Plan Review Notes
Plan Review Notes For Permit 05100089
Permit Number 05100089
Review Stop E
Sequence Number 1
Notes
Date Text
2005-12-24 00:00:00********** UNSAT **********
  
 PLEASE SEE PLANS HAVE ONLY BEEN
 SUBMITTED FOR "PLAN REVIEW " ONLY AND
 HAVE NOT BEEN SUBMITTED FOR PERMIT.
  
  
 1)NOTE: PLEASE SEE THAT AS OF OCT 1ST,
 2005 THE STATE OF FLORIDA HAS NOW
 ADOPTED THE 2004 FBC. PLEASE ADJUST ALL
 LOCATIONS AND DESIGNS ON PLANS.
 THIS IS REQUIRED FOR ALL TRADES AND FOR
 ALL TRADES WHETHER OR NOT COMMENTS ARE
 MADE BY OTHER REVIEWER(S).
 PLEASE KNOW, WE ARE CURRENTLY UNDER THE
 2002 NEC WHICH DOES NEED TO BE CHANGED
 ON PLANS.
  
 2)NOTE:PLEASE COMPLETE ALL TITLE BLOCK
 INFORMATION FOR MEP PLANS.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 WHICH REQUIRES, THE CERTIFICATE OF
 AUTHORIZATION # ON TITLE BLOCK ALONG
 WITH ALL OTHER INFORMATION AS SET FORTH
 IN FAC 61G15-23.002, AS REQUIRED UNDER
 FS 471.023.
 PLEASE SEE IF FIRM LISTED ON TITLE
 BLOCK, (HERSCHMAN) IS ALSO PRACTICING
 UNDER ENGINEERING, THEN A CA # FOR
 ENGINEERING BUS WOULD ALSO BE REQUIRED.
 PLEASE CALL TO GO OVER THIS IF THERE ARE
 ANY QUESTIONS.
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 PLEASE KNOW, IT IS KNOWN THAT THE AIC
 RATINGS ARE INDICATED FOR THE PANELS A
 AND B. JUST NEED MAIN DISCAND TWO 80 A
 MCB DISCONNECTS.
  
 4)NOTE: PLEASE VERIFY LOCATION FOR
 SERVICE EQUIPMENT. PLEASE SEE
 408.7,240.24,110.26
 IT APPEARS TO SHOW EQUIPMENT IN A
 "STORAGE ROOM" WHICH WOULD NOT BE
 PERMITTED.
 A PARTIONED AREA AROUND THIS EQUIPMENT
 MEETING WIDTH AND HEIGHT REQUIREMENT AS
 LISTED IN 110.26, WOULD BE PERMITTED TO
 MAINTAIN CLEARENCES, AND KEEP OCP AWAY
 FROM COMBUSTIBLES AND EASILY IGNITIBLE
 MATERIALS.
  
 5)NOTE: PLEASE SEE COLOR CODING FOR
 277/480 SHALL BE BROWN , PURPLE, YELLOW,
 AS 277/480 DOES NOT CONTAIN A "HIGH-LEG"
 AS LISTED IN WHICH THE NEC DOES REQUIRE
 "ORANGE".
 ELECTRICAL SYSTEM FOR THIS PROJECT DOES
 NOT APPEAR TO SHOW ANY 277/480V SYSTEMS,
 THEREFORE THE GENERAL NOT ON E-5 CAN BE
 REMOVED.
  
 6)NOTE: PLEASE PROVIDE WIND LOAD
 CALCUALTIONS FOR SITE LIGHTING POLES ,
 INCLUDING FIXTURE ATTACHED TO POLES.
 PLEASE KNOW THESE CALCUALTIONS ARE DUE
 IF PERMITTING WITH MAIN BUILDING.
 PLEASE ALSO KNOW, ALL CALCS TO MEET THE
 MIN FBC 140 MPH.
  
 7)NOTE: PLEASE ALSO INCLUDE THE FOOTER
 STEEL IN THE MAIN GROUNDING ELECTRODE
 SYSTEM.
 250.50.
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 FROM SETS AND ONLYINSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 ** PLEASE KNOW, THIS WAS FOR PLAN REVIEW
 ONLY.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW ALONG WITH PERMIT APPLICATION. IF
 THERE ARE ANY QUESTIONS, PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  