Plan Review Notes
Plan Review Notes For Permit 05100089
Permit Number 05100089
Review Stop E
Sequence Number 4
Notes
Date Text
2007-02-04 14:51:40*** UNSAT 4TH REVIEW ***
  
 ** PLEASE SEE THIS IS THE FIRST REVIEW UNDER PERMIT
 APPLICATION. THIS IS THE 4TH REVIEW FOR THE PROJECT.
  
 ** PLEASE SEE SOME OF THE NOTES ARE THE SAME FROM
 PREVIOUS REVIEW. PLEASE ALSO SEE NEW COMMENTS DUE TO
 CHANGES MADE TO PLANS, CHANGES IN CODE AND PLANS
 SUBMITTED.
  
  
 1) NOTE: PLEASE SEE THAT THE PLANS WERE ONLY NOW
 SUBMITTED FOR PERMIT APPLICATION ON JANUARY 16, 2007
 WHICH PLACES THE ENTIRE PROJECT UNDER THE NEW CODES
 WHICH WERE ADOPTED BY THE STATE OF FLORIDA ON DECEMBER
 8TH, 2006. THIS INFORMATION WAS DIRECTLY CONVEYED TO
 THE DESIGN TEAM AND ON PREVIOUS REVIEW NOTES THAT THE
 PLANS WERE ONLY SUBMITTED UNDER *PLAN REVIEW* AND WERE
 NOT SUBMITTED UNDER PERMIT APPLICATION. ONLY IF
 SUBMITTED UNDER PERMIT APPLICATION BEFORE THE DECEMBER
 8TH, 2006 DATE WOULD THIS PROJECT FALL UNDER THE
 PREVIOUS CODES?
 THIS INFORMATION WAS ALSO GIVEN TO THE CONTRACTOR
 BEFORE THE PLANS WERE SUBMITTED THAT THE NEW CODES WENT
 INTO AFFECT AND THE CONTRACTOR MENTIONED HE WAS ASSURED
 BY THE DESIGN TEAM THAT THE PLANS HAD BEEN CHANGED,
 HOWEVER THE PLANS HAVE NOT CHANGED AND THE CODES ARE
 STILL UNDER THE OLD CODES.
 PLEASE SEE THAT PLANS SHALL NOW BE DESIGNED UNDER 2006
 REVISIONS TO THE 2004 FBC, AND THE 2005 NEC.
 (NFPA-70).
  
 2) NOTE: PLEASE SEE HAND DRAWN CHANGES TO THE
 ELECTRICAL PLANS WERE DONE AND SOME ARE SIGNED BY OTHER
 THAN THE ENGINEER OF RECORD OF THOSE SHEETS. THE
 SIGNATURE AS ON THE ARCHITECTURAL PLANS IS THAT ON THE
 ELECTRICAL PLANS.
 PLEASE ALSO SEE OTHER ITEMS WHICH WERE HAND DRAWN ON
 PLANS WITH OUT ANY INFORMATION WHICH IS NOT PERMITTED.
 PLEASE RE-PRINT ALL SHEETS FOR CODE CORRECTIONS, AND
 OTHER ITEMS HAND DRAWN ON PLANS AND HAVE PLANS
 RE-SIGNED, DATED AND SEALED BY THE DESIGNER(S) OF
 RECORD WHICH ARE RESPONSIBLE FOR THEIR SHEETS ONLY.
 FS 471.025, FAC 61G15-23.002
 FBC 106.1, 106.3.5.1.2
 ** PLEASE KNOW THAT ONE SET OF PLANS ARE NOW BEING
 RETAINED BY THIS OFFICE.
  
 3) NOTE: PLEASE SEE ONLY ONE SET OF UPDATED ENERGY
 CALCULATIONS WERE SUBMITTED AND THE DATES ON THOSE WERE
 12/11/06. PLEASE SEE THAT IN ANY CASE THEY DO NOT
 CORRELATE WITH THE PLANS FOR LIGHTING ALLOWANCES.
 PLEASE SEE THE 2006 REVISIONS TO THE 2004 FBC CHAPTER
 HAVE HAD REVISIONS.
 PLEASE SEE 13-415.1.AB.1 AND 13-415.2 FOR PERFORMANCE
 CALCULATIONS WHICH NEED TO CORRELATE WITH THE ENERGY
 CALCULATIONS AND PLANS FOR MAXIMUM LIGHTING
 ALLOWANCES.
  
 4) NOTE: PLEASE SEE COMPLIANCE WITH CHAPTER 13 HAS NOT
 YET BEEN ACCOMPLISHED. PLEASE SEE THAT THE CODE HAS
 CHANGED, HOWEVER ITEMS FROM PREVIOUS REVIEW HAVE NOT
 YET BEEN COMPLETELY ADDRESSED.
 PLEASE SEE ALL ENTRANCES INTO SPACE SHALL CONTAIN AN
 OVER RIDE DEVICE OF SOME KIND. (FRONT DOOR?) WHICH DOES
 NOT CONTAIN EITHER OC TYPE DEVICE TO OVER-RIDE THE
 TIMED SCHEDULING OR AN OVER RIDE TYPE SWITCHING
 DEVICE.
 PLEASE SEE THE SWITCHES ON SW BANK *A* AND *B* DO NOT
 INDICATE ANY MAXIMUM TIMES FOR OVER RIDE, ONLY THE SW
 *C* INDICATES THE MAXIMUM OF 4HRS ON OVER RIDE.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 (PLEASE BE SURE TO SEE NEW 2006 REVISIONS TO THE 2004
 FBC).
  
 5) NOTE: PLEASE SEE THE PHOTO-METRICS SUBMITTED NOW
 CONTAIN A SIGNATURE AND LICENSE NUMBER FOR THE
 ARCHITECT, HOWEVER NOT COMPLETE TITLE BLOCK IS ON
 PLANS/SHEETS AND THEY ARE NOT SEALED WITH THE REQUIRED
 RAISED SEAL.
 FAC 61G1-16.004, FS 481.221
  
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]