Plan Review Notes
Plan Review Notes For Permit 05100089
Permit Number 05100089
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2006-06-08 00:00:00***DENIED***
  
 1) COMMENT #1&2- PLEASE ADD MINIMUM
 INTERIOR FINISH CLASSIFICATION NOTE TO
 THE PLANS THAT IS PERTINENT TO THIS
 PROJECT.
  
 2) COMMENT #3- RESPONSE INDICATES THAT
 SHEET A-5 WAS REVISED TO REFLECT THIS
 REQUIREMENT. NO REVISION WAS FOUND.
 PLEASE ILLUSTRATE ADDRESS REQUIREMENT ON
 ELEVATIONS.
  
 3) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION.
  
 4) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED AND SHALL BE MOUNTED NOT TO
 EXCEED 75'TRAVEL DISTANCE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722