| Plan Review Notes For Permit 05100079 |
| Permit Number |
05100079 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-10-05 00:00:00 | DENIED; | | | 1.DRINKING FOUNTAIN REQUIRED. FBC-2004 | | | PLUMBING TABLE 403.1 | | | 2.WHERE ARE BATHROOM FACILITIES FOR | | | WOMAN? | | | 3.SANITARY RISER DIAGRAM KITCHEN SINK | | | NOT VENTED. | | | 4.WATER RISER DIAGRAM; WATER HAMMER | | | ARRESTORS TO BE INSTALLED PER. | | | MANUFACTORS SPEC'S. ( AS CLOSE TO SOURCE | | | OF WATER HAMMER) MOVE TO BOTTOM OF | | | DROPS. | | | 5.WATER HEATER DETAIL; SHOW HOW IT WILL | | | BE PIPED TO OUTSIDE. | | | 6.WATER HEATER DETAIL; SHOW THERMAL | | | EXPANSION CONTROL. SEC. 607.3. | | | 7.ONE OF THE KITCHEN SINKS SHALL MEET | | | HANDICAP REQUIRMENTS. (SHOW DETAIL ) | | | MUST COMPLY WITH FBC-2004 CHAPTER 11 | | | SEC. 11-4.23.1 THRU 11-4.23.7. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|