| 2006-02-08 00:00:00 | ******** UNSAT 3RD REVIEW ********** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | TWO REVIEWS ARE NOT ADDRESSED. |
| | PLEASE SEE NEW NOTE FOR CHANGE IN PLANS. |
| | PLEASE SEE NOTES BELOW WHICH ARE |
| | DIRECTLY TAKEN FROM PREVIOUS REVIEW. |
| | |
| | *** UNSAT 2ND REVIEW *** |
| | |
| | PLEASE SEES SOME NOTES FROM PREVIOUS |
| | REVEW STILL NEED TO BE ADDRESSED. |
| | PLEASE SEE BELOW NOTES ARE TAKEN |
| | DIRECTLY FROM THOSE NOTES. |
| | |
| | 1)NOTE: OK |
| | |
| | 2)NOTE: OK |
| | |
| | 3)NOTE:NO. PLEASE SEE PANEL SCHEDULES |
| | OR LOAD CALCUALTIONS DO NOT INDICATE ANY |
| | CONTINUOUS OR LARGEST MOTOR LOADS?? |
| | |
| | ** NOTE #3 NO, PLEASE SEE THAT ALL |
| | CONTINUOUS LOADS AND LARGEST MOTOR LOADS |
| | ARE SHOWN AT 125%. |
| | 215.3,230.42 ETC. |
| | |
| | 4)NOTE: OK |
| | |
| | 5)NOTE: OK |
| | |
| | 6)NOTE: NOTE #6 NO, PLEASE SUBMIT AIC |
| | RATINGS FOR ALL NEW SERVICE EQUIPMENT |
| | BEING INSTALLED. MAINS/BRKRS AND PANELS |
| | ARE ALL TO BE RATED FOR THE AVAILABLE |
| | FAULT CURRENT.PER 110.9/215.5 |
| | ** IT IS NOTED THAT THE AIC RATINGS WERE |
| | SHOWN FOR PANELS , HOWEVER SHOW NEW MAIN |
| | DISCONNECT RATING ALSO. |
| | |
| | NEW NOTE: |
| | 7)NOTE:NO, PLEASE SEE THE FEE AS |
| | REQUIRED UNDER FLORIDA STATUE HAS NOW |
| | BEEN ACCESSED AND IS REQUIRED TO BE PAID |
| | BEFORE PLANS CAN BE RESUBMITTED. |
| | A FEE OF $4,293.60 IS NOW OWED. |
| | PLEASE SEE ONE SET OF PLANS ARE NOW |
| | BEING RETAINED FOR FILE. |
| | IT IS STRONGLY RECOMMEDED A MEETING BE |
| | HELD BEFORE RESUBMITTING PLANS TO |
| | ALLEAVIATE ANY FURTHER DELAYS OR FINES. |
| | PLEASE SEE COPY OF FS |
| | 553.80(2)(B) WITH RESPECT TO THE DESIGN |
| | PROFESSIONAL AND REPEAT COMMENTS. THIS |
| | IS ONLY A NOTICE GIVEN AT THIS TIME. |
| | |
| | ******* NEW NOTE ******** |
| | |
| | 1)NOTE: PLEASE SEE RISER NOW INDICATES A |
| | NEW UPS SYSTEM BEING INSTALLED HOWEVE NO |
| | INFORMATION HAS BEEN SUBMITTED FOR THIS |
| | SYSTEM. PLEASE ALSO BE SURE VALUE FOR |
| | THIS SCOPE OF WORK IS ADJUSTED EVEN IF |
| | OWNER SUPPLIED. FBC 108.3 ADMINISTRATIVE |
| | SECTION OF THE LOCAL ADMINISTRATIVE |
| | CODE. |
| | UNABLE TO REVIEW AS NOT ENOUGH |
| | INFORMATION IS SUBMITTED. |
| | PLEASE ALSO SEE ROOM IS NOW BEING LABLED |
| | AS A "NETWORK ROOM"?? PLEASE CLARIFY USE |
| | AS IF THIS ROOM IS AN IT ROOM, |
| | REQUIREMENTS OF 645 AND NFPA-75 MAY |
| | APPLY. |
| | THIS MAY ALSO AFFECT MECHANICAL, AND |
| | BLDG SHEETS. |
| | |
| | 2)NOTE: PLEASE SEE FBC CHAPTER 13, |
| | 13-415.1ABC.1.1,.2 |
| | PLEASE KNOW, THIS WAS NOT ON PREVIOUS |
| | REVIEW, HOWEVER IS REQUIRED UNDER THE |
| | 2004 FBC WHICH PLANS ARE NOW SHOWN TO BE |
| | DESIGNED UNDER. |
| | |
| | |
| | ** ONE COPY OF ALL OLD VOIDED SHEETS |
| | WERE NOT SUBMITTED AS REQUESTED. |
| | |
| | ** PLEASE REMOVE ANY OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONLY ONE COPY OF THE OLD VOIDED SHEETS |
| | NEED TO BE SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THEREARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |