 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 DENIED
 FROM PREVIOUS COMMENTS
  
 SHT A-4 ROOF PLAN:
 RESPONSE DATED 6-18-06
 SHOWS A SCUPPER AS WELL AS THE PRIMARY
 ROOF DRAIN IN ONE OPENING, NEXT TO THAT
 IS THE SECONDARY ROOF DRAIN.
 PLEASE CLARIFI,THEY ARE SEPERATE DRAINS.
 PROVIDE THE LOCATION OF THE CALCULATIONS
 FOR THE ROOF DRAINS AND THE SECONDARY
 DRAINS, COMPONET SIZES.
 PROVIDE AN ELEVATION DETAIL OF THE ROOF
 DRAIN AND THE SCUPPER DRAIN.
 SHT A-5 DETAIL "C" SHOWS ONE DRAIN THRU
 THE PARAPET WALL.
 END OF COMMENTS QUESTIONS 561-805-6692
  
 1) PREVIOUS NOTE #3 SHT A-4
 NOT ADDRESSED.
 SEPERATE SECONDARY DRAINAGE, FROM
 PRIMARY DRAINAGE SYSTEM REQUIRED.
 SECTION 1107
 SECONDARY (EMERGENCY) ROOF DRAINS
 1107.1 SECONDARY DRAINAGE REQUIRED.
 SECONDARY (EMERGENCY) ROOF DRAINS OR
 SCUPPERS SHALL BE PROVIDED WHERE THE
 ROOF PERIMETER CONSTRUCTION EXTENDS
 ABOVE THE ROOF IN SUCH A MANNER THAT
 WATER WILL BE ENTRAPPED IF THE PRIMARY
 DRAINS ALLOW BUILDUP FOR ANY REASON.
 1107.2 SEPARATE SYSTEMS REQUIRED.
 SECONDARY ROOF DRAIN SYSTEMS SHALL HAVE
 THE END POINT OF DISCHARGE SEPARATE FROM
 THE PRIMARY SYSTEM. DISCHARGE SHALL BE
 ABOVE GRADE, IN A LOCATION WHICH WOULD
 NORMALLY BE OBSERVED BY THE BUILDING
 OCCUPANTS OR MAINTENANCE PERSONNEL.
 1107.3 SIZING OF SECONDARY DRAINS.
 SECONDARY (EMERGENCY) ROOF DRAIN SYSTEMS
 SHALL BE SIZED IN ACCORDANCE WITH
 SECTION 1106 BASED ON THE RAINFALL RATE
 FOR WHICH THE PRIMARY SYSTEM IS SIZED IN
 TABLES 1106.2, 1106.3 AND 1106.6.
 SCUPPERS SHALL BE SIZED TO PREVENT THE
 DEPTH OF PONDING WATER FROM EXCEEDING
 THAT FOR WHICH THE ROOF WAS DESIGNED AS
 DETERMINED BY SECTION 1101.7. SCUPPERS
 SHALL NOT HAVE AN OPENING DIMENSION OF
 LESS THAN 4 INCHES (102 MM). THE FLOW
 THROUGH THE PRIMARY SYSTEM SHALL NOT BE
 CONSIDERED WHEN SIZING THE SECONDARY
 ROOF DRAIN SYSTEM.
  
 END OF COMMENTS QUESTIONS 561-805-6692