCTION SRVICES DEPARTMENT. ANY SUCH |
| | PLAN SHALL INCLUDE, AT A MINMUM, ON SITE LOCATION OF |
| | THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE |
| | SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH |
| | COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND |
| | THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS. |
| | PROTECTION OF OPENINGS SHALL BE ACCOMPLISHEDWITHIN |
| | TWELVE (12) HOURS OR LESS OF THE |
| | OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES |
| | OF A HURRICANE WATCH. |
| | |
| | PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD) |
| | ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE |
| | MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO |
| | REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN |
| | QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE, |
| | DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED |
| | UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE |
| | MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE |
| | BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO |
| | SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE. |
| | |
| | IF STORM SHUTTERS ARE APPROVED FOR THIS PROJECT THE |
| | FOLLOWING WOULD BE REQUIRED. |
| | PRODUCT APPROVAL REPORT WITH THE FOLLOWING |
| | INFORMATION. |
| | PROVIDE STORM PANEL INFORMATION WITH INSTALLATION |
| | SCHEDULE AND KEY PLAN WITH |
| | SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| | FOR ALL NON-IMPACT GLAZING. |
| | FBC 1606.1.4.FL BLD CODE 2001 SECTION 103.6, |
| | 1606.1.4, 1707.4 & 3401.7.2.4. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRES- |
| | SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | |
| | |
| | 2) WRONG ASCE7-98, SHOULD READ ASCE 7-02 |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC |
| | REQUIREMENT SHALL BE APPLICABLE. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | |
| | |
| | |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |