| 2005-12-24 00:00:00 | ********** UNSAT ********** |
| | |
| | PLEASE SEE PLANS HAVE ONLY BEEN |
| | SUBMITTED FOR "PLAN REVIEW " ONLY AND |
| | HAVE NOT BEEN SUBMITTED FOR PERMIT. |
| | |
| | |
| | 1)NOTE: PLEASE SEE THAT AS OF OCT 1ST, |
| | 2005 THE STATE OF FLORIDA HAS NOW |
| | ADOPTED THE 2004 FBC. PLEASE ADJUST ALL |
| | LOCATIONS AND DESIGNS ON PLANS. |
| | THIS IS REQUIRED FOR ALL TRADES AND FOR |
| | ALL TRADES WHETHER OR NOT COMMENTS ARE |
| | MADE BY OTHER REVIEWER(S). |
| | PLEASE KNOW, WE ARE CURRENTLY UNDER THE |
| | 2002 NEC WHICH DOES NEED TO BE CHANGED |
| | ON PLANS. |
| | |
| | 2)NOTE:PLEASE COMPLETE ALL TITLE BLOCK |
| | INFORMATION FOR MEP PLANS. |
| | PLEASE SEE FLORIDA ADMINISTRATIVE CODE |
| | WHICH REQUIRES, THE CERTIFICATE OF |
| | AUTHORIZATION # ON TITLE BLOCK ALONG |
| | WITH ALL OTHER INFORMATION AS SET FORTH |
| | IN FAC 61G15-23.002, AS REQUIRED UNDER |
| | FS 471.023. |
| | PLEASE SEE IF FIRM LISTED ON TITLE |
| | BLOCK, (HERSCHMAN) IS ALSO PRACTICING |
| | UNDER ENGINEERING, THEN A CA # FOR |
| | ENGINEERING BUS WOULD ALSO BE REQUIRED. |
| | PLEASE CALL TO GO OVER THIS IF THERE ARE |
| | ANY QUESTIONS. |
| | |
| | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | PLEASE KNOW, IT IS KNOWN THAT THE AIC |
| | RATINGS ARE INDICATED FOR THE PANELS A |
| | AND B. JUST NEED MAIN DISCAND TWO 80 A |
| | MCB DISCONNECTS. |
| | |
| | 4)NOTE: PLEASE VERIFY LOCATION FOR |
| | SERVICE EQUIPMENT. PLEASE SEE |
| | 408.7,240.24,110.26 |
| | IT APPEARS TO SHOW EQUIPMENT IN A |
| | "STORAGE ROOM" WHICH WOULD NOT BE |
| | PERMITTED. |
| | A PARTIONED AREA AROUND THIS EQUIPMENT |
| | MEETING WIDTH AND HEIGHT REQUIREMENT AS |
| | LISTED IN 110.26, WOULD BE PERMITTED TO |
| | MAINTAIN CLEARENCES, AND KEEP OCP AWAY |
| | FROM COMBUSTIBLES AND EASILY IGNITIBLE |
| | MATERIALS. |
| | |
| | 5)NOTE: PLEASE SEE COLOR CODING FOR |
| | 277/480 SHALL BE BROWN , PURPLE, YELLOW, |
| | AS 277/480 DOES NOT CONTAIN A "HIGH-LEG" |
| | AS LISTED IN WHICH THE NEC DOES REQUIRE |
| | "ORANGE". |
| | ELECTRICAL SYSTEM FOR THIS PROJECT DOES |
| | NOT APPEAR TO SHOW ANY 277/480V SYSTEMS, |
| | THEREFORE THE GENERAL NOT ON E-5 CAN BE |
| | REMOVED. |
| | |
| | 6)NOTE: PLEASE PROVIDE WIND LOAD |
| | CALCUALTIONS FOR SITE LIGHTING POLES , |
| | INCLUDING FIXTURE ATTACHED TO POLES. |
| | PLEASE KNOW THESE CALCUALTIONS ARE DUE |
| | IF PERMITTING WITH MAIN BUILDING. |
| | PLEASE ALSO KNOW, ALL CALCS TO MEET THE |
| | MIN FBC 140 MPH. |
| | |
| | 7)NOTE: PLEASE ALSO INCLUDE THE FOOTER |
| | STEEL IN THE MAIN GROUNDING ELECTRODE |
| | SYSTEM. |
| | 250.50. |
| | |
| | ** PLEASE SEE ANY OTHER COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | FROM SETS AND ONLYINSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | |
| | ** PLEASE KNOW, THIS WAS FOR PLAN REVIEW |
| | ONLY. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW ALONG WITH PERMIT APPLICATION. IF |
| | THERE ARE ANY QUESTIONS, PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. |
| | |
| | |