| Plan Review Notes For Permit 05100075 |
| Permit Number |
05100075 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-11-10 00:00:00 | 1. PORTABLE FIRE EXTINGUISHERS ARE | | | REQUIRED. THEY ARE TO BE TYPE 2A 10BC | | | PORTABLE FIRE EXTINGUISHERS CURRENTLY | | | SERVICE TAGGED AND MOUNTED. | | | | | | 2. AISLES BETWEEN THE WORK STATIONS | | | LOCATED IN THE OPEN WORK AREA SHALL BE | | | ARRANGED TO PROVIDE FOR THE MINIMUM | | | CLEARNCE OF 44 INCHES. THE PLANS SEEM TO | | | REFLECT MORE WHICH IS ACCEPTABLE. | | | | | | 3. CONSTRUCTION, DEMOLITION, AND | | | RENOVATION TO COMPLY WITH NFPA 241. | | | | | | 4. DEBRIS SHALL BE REMOVED DAILY FROM | | | THE SITE. | | | | | | 5. EXISTING HANDRAILS AND GUARDRAILS ARE | | | TO MEET THE PRESCRIPTIVE STRENGTH | | | REQUIREMENTS OF THE BUILDING AND FIRE | | | CODES. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER. | | | 804-4709 |
|