Plan Review Notes
Plan Review Notes For Permit 05100073
Permit Number 05100073
Review Stop E
Sequence Number 1
Notes
Date Text
2005-10-19 00:00:00*********** UNSAT ***********
  
  
 1) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
  
 2)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANEL SCHEDULES SUBMITTED.
 PLEASE SEE RISER SHOWS WHAT APPEARS TO
 BE A DISCONNECT LOCATED AT THE GROUNDING
 ELECTRODE CONDUCTOR??
 PLEASE SEE A FEEDER/CONDUIT SEEMS TO
 EXIT PANEL "A" AT TOP , BUT DOES NOT
 SHOW OR INDICATE WHERE THIS GOES??
 PLEASE SEE THE SAME IS HOWN FOR PANEL
 "B".
 PLEASE SEE SEC'S DO NOT MEET MIN FOR
 CODE COMPLIANCE PER 310.15B6, 240.4.
  
  
 3)NOTE: PLEASE SEE 250.66 FOR MIN GEC,
 SHOWN AS #4.
  
 4)NOTE: PLEASE SEE NOTE MENTIONS ALL
 RECEPTS WITHIN 15' OF POOL TO BE GFI??
 PLEASE SEE 680.22 ETC, A MIN OF 20'
 PLEASE ALSO SEE 680.22 FOR MIN DISTANCE
 AND PROTECTION REQUIRED FOR ALL FIXTURES
 WITH POOL AREA. PLEASE SEE LTS AS SHOWN
 ON PLANS FOR SCONCE LOCATIONS AND FUTURE
 POOL SHOWN.
  
 5)NOTE: PLEASE CORRELATE NOTES ON PLANS
 IN FOUR LOCATIONS FOR THE REQUIRED ARC
 FAULT PROTECTION.
 PLEASE SEE NOTE #6 MENTIONS THAT SD'S
 "SHALL NOT" HAVE ARC FAULT PROTECTION??
 PLEASE SEE OTHER NOTES MENTIONS ONLY
 RECEPTS AND OTHE NOTES MENTIONS ARC
 FAULT REQUIRED???
  
 ** PLEASE LIST ON THE PANEL SCHEDULE ALL
 THE MIN REQUIRED ARC FAULT PROTECTED
 CIRCUITS. PLEASE KNOW, UNDER THE 2002
 NEC 210.12 ALL OUTLETSIN BEDRMS ARE
 REQUIRED TO HAVE ARC FAULT PROTECTION.
 THIS IS LTS, FANS, SD'S AND RECEPTS.
  
 6)NOTE: PLEASE 210.52 FOR RECEPTS
 MISSING ON PLANS. PLEASE SEE MANY OF
 THESE HAVE BEEN REDLINED AT LOCATIONS
 MENTIONED.
  
 7)NOTE: PLEASE SEE MISSING RECEPTS ALONG
 KITCHEN COUNTERSPACE REQUIRED PER
 210.52C1
  
 8)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECTED.,210.8A6
  
 9)NOTE: PLEASE SEE MISSING REQUIRED
 EGRESS LT FIXTURES SHOWN AS "J" -BOXES
 ON PLANS. PLEASE SEE 210.70, LS 101 7.8
  
 10)NOTE: PLEASE SEE MISSING FRONT GFI
 RECEPT PER 210.52E, 210.8A
  
 11)NOTE: PLEASE SEE MISSING SD REQUIRED
 LEADING TO THE FLR ABOVE PER NFAP-72
 11.5.1.1
  
 PLEASE BE SURE TO ANY POSSIBLE COMMETNS
 FROM OTHER REVIEWERS WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS FOR
 REVIEW AND STAMPING.
 ON ECOPY OF ANY OLD/VOIDED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]