Plan Review Notes
Plan Review Notes For Permit 05100089
Permit Number 05100089
Review Stop M
Sequence Number 1
Notes
Date Text
2005-12-05 00:00:00------------------DENIED----------------
 NOTE: ALL CODE SECTIONS CITED REFER TO
 THE FLORIDA BUILDING CODE, MECHANICAL
 2004 EDITION.
  
 1) PAGE MP1.0: PLAN SHOWS 900 CFM OF
 SUPPLY INTO BACK ROOM.THIS REQUIRES A
 MIN. OF 450 SQ. IN. TOTAL AREA OF
 TRANSFER GRILLS TO ACHIEVE BALANCED
 RETURN PER 601.4.PLAN SHOWS (2) 18X10
 TGS WITH TOTAL 360 SQ IN.
  
 2) PAGE MP1.0: PLAN INDICATES MANUAL
 VOLUME DAMPERS IN 18" ROUND AND 24"
 ROUND DOUBLE-WALL LINED DUCTS.IS THERE
 AN APPROVED PRODUCT FOR THIS APPLICATION
 OR WILL THE DAMPERS BE RELOACTED?
  
 3) PAGE MP3.0 MECHANICAL SPECIFICATIONS:
 DUCT SMOKE DETECTORS SHALL BE CONNECTED
 TO THE BUILDING FIRE ALARM SYSTEM, IF
 APPLICABLE, OR SHALL ACTIVATE AN
 AUDIBLE/VISIBLE NOTIFICATION DEVICE
 (HORN/STROBE) IN AN APPROVED LOCATION
 PER 606.4.1.
  
 4) PLEASE INDICATE LOCATION OF
 CONDENSATE DISPOSAL TO ENSURE COMPLIANCE
 WITH FBC,M 307.2.1.
  
 5) AUXILIARY DRAIN PROTECTION IS
 REQUIRED FOR ROOFTOP PACKAGE UNITS PER
 307.2.3.THIS MAY BE ACHIEVED VIA A
 WATER-LEVEL DETECTION DEVICE IN THE
 UNIT'S PRIMARY DRAIN PAN TO SHUT-DOWN
 THE UNIT PRIOR TO OVERFLOW INTO THE
 SPACE BELOW.
  
 6) WHEN EQUIPMENT REQUIRING ACCESS IS
 INSTALLED ON A ROOF AT A HEIGHT
 EXCEEDING 16', ACCES SHALL BE PROVIDED
 BY PERMANENT APPROVED MEANS IN
 ACCORDANCE WITH 306.5
  
 PLEASE CALL RON REGUEIRO AT 561.805.6734
 OR PATTY KRAUS AT 561.805.6719 IF YOU
 HAVE ANY QUESTIONS.