Plan Review Notes
Plan Review Notes For Permit 05100065
Permit Number 05100065
Review Stop E
Sequence Number 2
Notes
Date Text
2006-02-03 00:00:00******** UNSAT 2ND REVIEW *********
  
 ** PLEASE KNOW, DUE TO CHANGES IN PLANS,
 PLEASE SEE COMMENTS BELOW.
  
  
 1)NOTE: PLEASE CORRELATE SERVICE AS
 PLANS INDICATE A MCB INSIDE GARAGE, YET
 RISER SHOWS THIS AS MLO?
 PLEASE ALSO SEE MISSING MAIN DISCONNECT.
 PLEASE SEE PLANS DO NOT SHOW NEW SERVICE
 AS SHOWN ON RISER.
 215.5
  
 2)NOTE: PLEASE SEE RISER SEEMS TO
 INDICATE THE 22,000 AIC RATING FOR THE
 MLO PANEL??
 PLEASE KNOW, IF THIS IS INDEED THE CASE,
 ALL BRANCH BRKRS IN THIS MLO PANEL WOULD
 BE REQUIRED TO HAVE 22,000 RATED BRKRS.
 THIS MUST BE A MISPRINT. PLEASE SPECIFY
 AIC RATING OF MAIN.
 110.9,215.5
  
 3)NOTE: PLEASE SEE SD'S WILL BE REQUIRED
 INSIDE AND OUTSIDE "OFFICE" AS THIS IS
 AN ADAPTABLE SLEEPING RM.
 NFPA-72 11.5.1.1
  
 4)NOTE: PLEASE SEE OCP FOR RANGE SAHLL
 NOT EXCEED THAT RATING OF THE RANGE
 RECEPT. (50A'S) PLEASE SEE 210.21B3
  
 5)NOTE: PLEASE SEE CLOSET LT SHALL MEET
 410.8, AS SHELVING IS NOT INDICCATE
 PLEASE SEE ASSUMED 18" ON EITHER SIDE
 AND MIN TYPE OF FIXTURE SHALL BE
 INDICATED.
  
 6)NOTE: PLEASE SEE MISSING RECEPTS FOR
 2' OF WALL SPACE. 210.52
 REDLINED.
  
 7)NOTE: PLEASE SEE NOTES AS MANY ITEMS
 AS LISTED , CENTRAL VAC, SPKR WIRING ETC
 ARE NOT SHOWN ON PLANS. IF THESE ITEMS
 ARE GOING TO BE INSTALLED UNDER THIS
 PERMIT , PLEASE SHOW. IF NOT, PLEASE
 REMOVE FROM NOTES.
  
 8)NOTE: PLEASE SEE NOTES, AS NOTE
 MENTIONS NO MORE THAN 6 RECEPTS
 PERMITTED ON A CIRCUIT, HOWEVER SOME
 CIRCUITS ON PLANS INDICATE MORE THAN 6.
 PLEASE ADJUST PLANS, CIRCUITING , OR
 NOTE.
 215.5
  
 9)NOTE: PLEASE KNOW, HOUSE/APT SEEMS TO
 BE A REMODEL, HOWEVER RISER SHOWS THE
 FOOTER STEEL TO BE PART OF THE GROUNDING
 ELECTRODE SYSTEM??
 ** PLEASE KNOW, EXISTING FOOTER ARE NOT
 REQUIRED TO HAVE THE FOOTER STEEL AS
 PART IF THE GROUNDING ELECTRODE SYSTEM.
 PLEASE ALSO KNOW, MANY OLDER BLDGS DO NO
 CONTAIN FOOTER STEEL.
 PLEASE ADJUST THIS ON RISER AS THIS
 WOULD BE MORE DETRIMENTAL TO THE
 STRUCTURE/FOOTERS.
 PLEASE INDICATE TWO GRND RODS.250.56
  
 10)NOTE: PLEASE SEE NOTES FROM PREVIOUS
 REVIEW WHICH REQUESTED THE MANUFACTURES
 CUT SHEETS FOR THE "INSTANT"ON DEMAND"
 WATER HEATERS. NEED TO VERIFY OCP, KW
 RATING, AND LISTING FROM A NRTL.
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE REMOVE ANY OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND
 STAMPING. PLEASE ONLY SUBMIT ONE COPY OF
 OLD/VOIDED SHEETS FOR REFERENCE.
  
 ** PLEASE SEE MANY OF THE ABOVE ITEMS
 ARE REDLINED ON ONE OF THE SETS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]