Plan Review Notes For Permit 05100089
Permit Number 05100089
Review Stop E
Sequence Number 3
Notes
Date Text
2006-09-24 00:00:00********** UNSAT 3RD REVIEW **********
  
 **PLEASE KNOW PLANS ARE BEING SUBMITTED
 FOR "PLAN REVIEW " FOR THE 3RD TIME.
  
 ** PLEASE SEE SOME COMMENTS FROM THE
 PREVIOUS REVIEW HAVE NOT BEEN ADDRESSED
 ANDNEW COMMENTS.
  
  
 1)NOTE: NO, COMPLETE COMPLIANCE WITH THE
 FBC CHAPTER 13 IS NOT YET ACHIEVED.
 PELASE SEE THAT ALL LIGHTING SHALL BE
 AUTOMATICALLY SHUT OFF FOR INTERIOR. NL
 CIRCUIT(S) ARE OK. ).
 PLEASE SEE OVER -RIDES SHALL LOCATED IN
 THE LOCATION OF INGRESS AND EGRES INTO
 SPACES/AREAS AND THE OCCUPANT MUST BE
 ABLE TO SEE ALL LIGHTING IN WHICH IS
 BEING OVER-RIDEN. PLEASE SEE THAT ALL
 OVER TIMES SHALL BE STATED ON PLANS FOR
 THE DEVICES BEING CHOSEN. IF A TIMER
 TYOE OFR OR, THEN 4HRS MAX, IF OCCUPANT
 SENSOR TYOE THEN 30 MINS MAX.
 PLEASE SEE ALSO ALL SEPARATE SPACES WITH
 NFLR TO CEILING HEIGHT PARTITIONS.
 PLEASE SEE MANY AREAS WHICH DO NOT
 CONTAIN THESE OVER RIDES.
 PLEASE SEE NO LIGHTING DENSITES ARE
 SUBMITTED OR INDICATED. PLEASE SEE FORM
 "A" SHOWS "MANUAL" MEANS FOR ALL
 SHUTOFF, WHICH IS NOT THE CASE.
 PLEASE SEE PERFORMANCE CALCULATIONS
 WHICH LIMITS THE WATTAGE USEAGE.
 PLEASE SEE FBC 2004 CHAPTER 13,
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 13-415.1.AB.1 WHICH MENTIONS 415.2, THEN
 SEE 13-415.2, 13-415.2.ABC.1, WHICH
 GIVES TABLES 415.2.C.1, 415.2.B.1
 ** PLEASE KNOW, AS THIS INFORMATION HAS
 NOT YET BEEN SUBMITTED, THIS CANE NOT BE
 REVIEWED.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 NOTE #1 NO, PLEASE SEE THAT THE
 PREVIOUS REVIEW NOTE WAS ALSO FOR
 COMPLIANCE OF THE FBC 2004.
 PLEASE SEE REPSONSE MENTIONS, THE PLANS
 INDICATED 2002 NEC.
 PLEASE SEE FBC 2004, CHAPTER 13
 413.1ABC.1 FOR VOLTAGE DROP CALCS
 REQUIED FOR WORST CASE.
 PLEASE SEE 13-413.1.ABC.2.2
 PLEASE SEE 13-415.1.ABC.1.1 , .2 AND .3
 PLEASE SEE A TIME CLOCK SYSTEM IS BEING
 PROPOSED WITH SWITCHES LOCATED AT THE
 ACCESSIBLE LOCATION, HOWEVER PLEASE
 PROVIDE INFORMATION ON THESE SWITCHES.
 THEY CAN OVER-RIDE NO LONGER THAN 4HRS.
 PLEASE SEE SEPARATE SPACES AND CONTROLS
 REQUIRED.
 ** PLEASE SEE ENERGY CALCS SHEETS ARE
 "RUBBER-STAMPED" WITHE THE ENGINEERS
 SEAL WHICH IS NOT PERMITTED UNDER FS
 471.025. PLEASE ALSO SEE THE WORDING
 "CERTIFICATE" IS NO LONGER PERMITTED IN
 SAID SEALS. PLEASE SEE FAC 61G15-23.001,
 IN A RULING PASSED IN FEB 04, IN WHICH
 THE WORDING "CERTIFICATE" IN SEAL HAD TO
 BE CHANGED TO "LICENSE". THE EXTENSION
 GRANTED WAS TO DEC 31ST,2005. THESE TYOE
 SEALS ARE NO LONGER PERMITTED.
  
 **PREVIOUS NOTE REVIEW #1 **
 PLEASE SEE THAT AS OF OCT 1ST,
 2005 THE STATE OF FLORIDA HAS NOW
 ADOPTED THE 2004 FBC. PLEASE ADJUST ALL
 LOCATIONS AND DESIGNS ON PLANS.
 THIS IS REQUIRED FOR ALL TRADES AND FOR
 ALL TRADES WHETHER OR NOT COMMENTS ARE
 MADE BY OTHER REVIEWER(S).
 PLEASE KNOW, WE ARE CURRENTLY UNDER THE
 2002 NEC WHICH DOES NEED TO BE CHANGED
 ON PLANS.
  
 2)NOTE: NO, PLEASE SEE ELECTRICAL SHEETS
 HAVE NOW HAD THE TITLE BLOCKS REVISED TO
 NOW INCLUDE AN ENGINEERING FIRM. PLEASE
 SEE THESE TITLE BLOCKS FOR ELECTRICAL
 SHEETS ARE REQUIRED TO CONTAIN THE
 PRINTED NAME AND PRINTED LICENSE NUMBER
 OF THE ENGINEER OF RECORD. FAC
 61G15-23.002.
 ** THE RESPONSE LETTER WAS REVIEWED
 WHERE HERSCHMAN DOES NOT BELIEVE THE
 ARCHITECTUARAL FIRM IS REQUIRED TO
 CONTAIN AND CA FOR THE ENGINEERING
 BUSINESS.
 PLEASE KNOW, WHEN THE VALUE AND SCOPE
 RELEVANT TO PROJECT ISINCIDENTAL TO
 THE MAJORITY OF SCOPE AND THE ARCHITECT
 IS QUALIFIED TO DO SCOPE AND SIGNS AND
 SEAL PLANS WHICH DOES NOT REQUIRE AN
 ENGINEER, THIS WOULD BE OK, HOWEVER THIS
 WAS CONFIRMED WITH THE STATE OF
 FLORIDA'S FLORIDA BOARD OF PROFESSIONAL
 ENGINEER'S AS THE PLANS ARE SIGNED,
 DATED AND SEALED BY AN ENGINEER. IF THE
 ENGINEER WORKS FOR HERSCHMAN AND IS
 PROVIDING ENGINEERING SERVICES, THEN A
 CERTIFICATE OF AUTHORIZATION NUMBER IS
 REQUIRED FOR THE FIRM. PLEASE OBTAIN IN
 WRITING FROM THE STATE BOARD AND STATE'S
 LEGAL COUNSEL TO THE BOARD WHERE THIS IS
 NOT REQUIRED ON THIS PROJECT AS THIS IS
 IN DIRECT CONFLICT WITH THE DIRECTION
 GIVEN TO THIS OFFICE BY THE BOARD AND
 LEAGAL COUNSEL.
 WE HAVE ONTACTED THE STATE'S LEGAL
 COUNSEL MORE THAN ONCE FOR THIS.
 ONCE ALL REVIEWS ARE COMPLETE, THE PLANS
 WILL BE RETAINED ANDTURNED OVER TO THE
 STATE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS FOR REVIEW OF THIS AND CODE
 COMPLIANT COMMENTS AS PLANS HAVE BEEN
 SUBMITTED THREE TIMES WITH MANY COMMENTS
 FOR CODE COMPLIANCE NOT ADDRESSED.
  
 ** PREVIOUS REVIEW COMMENTS REVIEW #2**
 NOTE #2 NO, PLEASE SEE THAT SAME
 COMMENT STANDS AS TITLE BLOCKS DO NOT
 CONTAIN THE REQUIRED CA # FOR NEW
 SHEETS. A CA# IS NOW SHOWN ONLY ON
 ARCHITECTURALS WHICH IS VALID FOR THE
 ARCH BUSINESS. PLEASE SEE NOTES BELOW,
 FOR ENGINEERING SERVICES PROVIDED. WE
 HAVE CONFIRMED THIS WITH THE STATE BOARD
 OF ENGINEERS. ONE ROLL OF PLANS ARE
 BEING RETAINED AT THE REQUEST OF THE
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS.
 PLEASE ADDRESS THIS COMMENT FOR ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 THIS COMMENT IS MADE BY ANY OTHER
 TRADES.
  
 ** PREVIOUS NOTE **PLEASE COMPLETE ALL
 TITLE BLOCK INFORMATION FOR MEP PLANS.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 WHICH REQUIRES, THE CERTIFICATE OF
 AUTHORIZATION # ON TITLE BLOCK ALONG
 WITH ALL OTHER INFORMATION AS SET FORTH
 IN FAC 61G15-23.002, AS REQUIRED UNDER
 FS 471.023.
 PLEASE SEE IF FIRM LISTED ON TITLE
 BLOCK, (HERSCHMAN) IS ALSO PRACTICING
 UNDER ENGINEERING, THEN A CA # FOR
 ENGINEERING BUS WOULD ALSO BE REQUIRED.
 PLEASE CALL TO GO OVER THIS IF THERE ARE
 ANY QUESTIONS.
  
 3)NOTE: NOTE #3 OK.
  
 4)NOTE: NOTE #4, OK.
  
 5)NOTE: OK
  
 6)NOTE: NOTE #6 OK.
  
 7)NOTE: OK, HOWEVER PLEASE SEE THAT ALL
 SETS MUST BE SIGNED, DATED AND SEALED.
 PLEASE SEE SHEETS WHICH ARE ONLY
 PHOTO-COPIES. WHICH IS NOT PERMITTED.
 FAC 61G15-23.002, FS 471.025
  
 ** NEW NOTES**
  
 1) NOTE:NO, PLEASE SEE THESE CONTAIN A
 TITLE BLOCK FROM HERSCHMAN AND ARE
 REQUIRED TO BE SIGNED, DATED SEALED. FS
 481.221.
 PLEASE KNOW IF THESE DOCUMNETS WERE NTO
 BE HERSCHMAN, THEN PLEASE REMOVE TITLE
 BLOCKS AND THE PERSON/PERSONS WHO ARE
 RESPONSIBLE FOR SAID PLANS SHALL CLEARLY
 INDICATE ALL THEIR INFORMATIONA AND SIGN
 PLANS. ETC
 FBC 106.1, FS 481, 471, FAC 61G1-16.004,
 61G15-23.002 ETC.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2
 PLEASE SEE PHOTO-METRICS WHICH
 WERE SUBMITTED IN INDIVIDUAL SHEETS IN
 PACKAGE. PLEASE BE SURE THESE SHEETS ARE
 SIGNED, DATED AND SEALED AND INSERTED
 INTO SETS.
  
 2) NOTE: THIS NOTE WILL STAND FOR NEW
 PLANS.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 PLEASE SEE PREVIOUS NOTES FROM
 MORE THAN ONE TRADE WHICH REQUESTED ALL
 OLD/VOIDED SHEETS TO BE REMOVED FROM
 SETS AND ONLY INSERT NEW SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONLY ONE COPY OF THE OLD/VOIDED SHOULD
 BE SUBMITTED SEPARATELY FOR REFERENCE.
  
 ** NEW NOTES 3RD REVIEW **
  
 1) NOTE: PLEASE SEE THAT AN ADDRESS OF
 1552 PALM BEACH LAKES BLVD HAS BEEN
 ASSIGNED TO THIS BUILDING AND PROJECT.
 PLEASE BE SURE THAT ALL SHEETS AND ALL
 TITLE BLOCKS CONTAIN THE CORRECT
 ADDRESS. PLEASE SEE SOME PAPERWORK
 SUBMITTED BACK CONTAINS "1540".
 FAC 61G1-16.004, 61G15-23.002
  
 ** IMPORTANT **
 PLEASW KNOW, MANY COMMENTS ABOVE ARE
 REQUIRED FOR ALL TRADES AND FOR ALL
 SHEETS WHETHER OR NOT COMMENTS ARE MADE
 BY OTHER REVIEWER(S).
  
  
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2006-09-22 00:00:00IN ELEC FOR REVIEW.