Plan Review Notes For Permit 05100089
Permit Number 05100089
Review Stop E
Sequence Number 2
Notes
Date Text
2006-05-18 00:00:00********** UNSAT 2ND REVIEW **********
  
 **PLEASE KNOW PLANS HAVE ONLY BEEN
 SUBMITTED FOR "PLAN REVIEW " FOR THE 2ND
 TIME AND HAVE NOT BEEN SUBMITTED FOR
 PERMIT.
  
 ** PLEASE SEE SOME COMMENTS FROM THE
 PREVIOUS REVIEW HAVE NOT BEEN ADDRESSED
 ANDNEW COMMENT.
  
  
 1)NOTE: NOTE #1 NO, PLEASE SEE THAT THE
 PREVIOUS REVIEW NOTE WAS ALSO FOR
 COMPLIANCE OF THE FBC 2004.
 PLEASE SEE REPSONSE MENTIONS, THE PLANS
 INDICATED 2002 NEC.
 PLEASE SEE FBC 2004, CHAPTER 13
 413.1ABC.1 FOR VOLTAGE DROP CALCS
 REQUIED FOR WORST CASE.
 PLEASE SEE 13-413.1.ABC.2.2
 PLEASE SEE 13-415.1.ABC.1.1 , .2 AND .3
 PLEASE SEE A TIME CLOCK SYSTEM IS BEING
 PROPOSED WITH SWITCHES LOCATED AT THE
 ACCESSIBLE LOCATION, HOWEVER PLEASE
 PROVIDE INFORMATION ON THESE SWITCHES.
 THEY CAN OVER-RIDE NO LONGER THAN 4HRS.
 PLEASE SEE SEPARATE SPACES AND CONTROLS
 REQUIRED.
 ** PLEASE SEE ENERGY CALCS SHEETS ARE
 "RUBBER-STAMPED" WITHE THE ENGINEERS
 SEAL WHICH IS NOT PERMITTED UNDER FS
 471.025. PLEASE ALSO SEE THE WORDING
 "CERTIFICATE" IS NO LONGER PERMITTED IN
 SAID SEALS. PLEASE SEE FAC 61G15-23.001,
 IN A RULING PASSED IN FEB 04, IN WHICH
 THE WORDING "CERTIFICATE" IN SEAL HAD TO
 BE CHANGED TO "LICENSE". THE EXTENSION
 GRANTED WAS TO DEC 31ST,2005. THESE TYOE
 SEALS ARE NO LONGER PERMITTED.
  
  
 **PREVIOUS NOTE**
 PLEASE SEE THAT AS OF OCT 1ST,
 2005 THE STATE OF FLORIDA HAS NOW
 ADOPTED THE 2004 FBC. PLEASE ADJUST ALL
 LOCATIONS AND DESIGNS ON PLANS.
 THIS IS REQUIRED FOR ALL TRADES AND FOR
 ALL TRADES WHETHER OR NOT COMMENTS ARE
 MADE BY OTHER REVIEWER(S).
 PLEASE KNOW, WE ARE CURRENTLY UNDER THE
 2002 NEC WHICH DOES NEED TO BE CHANGED
 ON PLANS.
  
 2)NOTE: NOTE #2 NO, PLEASE SEE THAT SAME
 COMMENT STANDS AS TITLE BLOCKS DO NOT
 CONTAIN THE REQUIRED CA # FOR NEW
 SHEETS. A CA# IS NOW SHOWN ONLY ON
 ARCHITECTURALS WHICH IS VALID FOR THE
 ARCH BUSINESS. PLEASE SEE NOTES BELOW,
 FOR ENGINEERING SERVICES PROVIDED. WE
 HAVE CONFIRMED THIS WITH THE STATE BOARD
 OF ENGINEERS. ONE ROLL OF PLANS ARE
 BEING RETAINED AT THE REQUEST OF THE
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS.
 PLEASE ADDRESS THIS COMMENT FOR ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 THIS COMMENT IS MADE BY ANY OTHER
 TRADES.
  
  
 ** PREVIOUS NOTE **PLEASE COMPLETE ALL
 TITLE BLOCK INFORMATION FOR MEP PLANS.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 WHICH REQUIRES, THE CERTIFICATE OF
 AUTHORIZATION # ON TITLE BLOCK ALONG
 WITH ALL OTHER INFORMATION AS SET FORTH
 IN FAC 61G15-23.002, AS REQUIRED UNDER
 FS 471.023.
 PLEASE SEE IF FIRM LISTED ON TITLE
 BLOCK, (HERSCHMAN) IS ALSO PRACTICING
 UNDER ENGINEERING, THEN A CA # FOR
 ENGINEERING BUS WOULD ALSO BE REQUIRED.
 PLEASE CALL TO GO OVER THIS IF THERE ARE
 ANY QUESTIONS.
  
 3)NOTE: NOTE #3 OK.
  
  
  
 4)NOTE: NOTE #4, PLEASE SEE LOCATION IS
 NOW SHOWN MEETING CLEARENCE REQUIREMENTS
 SEPARATING THIS FROM STORAGE AREA,
 HOWEVER PLEASE SEE NOW IF MAINS ARE
 NEEDED TO BE ACCESSED BY FIRE DEPT
 PERSONNEL IT WOULD APPEAR ONCE INTO THE
 REAR DOOR OF THE BLDG THEY WOULD HAVE TO
 OBTAIN ACCESS BY ANOTHER DOOR( STORAGE)
 WHICH MAY OR MAY NOT BE LOCKED, THEN
 TRAVEL THROUGH A "STORAGE ROOM" TO
 ANOTHER FENCED IN ENCLOSURE WHICH WILL
 ALSO MOST LIKELY BE LOCKED. PLEASE KNOW,
 THIS LOCATION DOES NOT SEEM TO BE
 READILY ACCESSIBLE FOR MEANS OF SHUTTING
 DOWN ELECTRICAL. 230.70,110.26 100,90.4.
 THIS HAS BEEN CONFIRMED WITH THE FIRE
 MARSHAL'S OFFICE AND SUCH LOCATION WOULD
 NOT BE ACCEPTABLE. PLEASE ADJUST ROOM/
 ELECTRICAL MAINS ACCESSIBILITY.
 THIS WAS DISCUSSED AS THIS AREA COULD BE
 CLOSED IN BY PARITIIONS, HOWEVER THIS
 ACCESS SHOULD BE MADE CLOSER TO THE
 BUILDING REAR ACCESS/ ENTRANCE DOOR.
  
  
 ** PREVIOUS NOTE **
 PLEASE VERIFY LOCATION FOR
 SERVICE EQUIPMENT. PLEASE SEE
 408.7,240.24,110.26
 IT APPEARS TO SHOW EQUIPMENT IN A
 "STORAGE ROOM" WHICH WOULD NOT BE
 PERMITTED.
 A PARTIONED AREA AROUND THIS EQUIPMENT
 MEETING WIDTH AND HEIGHT REQUIREMENT AS
 LISTED IN 110.26, WOULD BE PERMITTED TO
 MAINTAIN CLEARENCES, AND KEEP OCP AWAY
 FROM COMBUSTIBLES AND EASILY IGNITIBLE
 MATERIALS.
  
 5)NOTE: OK
  
 6)NOTE: NOTE #6 NO, THIS COULD NOT BE
 LOCATED ON PLANS?? PLEASE SEE NEW NOTE
 FOR PHOTO-METRICS.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE WIND LOAD
 CALCUALTIONS FOR SITE LIGHTING POLES ,
 INCLUDING FIXTURE ATTACHED TO POLES.
 PLEASE KNOW THESE CALCUALTIONS ARE DUE
 IF PERMITTING WITH MAIN BUILDING.
 PLEASE ALSO KNOW, ALL CALCS TO MEET THE
 MIN FBC 140 MPH.
  
 7)NOTE: OK
  
 ** NEW NOTES**
  
 1) NOTE: PLEASE SEE PHOTO-METRICS WHICH
 WERE SUBMITTED IN INDIVIDUAL SHEETS IN
 PACKAGE. PLEASE BE SURE THESE SHEETS ARE
 SIGNED, DATED AND SEALED AND INSERTED
 INTO SETS.
  
 2) NOTE: PLEASE SEE PREVIOUS NOTES FROM
 MORE THAN ONE TRADE WHICH REQUESTED ALL
 OLD/VOIDED SHEETS TO BE REMOVED FROM
 SETS AND ONLY INSERT NEW SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONLY ONE COPY OF THE OLD/VOIDED SHOULD
 BE SUBMITTED SEPARATELY FOR REFERENCE.
  
  
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 FROM SETS AND ONLYINSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW ALONG WITH PERMIT APPLICATION. IF
 THERE ARE ANY QUESTIONS, PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
2006-05-17 00:00:00IN ELEC FOR REVIEW
 PLANS WILL GO TO A "F" STATUS, REVIEW
 COMPLETED. NOTES TO FOLLOW ON 5/18
 NOTES ON 5/18