| 2006-03-01 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05100089 |
| | ADD: 1540 P B LAKES BLVD |
| | CONT: "PLAN REVIEW" |
| | RETAIL PROPERTY INVESTORS, |
| | |
| | LLC |
| | TEL: (301)479-3248 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |
| | 1) SEE ADDRESSING CONTACT LILI URSA AT |
| | (561)822-1239 FOR APPROVED ADDRESS AND |
| | SUBMIT REPLAT. |
| | |
| | 2) SUBMIT SURVEY WITH PROPOSED BUILDING |
| | ON SURVEY. |
| | |
| | 3) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | NOTE RECORDED NOC IF WORK HAS NOT |
| | STARTED WITHIN 90 DAYS OF RECORDING, NOC |
| | BECOMES NULL AND VOID REQUIRING |
| | RE-RECODING. FL S S 713.13(2) |
| | |
| | 4)SHEET C-3 INDICATES ONLY 2 HANDICAPPED |
| | SPOTS WHILE 3 ARE REQUIRED.11-4.1.2(5) |
| | PARKING SPACES: |
| | (A)IF PARKING SPACES ARE PROVIDED FOR |
| | SELF-PARKING BY EMPLOYEES OR VISITORS, |
| | OR BOTH, THEN ACCESSIBLE SPACES |
| | COMPLYING WITH SECTION 11-4.6 SHALL BE |
| | PROVIDED IN EACH SUCH PARKING AREA. SUCH |
| | SPACES SHALL BE DESIGNED AND MARKED FOR |
| | EXCLUSIVE USE OF THOSE INDIVIDUALS WHO |
| | HAVE A SEVERE PHYSICAL DISABILITY AND |
| | HAVE PERMANENT OR TEMPORARY MOBILITY |
| | PROBLEMS THAT SUBSTANTIALLY IMPAIR THEIR |
| | ABILITY TO AMBULATE AND WHO HAVE BEEN |
| | ISSUED EITHER A DISABLED PARKING PERMIT |
| | UNDER SECTION 316.1958 OR 320.0848, |
| | FLORIDA STATUTES, OR A LICENSE PLATE |
| | UNDER SECTION 320.084, 320.0842, |
| | 320.0843, OR 320.0845, FLORIDA STATUTES. |
| | THE NUMBER OF ACCESSIBLE PARKING SPACES |
| | SHALL COMPLY WITH THE TABLE BELOW AND |
| | THE FOLLOWING: |
| | |
| | TOTAL PARKING IN LOT |
| | REQUIRED MINIMUM NUMBER OF ACCESSIBLE |
| | SPACES |
| | 1 TO 251 |
| | 26 TO 502 |
| | 51 TO 753 |
| | |
| | 5)SHEET C-3 SHOW COMPLICANCE WITH |
| | 11-4.1.2(1) |
| | AT LEAST ONE ACCESSIBLE ROUTE COMPLYING |
| | WITH SECTION 11-4.3 SHALL BE PROVIDED |
| | WITHIN THE BOUNDARY OF THE SITE FROM |
| | PUBLIC TRANSPORTATION STOPS, ACCESSIBLE |
| | PARKING SPACES, PASSENGER LOADING ZONES |
| | IF PROVIDED, AND PUBLIC STREETS OR |
| | SIDEWALKS, TO AN ACCESSIBLE BUILDING |
| | ENTRANCE. |
| | |
| | 6) SHEET AA INDICATES THE WRONG CODE, |
| | OCT 1, 2006 PLANS SUBMITTED ON THIS DATE |
| | AND AFTER WILL BE REVIEWED UNDER THE |
| | 2004 FL BUILDING CODE. NOTE, IF PLANS |
| | SUBMITTED BEFORE THIS DATE UNDER PLAN |
| | REVIEW AND NO PERMIT APPLICATION WAS |
| | APPLIED FOR BEFORE OCT 1, 2006, THE |
| | PROJECT WILL NEED TO BE RE-REVIEWED |
| | UNDER THE 2004 FBC. |
| | |
| | 7) 109.3.10* IMPACT OF CONSTRUCTION. ALL |
| | CONSTRUCTION ACTIVITY REGULATED BY THIS |
| | CODE SHALL BE PERMORMED IN A MANNER SO |
| | AS NOT TO ADVERSLY IMPACT THE CONDITION |
| | OF ADJACENT PROPERTY, UNLESS SUCH |
| | ACTIVITY IS PERMITTED TO AFFECT SAID |
| | PROPERTY PURSUANT TO A CONSENT BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS & |
| | CONDITIONS AGREEABLE TO THE APPLICABLE |
| | PROPERTY OWNER.THIS INCLUDES BUT IS NOT |
| | LIMITED TO THE CONTROL OF DUST, NOISE, |
| | WATER OR DRAINAGE RUN-OFF, DEBRIS, AND |
| | THE STORAGE OF CONSTRUCTION MATERIALS. |
| | NEW CONSTRUCTION ACTIVITY SHALL NOT |
| | ADVERSELY IMPACT HISTORICSURFACE WATER |
| | DRAINAGE FLOWS SERVING ADJACENT |
| | PROPERTIES, & MAY REQUIRE SPECIAL |
| | DRAINAGE DESIGNCOMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED |
| | SITES.ACCORDINGLY, DEVELOPERS, |
| | CONTRACTORS, AND OWNERS OF ALL NEW |
| | RESIDENTIAL DEVELOPMENET, INCLUDING |
| | ADDITIONS, POOLS, PATIOS, DRIVEWAYS, |
| | DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN |
| | EXCESS OF 800SQ FT OF PERMEABLE LAND |
| | AREA ON ANY PARCELL SHALL AS A PERMIT |
| | CONDITION, PROVIDE A PROFESSIONALY |
| | PREPARED DRAINAGE PLAN CLEARLY |
| | INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE |
| | IMPROVEMENT, A CERTIFICATE FROM A |
| | LICENSED ENGINEER SHALL BE SUBMITTED TO |
| | THE INSPECTOR IN ORDER TO RECEIVE |
| | APPROVAL OF THE FINAL INSPECTION. |
| | |
| | 8) 109.3.10.1 HURICANE PROTECTION. |
| | IT SHALL BE UNLAWFUL FOR ANY PERSON TO |
| | ALLOW CONSTRUCTION RELATED MATERIALS |
| | EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION |
| | SITE FROM 24 HRS. AFTER A HURRICANE |
| | WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN |
| | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, |
| | EQUIPMENT AND DEBRIS SHALL BE EITHER |
| | REMOVED FROM THE CONSTRUCTION SITE OR |
| | SECURED IN SUCH A MANNER AS TO MINIMIZE |
| | THE DANGER OF SUCH CONSTRUCTION |
| | MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM |
| | HIGHWINDS. |
| | ANY PERSONS WHO FAILS TO COMPLY TO |
| | REMOVE OR SECURE THE CONSTRUCTION |
| | MATERIALS EQUIPMENT AND DEBRIS WITHIN |
| | 24 HRS AFTER A HURRICANE WATCH HAS BEEN |
| | ISSUED SHALL BE SUBJECT TO A FINE NOT TO |
| | EXCEED $500.00. |
| | IN ADDITION TO THE ABOVE, A LICENSED |
| | CONTRACTOR WHO VIOLATES THIS SECTION |
| | SHALL BE SUBJECT TO DISCIPLINE PURSUANT |
| | TO SECTION 113 OF THIS CHAPTER. |
| | |
| | 9) 110.2* W. P. B. ADMINISTRATIVE CODE, |
| | INFORMATION THAT IS REQUIRED FOR RECORD |
| | KEEPING & FOR CERTIFICATE OF OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | |
| | 10) 1609.1.4 PROTECTION OF OPENINGS. |
| | IN WIND-BORNE DEBRIS REGIONS, EXTERIOR |
| | GLAZING THAT RECEIVES POSITIVE PRESSURE |
| | IN THE LOWER 60 FEET (18.3 M) IN |
| | BUILDINGS SHALL BE ASSUMED TO BE |
| | OPENINGS AND THE BALANCE OF GLAZED |
| | OPENINGS IN THE REST OF THE BUILDING |
| | SHALL BE ASSUMED TO BE ZERO UNLESS SUCH |
| | GLAZING THAT RECEIVES POSITIVE PRESSURE |
| | IS IMPACT RESISTANT OR PROTECTED WITH AN |
| | IMPACT RESISTANT COVERING MEETING THE |
| | REQUIREMENTS OF SSTD 12, ASTM E 1886 AND |
| | ASTM E 1996, OR MIAMI-DADE TAS 201, 202 |
| | AND 203 REFERENCED THEREIN AS FOLLOWS: |
| | 1.GLAZED OPENINGS LOCATED WITHIN 30 |
| | FEET (9.1 M) OF GRADE SHALL MEET THE |
| | REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2.GLAZED OPENINGS LOCATED MORE THAN |
| | 30 FEET (9.1 M) ABOVE GRADE SHALL MEET |
| | THE PROVISIONS OF THE SMALL MISSILE |
| | TEST. |
| | |
| | 11) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) METAL EXTERIOR DOORS |
| | B) GLAZED DOORS |
| | C) WINDOWS |
| | D) MULLIONS |
| | E) EFIS SYSTEMS AND COMPONENTS |
| | F) AWNINGS |
| | G) ROOFING ASSEMBLIES |
| | FLAT ROOF MEMBRANE |
| | INSULATION |
| | UNDERLAYMENT |
| | TILE |
| | |
| | 12) FABRIC AWNINGS: |
| | 3105.4.1 |
| | DESIGN OF THE FRAMING MEMBERS SHALL NOT |
| | BE BASED ON REMOVAL OR REPOSITIONING OF |
| | PARTS, OR THE WHOLE, DURING PERIODS OF |
| | 75 MPH WIND VELOCITY. |
| | |
| | 3105.4.2 |
| | DESIGN OF THE STRUCTURAL FRAMING MEMBERS |
| | SHALL BE BASED ON RATIONAL ANALYSIS, |
| | USING THE APPLICABLE WIND LOADS OF |
| | CHAPTER 16 AS SHOWN BELOW: |
| | |
| | 3105.4.2.1 |
| | THE WIND DESIGN LOADS FOR ANY FABRIC OR |
| | MEMBRANE-COVERED STRUCTURE DESIGNED WITH |
| | A QUICK REMOVAL OR BREAKAWAY MEMBRANE OR |
| | FABRIC AT WIND VELOCITIES OF 75 MPH, |
| | SHALL BE BASED ON THE FOLLOWING |
| | CRITERIA: |
| | 1.MINIMUM WIND VELOCITY OF 3-SECOND |
| | WIND GUST 90 MPH |
| | 2.IMPORTANCE FACTOR BASED ON LOW |
| | HAZARD TO HUMAN LIFE OF 0.77. |
| | 3.EXPOSURE CATEGORY B FOR OR C AS |
| | DEFINED IN CHAPTER 16 . |
| | |
| | 3105.4.2.2 |
| | THE WIND DESIGN LOADS FOR ANY FABRIC OR |
| | MEMBRANE COVERED STRUCTURE DESIGNED WITH |
| | A PERMANENT OR NONREMOVABLE FABRIC OR |
| | MEMBRANE, SHALL BE BASED ON THE |
| | FOLLOWING CRITERIA: |
| | 1.MINIMUM WIND VELOCITY AS REQUIRED |
| | IN CHAPTER 16 . |
| | 2.IMPORTANCE FACTOR BASED ON LOW |
| | HAZARD TO HUMAN LIFE OF 0.77. |
| | 3.EXPOSURE CATEGORY B OR C AS |
| | DEFINED IN CHAPTER 16 . |
| | |
| | 3105.4.2 |
| | THE FABRIC PORTIONS OF AWNINGS FABRIC |
| | COVERED FRAMES SHALL BE SECURELY LACED, |
| | TIED OR OTHERWISE FASTENED TO THE FRAME; |
| | NO RAFTER OR FRONT BAR WILL BE PERMITTED |
| | IN POCKETS; AND IN NO CASE SHALL A |
| | ROLLING CURTAIN BE CAUSED TO OPERATE |
| | OVER A CANOPY FRAME. |
| | |
| | 3105.4.3 |
| | THE HORIZONTAL PROJECTION OF |
| | CANTILEVERED PORTIONS SHALL NOT BE |
| | GREATER THAN TWO TIMES THE HEIGHT, |
| | EXCEPT WHERE THE BUILDING CONSTRUCTION |
| | DOES NOT PERMIT A PROPER INSTALLATION; |
| | IN WHICH CASE, VARIANCE MAY BE PERMITTED |
| | BY THE BUILDING OFFICIAL, BASED ON |
| | SPECIAL DESIGN AND CONSTRUCTION. |
| | |
| | 13) CONCENTRATED LOADS PROVIDE |
| | INFORMATION ON THE CONCENTRATED LOADS OF |
| | THE AIR HANDLERS ON THE ROOF ABOVE THE |
| | BAR JOIST.1607.4 CONCENTRATED LOADS . |
| | FLOORS AND OTHER SIMILAR SURFACES SHALL |
| | BE DESIGNED TO SUPPORT THE UNIFORMLY |
| | DISTRIBUTED LIVE LOADS PRESCRIBED IN |
| | SECTION 1607.3 OR THE CONCENTRATED LOAD, |
| | IN POUNDS (KILONEWTONS), GIVEN IN TABLE |
| | 1607.1 , WHICHEVER PRODUCES THE GREATER |
| | LOAD EFFECTS. UNLESS OTHERWISE |
| | SPECIFIED, THE INDICATED CONCENTRATION |
| | SHALL BE ASSUMED TO BE UNIFORMLY |
| | DISTRIBUTED OVER AN AREA 2.5 FEET BY 2.5 |
| | FEET [6.25 FT 2 (0.58 M 2 )] AND SHALL |
| | BE LOCATED SO AS TO PRODUCE THE MAXIMUM |
| | LOAD EFFECTS IN THE STRUCTURAL MEMBERS. |
| | |
| | 14) PROVIDE INFORMATION ON ATTACHMENT OF |
| | THE ROOF TOP AIR HANDLERS TO THE ROOF |
| | DECK. ADDITIONAL INFORMATION. |
| | |
| | 15) NOTE PROVIDE THE EFIS PRODUCT |
| | APPROVAL REPORT, ALSO PROVIDE |
| | INFORMATION ON EFIS FOR HORIZONTAL |
| | APPLICATION. |
| | |
| | 16) ENGINEER TO SIGN AND SEAL PLANS SO |
| | SEAL IS VISIBLE. |
| | PLANS, SPECIFICATIONS,REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | |
| | 17) SEAL IS UNREADABLE STAMPED OVER THE |
| | ENGINEERS HEADER. NOTE PLANS SUBMITTED |
| | AFTER 01-01-06 FOR PERMIT APPLICATION |
| | SHALL HAVE THE WORD "LICENSE" RATHER |
| | THAN CERTIFICATE ON THE EMBOSSED SEAL. |
| | RULE 61G15-23.001(1) |
| | |
| | 18) SHEET S.01 REVISE PLANS TO THE 2004 |
| | FBC. |
| | |
| | 19) SHEET S.30 DETAIL 1 INDICATES USE OF |
| | PLYWOOD SHEETHING, SEE TABLE 601 |
| | FOOTNOTE (2). |
| | IN TYPE I AND II CONSTRUCTION, |
| | FIRE-RETARDANT-TREATED WOOD SHALL BE |
| | ALLOWED IN BUILDINGS INCLUDING GIRDERS |
| | AND TRUSSES AS PART OF THE ROOF |
| | CONSTRUCTION WHEN THE BUILDING IS: |
| | I. TWO STORIES OR LESS IN HEIGHT; |
| | II. TYPE II CONSTRUCTION OVER TWO |
| | STORIES; OR |
| | III. TYPE I CONSTRUCTION OVER TWO |
| | STORIES AND THE VERTICAL DISTANCE FROM |
| | THE UPPER FLOOR TO THE ROOF IS 20 FEET |
| | OR MORE. |
| | |
| | 20) SUBMIT GEOTECH REPORT: |
| | 1802.2.1 QUESTIONABLE SOIL. |
| | WHERE THE SAFE-SUSTAINING POWER OF THE |
| | SOIL IS IN DOUBT, OR WHERE A |
| | LOAD-BEARING VALUE SUPERIOR TO THAT |
| | SPECIFIED IN THIS CODE IS CLAIMED, THE |
| | BUILDING OFFICIAL SHALL REQUIRE THAT THE |
| | NECESSARY INVESTIGATION BE MADE. SUCH |
| | INVESTIGATION SHALL COMPLY WITH THE |
| | PROVISIONS OF SECTIONS 1802.4 THROUGH |
| | 1802.6 . |
| | |
| | 21) SHEET S.20 BAASE PLATE MISSING SIZE |
| | OF WELD COLUMN TO BASE PLATE. |
| | |
| | 22) BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | 1609.1.4 PROTECTION OF OPENINGS. |
| | IN WIND-BORNE DEBRIS REGIONS, EXTERIOR |
| | GLAZING THAT RECEIVES POSITIVE PRESSURE |
| | IN THE LOWER 60 FEET (18.3 M) IN |
| | BUILDINGS SHALL BE ASSUMED TO BE |
| | OPENINGS AND THE BALANCE OF GLAZED |
| | OPENINGS IN THE REST OF THE BUILDING |
| | SHALL BE ASSUMED TO BE ZERO UNLESS SUCH |
| | GLAZING THAT RECEIVES POSITIVE PRESSURE |
| | IS IMPACT RESISTANT OR PROTECTED WITH AN |
| | IMPACT RESISTANT COVERING MEETING THE |
| | REQUIREMENTS OF SSTD 12, ASTM E 1886 AND |
| | ASTM E 1996, OR MIAMI-DADE TAS 201, 202 |
| | AND 203 REFERENCED THEREIN AS FOLLOWS: |
| | 1.GLAZED OPENINGS LOCATED WITHIN 30 |
| | FEET (9.1 M) OF GRADE SHALL MEET THE |
| | REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2.GLAZED OPENINGS LOCATED MORE THAN |
| | 30 FEET (9.1 M) ABOVE GRADE SHALL MEET |
| | THE PROVISIONS OF THE SMALL MISSILE |
| | TEST. |
| | ) 106.3.3* PRODUCT APPROVALS- 2004 |
| | THOSE PRODUCTS THAT ARE RGULATED BY DCA |
| | RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITTING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |