| 2005-10-19 00:00:00 | *********** UNSAT *********** |
| | |
| | |
| | 1) NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | |
| | 2)NOTE: PLEASE CORRELATE RISER DIAGRAM |
| | AND PANEL SCHEDULES SUBMITTED. |
| | PLEASE SEE RISER SHOWS WHAT APPEARS TO |
| | BE A DISCONNECT LOCATED AT THE GROUNDING |
| | ELECTRODE CONDUCTOR?? |
| | PLEASE SEE A FEEDER/CONDUIT SEEMS TO |
| | EXIT PANEL "A" AT TOP , BUT DOES NOT |
| | SHOW OR INDICATE WHERE THIS GOES?? |
| | PLEASE SEE THE SAME IS HOWN FOR PANEL |
| | "B". |
| | PLEASE SEE SEC'S DO NOT MEET MIN FOR |
| | CODE COMPLIANCE PER 310.15B6, 240.4. |
| | |
| | |
| | 3)NOTE: PLEASE SEE 250.66 FOR MIN GEC, |
| | SHOWN AS #4. |
| | |
| | 4)NOTE: PLEASE SEE NOTE MENTIONS ALL |
| | RECEPTS WITHIN 15' OF POOL TO BE GFI?? |
| | PLEASE SEE 680.22 ETC, A MIN OF 20' |
| | PLEASE ALSO SEE 680.22 FOR MIN DISTANCE |
| | AND PROTECTION REQUIRED FOR ALL FIXTURES |
| | WITH POOL AREA. PLEASE SEE LTS AS SHOWN |
| | ON PLANS FOR SCONCE LOCATIONS AND FUTURE |
| | POOL SHOWN. |
| | |
| | 5)NOTE: PLEASE CORRELATE NOTES ON PLANS |
| | IN FOUR LOCATIONS FOR THE REQUIRED ARC |
| | FAULT PROTECTION. |
| | PLEASE SEE NOTE #6 MENTIONS THAT SD'S |
| | "SHALL NOT" HAVE ARC FAULT PROTECTION?? |
| | PLEASE SEE OTHER NOTES MENTIONS ONLY |
| | RECEPTS AND OTHE NOTES MENTIONS ARC |
| | FAULT REQUIRED??? |
| | |
| | ** PLEASE LIST ON THE PANEL SCHEDULE ALL |
| | THE MIN REQUIRED ARC FAULT PROTECTED |
| | CIRCUITS. PLEASE KNOW, UNDER THE 2002 |
| | NEC 210.12 ALL OUTLETSIN BEDRMS ARE |
| | REQUIRED TO HAVE ARC FAULT PROTECTION. |
| | THIS IS LTS, FANS, SD'S AND RECEPTS. |
| | |
| | 6)NOTE: PLEASE 210.52 FOR RECEPTS |
| | MISSING ON PLANS. PLEASE SEE MANY OF |
| | THESE HAVE BEEN REDLINED AT LOCATIONS |
| | MENTIONED. |
| | |
| | 7)NOTE: PLEASE SEE MISSING RECEPTS ALONG |
| | KITCHEN COUNTERSPACE REQUIRED PER |
| | 210.52C1 |
| | |
| | 8)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI |
| | PROTECTED.,210.8A6 |
| | |
| | 9)NOTE: PLEASE SEE MISSING REQUIRED |
| | EGRESS LT FIXTURES SHOWN AS "J" -BOXES |
| | ON PLANS. PLEASE SEE 210.70, LS 101 7.8 |
| | |
| | 10)NOTE: PLEASE SEE MISSING FRONT GFI |
| | RECEPT PER 210.52E, 210.8A |
| | |
| | 11)NOTE: PLEASE SEE MISSING SD REQUIRED |
| | LEADING TO THE FLR ABOVE PER NFAP-72 |
| | 11.5.1.1 |
| | |
| | PLEASE BE SURE TO ANY POSSIBLE COMMETNS |
| | FROM OTHER REVIEWERS WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS FOR |
| | REVIEW AND STAMPING. |
| | ON ECOPY OF ANY OLD/VOIDED SHEETS SHOULD |
| | BE SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |