Plan Review Notes
Plan Review Notes For Permit 05100073
Permit Number 05100073
Review Stop E
Sequence Number 4
Notes
Date Text
2007-03-21 18:15:28 
 ** UNSAT **
  
 1) NOTE:PLEASE CORRELATE RISER AND PANELS. PLEASE SEE
 RISER SHOWS 3-3/0'S FOR THE FEEDERS TO THE JANDY PANEL,
 WHEN THE SCHEDULE FOR THE JANDY PANEL AND THE JANDY
 PANEL ITSELF SHOWS 3-#3'S.
 PLEASE KNOW IF THIS IS INDEED 3/0'S THEN THE CONDUIT
 SIZE OF 1 1/4 INCH IS TOO SMALL PER CHAPTER 9 TABLES
 FOR CONDUIT FILL.
 PLEASE ADJUST.
 408.4, 204.4, 310.16. FBC 106.1.2
  
 2) NOTE: PLEASE SEE NEW SCHEDULE FOR THE 400A MAIN
 PANEL. PLEASE CLARIFY THE NUMBER OF CIRCUITS AND THIS
 EQUIPMENT BEING SHOWN WITH MORE THAN 6 CIRCUITS AND
 SPACES. PLEASE SEE 230.71 AS NO MORE THAN 6 SPACES IS
 PERMITTED OR THIS EQUIPMENT MUST CONTAIN A MCB. (SHOWN
 AS MLO).
  
 3) NOTE: PLEASE SEE BOTH PANELS A AND B ARE BEING SHOWN
 ON PANEL AS 42 CIRCUIT PANELS, HOWEVER ONLY PANEL *A*
 IS SHOWN WITH 42 CIRCUITS, PANEL *B* SHOWS ONLY 40?
 PLEASE CORRELATE.
 FBC 106.1.2
  
 4) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.16 AS
 ONE OR MORE OF THE CIRCUITS AS CONSIDERED IN 210.52B
 ARE REQUIRED TO BE ON ONE OR MORE OF THE SMALL
 APPLIANCE CIRCUITS. PLEASE SEE THAT EACH CIRCUIT OVER
 SHALL BE SHOWN AND FIGURED AT 1500VA EACH. PLEASE SEE
 PANEL *A* SEEMS TO SHOW A MINIMUM OF FOUR OF THESE
 CIRCUITS, YET LOAD CALCULATIONS ONLY SHOW THREE
 CIRCUITS AND LOADS FOR ONLY TWO?
 PLEASE VERIFY HOW MANY OF THESE CIRCUITS ARE ACTUALLY
 INSTALLED AND ADJUST ACCORDINGLY.
 FBC 106.3.5.4
  
 5) NOTE: PLEASE SEE THE LOAD SHOWN FOR THE
 REFRIGERATOR/FREEZER IN LOAD CALCULATIONS IS SHOWN AT
 1800VA WHICH EXCEEDS THAT OF THE 15AMP CIRCUIT
 PROVIDED.
 PLEASE VERIFY ACTUAL LOAD AND ADJUST ACCORDINGLY.
 PLEASE KNOW IF THE LOAD IS NOT AS HIGH AS SHOWN, THE
 CIRCUIT WOULD NOT NEED TO BE ADJUSTED. IF LOAD IS
 INDEED THIS HIGH, PLEASE CHANGE TO A 20AMP CIRCUIT.
 240.4, 310.16 ETC.
  
 6) NOTE: PLEASE CORRELATE THE LAUNDRY CIRCUIT FROM THE
 LOAD CALCULATIONS AND THE PANEL SCHEDULE. PLEASE SEE
 THE LOAD CALCULATIONS SHOW 1-POLE 30AMP CIRCUIT, YET
 PANEL A SHOWS 1-POLE 20AMP CIRCUIT??
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE THE BATHROOM DEDICATED GFI CIRCUITS
 ARE NOTED ON PLANS AS 20AMP AND ARE ON PANEL SCHEDULES
 AS 20AMP, HOWEVER PLEASE SEE THE LOAD CALCULATIONS
 SCHEDULE WHICH SHOWS THESE AS 15AMPS CIRCUITS. THIS
 SEEMS TO BE A MISPRINT.
 210.11C3, 210.52D.
 FBC 106.1.2
  
 8) NOTE: PLEASE SEE THE LOAD CALCULATIONS WHICH
 INDICATE A TOTAL OF 8-GEN LTS AND RECEPTS CIRCUITS WITH
 A LOAD OF 13,923, WHICH PLACES A LOAD OF 14.503 AMPS ON
 EACH OF THESE 15AMP RATED CIRCUITS.
 PLEASE GO OVER LOADS BEING SHOWN ON THESE 15AMPS
 CIRCUIT AND ADJUST.
 FBC 106.3.5.4
  
 ** PLEASE CALL TO GO OVER ANY OF THE COMMENTS IF NEED
 BE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]