2005-11-09 00:00:00********* UNSAT **************
  
  
 **** PLEASE SEE ZONING REVIEW COMMENTS
 AS THIS WILL GREATLY AFFECT ELECTRICAL
 PLANS AND OTHER PLANS AS WELL.
  
  
 1)NOTE: PLEASE SEE SF-14 DESIGNATION
 ONLY PERMITS ONE METER FOR GARAGE APT
 AND AND 230.2 ONLY PERMITS ONE SERVICE.
 PLEASE SEE TWO RISER DIAGRAMS ARE SHOWN/
 PLEASE ALSO CLARIFY MAIN HOUSE SERVICE
 AND THIS BEING PART OF GARAGE APT
 SERVICE. WILL THIS BE A 2-GANG METER AND
 ONE FEEDING GARAGE APT?
 PLEASE KNOW, DUE TO CHANGES IN SERVICE,
 THERE MAY BE COMMENTS AS PERMANANT
 SERVICE IS NOT SHOWN AT THIS TIME.
  
 2)NOTE: ELECTRICAL PLANS ARE TO SHOW ALL
 A/C EQUIPMENT AND DISCONNECTS PER 440.11
  
 3)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52
  
 3)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 11.5.1.1
  
 4)NOTE: PLEASE INDICATE ALL OUTSIDE,
 GARAGE RECEPTS AS GFI. 210.8A
  
 5)NOTE: PLEASE SEE MISSING GFI FOR CU,
 210.63
  
 6)NOTE: PLEASE SHOW LOCATIONS OF ALL
 ELECTRICAL EQUIPMENT, NO VERIFICATION
 CAN BE DONE AT THIS TIME FOR CODE
 COMPLIANCE OF 230.70,230.72, 230.2 ETC.
  
 7)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO PANEL.
 250.24,250.110,250.122 ETC.
  
 8)NOTE: PLEASE VERIFY THE KW LOAD FOR
 THE "ON DEMAND" HWH.
 PLEASE SUBMIT SPECS ON UNIT. 4.5 KW UNIT
 DO NOT SEEM LIKE A COMMON SIZE.
  
 9)NOTE: PLEASE SEE MISSING REQUIRED
 DEDICATED BATH CIRCUIT(S). 20A, #12.
 210.11C3
  
 10)NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED ON TITLE BLOCK PER FAC
 61G15-23.002
  
 11)NOTE: PLEASE SEE PLANS INDICATE WHAT
 APPEARS TO BE STACKABLE WASHER/DRYER
 YET, PANEL SCHEDULE SHOWS TWO SEPARATE
 UNITS?
  
 12)NOTE: PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS PER 2002 NEC
 210.12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-10-09 00:00:00SENT TO ZONING FOR CONVERSION OF FIRST
 FLR.
 PLANS TO RETURN TO ELECTRICAL FOR REVIEW
 AFTER ZONING REVIEW.