Plan Review Notes
Plan Review Notes For Permit 05100006
Permit Number 05100006
Review Stop E
Sequence Number 3
Notes
Date Text
2006-06-09 00:00:00*********** UNSAT 3RD REVIEW *********
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEWS AND SOME NEW COMMENTS
 DUE TO THE PLANS BEING SUBMITTED.
  
 1) NOTE: PLEASE SEE AS REQUESTED ON THE
 TWO PREVIOUS REVIEWS, PHOTO-METRICS ARE
 TO BE PROVIDED WHICH MEET THE MINIMUM
 REQUIREMENTS AS SET FORTH IN THE 2003
 NFPA-101 LIFE SAFETY CODE.
 PLEASE SEE THE RESPONSE MENTIONED THAT
 THIS HAD BEEN ACHIEVED ON BOTH SETS
 SUBMITED, HOWEVER AS STATED ON PREVIOUS
 REVIEWS: 7.8.1.3 UNDER NORMAL
 CONDITIONS, THE LIGHTING LEVELS ARE TO
 BE 10FT CANDLES MIN(AVG)(108 LUX)AND
 ONLY UNDER EMERGENCY CONDITIONS CAN THE
 LIGHTING LEVELS BE REDUCED TO 1FT CANDLE
 AVG MIN (10.8LUX). PLEASE SEE STAIR
 LOCATIONS DO NOT SHOW THIS.
 PLEASE SEE THIS IS NOT SHOWN ON PLANS.
 PLEASE SEE ON PREVIOUS REVIEW IT WAS
 REQUESTED THE PERSON RESPONSIBLE FOR
 LIGHTING DESIGN/PHOTO-METRICS WHICH IS
 THE ENGINEER OF RECORD SHALL SIGN,DATE
 AND SEAL PLANS.
 PLEASE SEE LIGHTING DESIGN IS NOW SHOWN
 BY ANOTHER PERSON WHICH IS NOT SIGNED
 PER FBC 104.2.1,106.3 ADMINISTRATIVE
 SEC.
  
 2) NOTE: PLEASE SEE PREVIOUS NOTE FOR
 THE 2004 FBC CHAPTER 13.
 13-415.1.ABC.1.1, .1.2, .1.3 ETC.
 PLEASE SEE A TIME CLOCK IS MENTIONED IN
 RESPONSE HOWEVER THIS IS NOT THE ONLY
 ITEM REQUIRED.
 PLEASE SEE MULTIPLE FLOORS, OVER RIDES,
 LOCATIONS, SCHEDULING ETC COULD NOT BE
 LOCATED.
 PLEASE SEE MORE THAN ONE SYSTEM IS
 REQUIRED WHEN MORE THAN ONE FLOOR IS IN
 SCOPE ETC.
 PLEASE SEE ENERGY CALCS SUBMITTED
 INDICATE THE 2001 FBC?, YET PLANS ARE TO
 BE UNDER THE 2004 FBC. PLEASE SEE
 13-415.1.AB.1 AND PRESCRIPTIVE METHODS
 WHICH MUST BE DONE FOR RENOVATIONS. "C".
  
 3) NOTE: PLEASE SEE VALUATION FOR SCOPE
 OF WORK HAS STILL NOT BEEN ADJUSTED.
 PLEASE SEE FBC ADMINISTRATIVE SECTION AS
 ADOPTED BY THE CITY OF WEST PALM BEACH
 108.3. COMPLETE SCOPE PF WORK SHALL
 INCLUDE ALL LABOR AND MATERIALS.
 PLEASE SEE THE FOLLOWING COMMENT AS THE
 FEES WILL BE AFFECTED.
  
 4) NOTE: PLEASE SEE A NOTICE WAS GIVEN
 ON PREVIOUS REVIEW WITH REFERENCE TO THE
 FS 553.80(2)(B) WITH RESPECT TO REPEAT
 COMMENTS THREE OR MORE TIMES.
 PLEASE SEE A 4X FEE FOR THE PLAN REVIEW
 PORTION OF THE EMIT FEE HAS NOW BEEN
 ASSESSED AND SHALL BE PAID BEFORE
 RE-SUBMITTING PLANS FOR THE NEXT REVIEW.
 PLEASE KNOW THE VALUE FOR SCOPE OF WORK
 WILL BE ASSESSED BY THIS DEPARTMENT
 WHICH WILL AFFECT THIS FINE.
  
 **
 NEW NOTES;
  
 5) NOTE: PLEASE SEE PLANS NOW PLANS ARE
 BEING SUBMITTED DONE BY AN ENGINEER AND ENGINEERING
 FIRM.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002
 WHICH REQUIRES THE PRINTED
 NAME AND LICENSE NUMBER OF SAID ENGINEER
 ON TITLE BLOCKS. THIS SAME SECTION ALSO
 REQUIRES A CERTIFICATE OF AUTHORIZATION
 NUMBER FOR SAID ENGINEERING FIRM AS
 REQUIRED PER FS 471.023
  
 6) NOTE: PLEASE SEE ELECTRICAL PLANS
 ALSO CONTAIN A "STAMP" FOR THE SIGNATURE
 OF THE SAID ENGINEER WHICH UNDER FS
 471.025, FAC 61G15-23.002 IS REQUIRED TO
 BE ORIGINAL SIGNATURE AND DATED.
 PLEASE SEE ONLY THE DATE IS IN ORIGINAL
 "WET" INK.
 PLEASE KNOW, STAMPS FOR SIGNATURES ARE
 NOT PERMITTED UNDER FS/ FAC.
 PLEASE ALSO KNOW, BOTH SETS OF
 ELECTRICAL PLANS AND ORIGINAL ELECTRICAL
 PLANS DONE BY THE ARCHITECT ARE ALL
 BEING RETAINED FOR FILE AND POSSIBLE
 REVIEW BY THE FLORIDA BOARD OF ENGINEERS
 AND STATE'S LEGAL COUNSEL.
  
 ** PLEASE KNOW, IT IS STRONGLY SUGGESTED
 A MEETING BE HELD TO GO OVER COMMENTS
 AND QUESTIONS BEFORE RE-SUBMITTING
 PLANS.
 THIS MAY HELP ALLEVIATE DELAYS IN
 PROJECT AND THE HELP EXPEDITE THE
 REVIEWS WHEN PLANS ARE BROUGHT BACK IN
 FOR REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  