| Plan Review Notes For Permit 05100075 |
| Permit Number |
05100075 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-10-06 00:00:00 | DENIED; | | | 1.PLUMBING NOTES; NOTE #1 CHANGE TO 2004 | | | CODE. | | | 2.SHOW COMPLIANCE TO FBC-2004 PLUMBING | | | TABLE 403.1. SHOW CAULK'S ON PLUMBING | | | PAGE. | | | 3.WATER RISER; BREAK SINK DROP NOT | | | SHOWN. PLEASE SHOW WATER HAMMER | | | ARRESTORS AT THE BOTTOM OF DROPS. | | | MANUFACTOR INSTALLATION INSTRUCTIONS, TO | | | BE INSTALLED AS CLOSE TO THE SOURCE OF | | | THE HAMMER. | | | 4.BREAK ROOM SINK MUST COMPLY WITH | | | FBC-2004 BUILDING CHAPTER 11 SEC. | | | 11-4.24.1 THRU 11-4.24.7. (SHOW DETAIL) | | | 5.SANITARY ISOMETRIC; BREAK SINK NOT | | | VENTED. URINALS ARE "S" TRAPED. USE | | | SANITARY TEE'S OFF OF VENT STACK. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 | | | | | | |
|