Plan Review Notes
Plan Review Notes For Permit 05100073
Permit Number 05100073
Review Stop E
Sequence Number 3
Notes
Date Text
2007-03-02 07:41:07*** UNSAT ***
  
  
  
 ** PLEASE SEE RISER HAS CHANGED FROM PREVIOUS PLANS AND
 PLEASE SEE ITEMS WHICH WERE REDLINED FROM PREVIOUS
 PLANS FROM 4/28/06 WHICH WERE NOT ADJUSTED AS MENTIONED
 ON PLANS TO BE DONE BEFORE ROUGH.
  
 1) NOTE: PLEASE SEE SERVICE HAS NOW COMPLETELY CHANGED
 TO INCLUDE SERVICE AT 400AMPS HOWEVER GROUNDING
 ELECTRODE CONDUCTOR WAS NOT INCREASED PER 250.66,
 310.15B6. (1/0)
  
 2) NOTE: PLEASE PLANS STILL INDICATE A MAIN DISCONNECT
 OUTSIDE WHERE RISER DOES NOT INCLUDE THIS.
 PLEASE CORRELATE RISER AND PLANS.
 PLEASE SEE LOAD CALCULATIONS ALSO CALL FOR A 300AMP
 SERVICE AS SHOWN ON PREVIOUS PLANS HOWEVER PLANS NOW
 SHOW 400AMP SERVICE.
 PLEASE SEE THAT THE RISER NOW SHOWS PANEL *B* AS
 200AMPS WITH WHAT APPEARS TO BE 2-100AMP BREAKERS SHOWN
 ON RISER?? IT IS UNCLEAR WHAT THIS IS?
 PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS OR FEEDERS
 DEPENDING IF THERE IS A MAIN OUTSIDE ARE NOT RATED FOR
 THE NEW 200AMP RATED MAIN.
 PLEASE CORRELATE SEVERAL ITEMS ON PLANS AND RISER.
 PLEASE SEE 310.15B6, 310.16, 240.4, 230.70 ETC FOR THE
 MINIMUM REQUIRED FOR SERVICE, MAINS ETC.
  
 3) NOTE: PLEASE VERIFY IF THERE IS NO MAINS OUTSIDE
 THAT THE CONDUITS FROM METER TO PANELS ARE IN THE SLAB
 AS REQUIRED PER 230.70, 230.71
  
 4) NOTE: PLEASE SEE NEW RECEPTACLE ADDED TO COUNTER
 SPACE IN KITCHEN SHALL BE GFI/GFI PROTECTED PER
 210.8A6.(PLEASE SHOW).
  
 5) NOTE: PLEASE KNOW THAT A MEETING WAS HELD AT THE
 SOUTHERN SECTION MEETING IN OCT 06 WHERE WE WERE
 DIRECTLY INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE
 DETECTORS ON PLANS FOR RESIDENTIAL HOMES IS NOT
 ACCEPTABLE WHEN THESE DEVICES ANY ACTUALLY FALL UNDER
 THE DEFINITIONS OF SMOKE ALARMS WHICH WOULD BE SHOWN AS
 SA/SMOKE ALARMS.
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. BY
 THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE*.
 PLEASE SEE NFPA-72 11.5.1.1, 11.8.3
  
 6) NOTE: PLEASE KNOW THAT COMPLETE PANEL SCHEDULES
 SHOWING ALL ROOMS AND AREAS IN WHICH CIRCUITS FEED WILL
 BE REQUIRED FOR EACH PANEL. PLEASE SEE TEXT WHICH IS
 TAKEN FROM COMMENTARY IN THE CODE WHICH STATES THE USE
 OF *GEN LT* ETC IS NOT ACCEPTABLE.
  
 *CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* PLEASE
 INCLUDE THESE IN TWO SEPARATE PANEL SCHEDULE(S) AND
 DEPENDING ON RISER BASED ON NOTES ABOVE IT BEING
 UNCLEAR WHAT THE TWO 100AMP BREAKERS ARE?
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 7) NOTE: PLEASE SEE THE NOTES ON THE LOWER PART OF LOAD
 CALCULATIONS WHICH STILL MENTIONS OUTSIDE WP LIGHTING
 TO BE ON BATH CIRCUIT(S) WHICH IS NOT PERMITTED. THIS
 WAS REDLINED ALSO ON PREVIOUS PLANS.
 210.52D, 210.11C3
  
 * PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]