| Notes |
| Date |
Text |
| 2005-12-23 00:00:00 | **** REDLINED PLANS***** | | | | | | PLEASE SEE NEW REVISED E2-1 SHOWS | | | TRANSFORMER AND PANELS BEING RELOCATED | | | TO HALL WAY AND ABOVE CEILING, HOWEVER | | | PLEASE SEE E1.1 WAS NOT REVISED. | | | | | | PLEASE SEE GROUNDING ATTACHMENT LOCATION | | | FOR TRANSFORMER NOT SHOWN, MUST CONNECT | | | TO EXISTING GROUNDING ELECTRODE SYSTEM. | | | 250.30 |
|