| 2005-11-21 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2004 |
| | |
| | 1.)GOVERNING CODE IS FBC2004 EFFECTIVE |
| | 10/1/2005. |
| | |
| | 2.)BUILDING DATA (UNNUMBERED SHEET) |
| | PROVIDES INCORRECT TABLE FOR INTERIOR |
| | FINISH CLASSIFICATION, FBC TABLE 803.5. |
| | |
| | 3.)THE APPLICATION STATES THAT THIS IS |
| | A TENANT IMPROVEMENT.PLANS SHOW A NEW |
| | EXTERIOR STAIR AND WHEELCHAIR LIFT. |
| | REVISE THE PERMIT APPLICATION. |
| | |
| | 4.)THE WHEELCHAIR LIFT IS TO COMPLY |
| | WITH ASME A17.1, FBC3001.2. |
| | |
| | 5.)SHOW COMPLIANCE WITH FBC11-4.11.2, |
| | FBC11-4.2.4 FOR THE LIFT.INDICATE THAT |
| | THE SURFACE IS LEVEL. |
| | |
| | 6.)SHOW COMPLIANCE WITH ALL |
| | REQUIREMENTS OF FBC11-4.27. |
| | |
| | 7.)PROVIDE A DETAIL FOR THE BREAKROOM |
| | SINK, FBC11-24.PLEASE NOTE THE |
| | REQUIREMENT FOR KNEE CLEARANCE, |
| | FBC11-24.3. |
| | |
| | 8.)SHOW MANEUVERING CLEARANCE FOR DOOR |
| | 106, PUSH SIDE, FBC11 FIGURE 25. |
| | |
| | 9.)THE STAIR HANDRAIL AT THE BOTTOM OF |
| | THE STAIR IS TO COMPLY WITH |
| | FBC11-4.8.5(6), FIGURE 11-19. |
| | |
| | 10.)SHOW THE DIMENSION OF THE HANDRAIL |
| | EXTENSION AT THE TOP OF THE STAIR, |
| | FBC1009.11.5. |
| | |
| | 11.)SHOW LANDING AND DOOR DIMENSIONS, |
| | FBC1009.4, EXCEPTION 2. |
| | |
| | 12.)PROVIDE EITHER AN APPROVED |
| | ASSEMBLY OR CALCULATED FIRE RESISTANCE |
| | FOR THE 1 HOUR WALL, FBC7. |