| 2006-03-08 00:00:00 | ****** UNSAT 3RD REVIEW ******* |
| | |
| | **PLEASE SEE NOTES FROM PREVIOUS HAVE |
| | BEEN ADDRESSED, HOWEVER PLEASE SEE NEW |
| | NOTES DUE TO ITEMS ON PLANS. |
| | |
| | 1)NOTE: PLEASE SEE PLANS NOW CONTAIN |
| | "WHITE-OUT" AND PENCILED ITEMS ON PLANS. |
| | PLEASE SEE SOME PLANS SHOW DOOR AND SOME |
| | DETAILS REMOVE DOOR?? |
| | PLEASE SEE NOW DOOR IS OR IS NOT |
| | REMOVED, ARE LIGHT SWITCHES STILL BEING |
| | INSTALLED AT LOCATION SHOWN? |
| | PLANS CAN NOT CONTAIN "WHITE-OUT" AND |
| | PENCIL. |
| | FS 471.025 |
| | |
| | 2)NOTE: PLEASE SEE NOW KITCHEN DINING |
| | AREA SHOWS CIRCUITING SHARED WITH |
| | LIVING/FAMILY RM. |
| | PLEASE SEE210.52B1, KITCHEN/DINING AREA |
| | MUST HAVE A 20A , #12 CIRCUIT, MAY BE |
| | ONE OF THE SMALL APPLIANCE CIRCUITS. |
| | SHOWN AS 15A #14. |
| | |
| | 3)NOTE: PLEASE SEE NEW TITLE BLOCKS ARE |
| | NOW MISSING THE REQUIRED PRINTED LICENSE |
| | # OF THE ENGINEER. |
| | THIS IS REQUIRED TO BE PRINTED IN THE |
| | TITLE BLOCK PER FAC 61G15-23.002 |
| | |
| | ** PLEASE SEE ONCE COPY OF ELECTRICAL |
| | PLANS WERE STAMPED IN ERROR AND HAS |
| | SINCE BEEN VOIDED AND NEEDS TO BE |
| | REPLACED. |
| | |
| | PLEASE SUBMIT THE ABOVE CORRECTIONS FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |