| 2007-03-21 18:15:28 | |
| | ** UNSAT ** |
| | |
| | 1) NOTE:PLEASE CORRELATE RISER AND PANELS. PLEASE SEE |
| | RISER SHOWS 3-3/0'S FOR THE FEEDERS TO THE JANDY PANEL, |
| | WHEN THE SCHEDULE FOR THE JANDY PANEL AND THE JANDY |
| | PANEL ITSELF SHOWS 3-#3'S. |
| | PLEASE KNOW IF THIS IS INDEED 3/0'S THEN THE CONDUIT |
| | SIZE OF 1 1/4 INCH IS TOO SMALL PER CHAPTER 9 TABLES |
| | FOR CONDUIT FILL. |
| | PLEASE ADJUST. |
| | 408.4, 204.4, 310.16. FBC 106.1.2 |
| | |
| | 2) NOTE: PLEASE SEE NEW SCHEDULE FOR THE 400A MAIN |
| | PANEL. PLEASE CLARIFY THE NUMBER OF CIRCUITS AND THIS |
| | EQUIPMENT BEING SHOWN WITH MORE THAN 6 CIRCUITS AND |
| | SPACES. PLEASE SEE 230.71 AS NO MORE THAN 6 SPACES IS |
| | PERMITTED OR THIS EQUIPMENT MUST CONTAIN A MCB. (SHOWN |
| | AS MLO). |
| | |
| | 3) NOTE: PLEASE SEE BOTH PANELS A AND B ARE BEING SHOWN |
| | ON PANEL AS 42 CIRCUIT PANELS, HOWEVER ONLY PANEL *A* |
| | IS SHOWN WITH 42 CIRCUITS, PANEL *B* SHOWS ONLY 40? |
| | PLEASE CORRELATE. |
| | FBC 106.1.2 |
| | |
| | 4) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.16 AS |
| | ONE OR MORE OF THE CIRCUITS AS CONSIDERED IN 210.52B |
| | ARE REQUIRED TO BE ON ONE OR MORE OF THE SMALL |
| | APPLIANCE CIRCUITS. PLEASE SEE THAT EACH CIRCUIT OVER |
| | SHALL BE SHOWN AND FIGURED AT 1500VA EACH. PLEASE SEE |
| | PANEL *A* SEEMS TO SHOW A MINIMUM OF FOUR OF THESE |
| | CIRCUITS, YET LOAD CALCULATIONS ONLY SHOW THREE |
| | CIRCUITS AND LOADS FOR ONLY TWO? |
| | PLEASE VERIFY HOW MANY OF THESE CIRCUITS ARE ACTUALLY |
| | INSTALLED AND ADJUST ACCORDINGLY. |
| | FBC 106.3.5.4 |
| | |
| | 5) NOTE: PLEASE SEE THE LOAD SHOWN FOR THE |
| | REFRIGERATOR/FREEZER IN LOAD CALCULATIONS IS SHOWN AT |
| | 1800VA WHICH EXCEEDS THAT OF THE 15AMP CIRCUIT |
| | PROVIDED. |
| | PLEASE VERIFY ACTUAL LOAD AND ADJUST ACCORDINGLY. |
| | PLEASE KNOW IF THE LOAD IS NOT AS HIGH AS SHOWN, THE |
| | CIRCUIT WOULD NOT NEED TO BE ADJUSTED. IF LOAD IS |
| | INDEED THIS HIGH, PLEASE CHANGE TO A 20AMP CIRCUIT. |
| | 240.4, 310.16 ETC. |
| | |
| | 6) NOTE: PLEASE CORRELATE THE LAUNDRY CIRCUIT FROM THE |
| | LOAD CALCULATIONS AND THE PANEL SCHEDULE. PLEASE SEE |
| | THE LOAD CALCULATIONS SHOW 1-POLE 30AMP CIRCUIT, YET |
| | PANEL A SHOWS 1-POLE 20AMP CIRCUIT?? |
| | FBC 106.1.2 |
| | |
| | 7) NOTE: PLEASE SEE THE BATHROOM DEDICATED GFI CIRCUITS |
| | ARE NOTED ON PLANS AS 20AMP AND ARE ON PANEL SCHEDULES |
| | AS 20AMP, HOWEVER PLEASE SEE THE LOAD CALCULATIONS |
| | SCHEDULE WHICH SHOWS THESE AS 15AMPS CIRCUITS. THIS |
| | SEEMS TO BE A MISPRINT. |
| | 210.11C3, 210.52D. |
| | FBC 106.1.2 |
| | |
| | 8) NOTE: PLEASE SEE THE LOAD CALCULATIONS WHICH |
| | INDICATE A TOTAL OF 8-GEN LTS AND RECEPTS CIRCUITS WITH |
| | A LOAD OF 13,923, WHICH PLACES A LOAD OF 14.503 AMPS ON |
| | EACH OF THESE 15AMP RATED CIRCUITS. |
| | PLEASE GO OVER LOADS BEING SHOWN ON THESE 15AMPS |
| | CIRCUIT AND ADJUST. |
| | FBC 106.3.5.4 |
| | |
| | ** PLEASE CALL TO GO OVER ANY OF THE COMMENTS IF NEED |
| | BE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |