| Plan Review Notes For Permit 05100089 |
| Permit Number |
05100089 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-06-08 00:00:00 | ***DENIED*** | | | | | | 1) COMMENT #1&2- PLEASE ADD MINIMUM | | | INTERIOR FINISH CLASSIFICATION NOTE TO | | | THE PLANS THAT IS PERTINENT TO THIS | | | PROJECT. | | | | | | 2) COMMENT #3- RESPONSE INDICATES THAT | | | SHEET A-5 WAS REVISED TO REFLECT THIS | | | REQUIREMENT. NO REVISION WAS FOUND. | | | PLEASE ILLUSTRATE ADDRESS REQUIREMENT ON | | | ELEVATIONS. | | | | | | 3) LIFE SAFETY SHALL COMPLY WITH NFPA | | | 101, 2003 EDITION. | | | | | | 4) 2A-10B,C RATED FIRE EXTINGUISHERS ARE | | | REQUIRED AND SHALL BE MOUNTED NOT TO | | | EXCEED 75'TRAVEL DISTANCE. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|