| Date |
Text |
| 2005-11-09 00:00:00 | ********* UNSAT ************** |
| | |
| | |
| | **** PLEASE SEE ZONING REVIEW COMMENTS |
| | AS THIS WILL GREATLY AFFECT ELECTRICAL |
| | PLANS AND OTHER PLANS AS WELL. |
| | |
| | |
| | 1)NOTE: PLEASE SEE SF-14 DESIGNATION |
| | ONLY PERMITS ONE METER FOR GARAGE APT |
| | AND AND 230.2 ONLY PERMITS ONE SERVICE. |
| | PLEASE SEE TWO RISER DIAGRAMS ARE SHOWN/ |
| | PLEASE ALSO CLARIFY MAIN HOUSE SERVICE |
| | AND THIS BEING PART OF GARAGE APT |
| | SERVICE. WILL THIS BE A 2-GANG METER AND |
| | ONE FEEDING GARAGE APT? |
| | PLEASE KNOW, DUE TO CHANGES IN SERVICE, |
| | THERE MAY BE COMMENTS AS PERMANANT |
| | SERVICE IS NOT SHOWN AT THIS TIME. |
| | |
| | 2)NOTE: ELECTRICAL PLANS ARE TO SHOW ALL |
| | A/C EQUIPMENT AND DISCONNECTS PER 440.11 |
| | |
| | 3)NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52 |
| | |
| | 3)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 11.5.1.1 |
| | |
| | 4)NOTE: PLEASE INDICATE ALL OUTSIDE, |
| | GARAGE RECEPTS AS GFI. 210.8A |
| | |
| | 5)NOTE: PLEASE SEE MISSING GFI FOR CU, |
| | 210.63 |
| | |
| | 6)NOTE: PLEASE SHOW LOCATIONS OF ALL |
| | ELECTRICAL EQUIPMENT, NO VERIFICATION |
| | CAN BE DONE AT THIS TIME FOR CODE |
| | COMPLIANCE OF 230.70,230.72, 230.2 ETC. |
| | |
| | 7)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR FROM MAIN TO PANEL. |
| | 250.24,250.110,250.122 ETC. |
| | |
| | 8)NOTE: PLEASE VERIFY THE KW LOAD FOR |
| | THE "ON DEMAND" HWH. |
| | PLEASE SUBMIT SPECS ON UNIT. 4.5 KW UNIT |
| | DO NOT SEEM LIKE A COMMON SIZE. |
| | |
| | 9)NOTE: PLEASE SEE MISSING REQUIRED |
| | DEDICATED BATH CIRCUIT(S). 20A, #12. |
| | 210.11C3 |
| | |
| | 10)NOTE: PLEASE SEE MISSING INFORMATION |
| | REQUIRED ON TITLE BLOCK PER FAC |
| | 61G15-23.002 |
| | |
| | 11)NOTE: PLEASE SEE PLANS INDICATE WHAT |
| | APPEARS TO BE STACKABLE WASHER/DRYER |
| | YET, PANEL SCHEDULE SHOWS TWO SEPARATE |
| | UNITS? |
| | |
| | 12)NOTE: PLEASE LIST THE REQUIRED ARC |
| | FAULT PROTECTED CIRCUITS PER 2002 NEC |
| | 210.12 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW AND IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2005-10-09 00:00:00 | SENT TO ZONING FOR CONVERSION OF FIRST |
| | FLR. |
| | PLANS TO RETURN TO ELECTRICAL FOR REVIEW |
| | AFTER ZONING REVIEW. |