| 2006-06-09 00:00:00 | *********** UNSAT 3RD REVIEW ********* |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM |
| | PREVIOUS REVIEWS AND SOME NEW COMMENTS |
| | DUE TO THE PLANS BEING SUBMITTED. |
| | |
| | 1) NOTE: PLEASE SEE AS REQUESTED ON THE |
| | TWO PREVIOUS REVIEWS, PHOTO-METRICS ARE |
| | TO BE PROVIDED WHICH MEET THE MINIMUM |
| | REQUIREMENTS AS SET FORTH IN THE 2003 |
| | NFPA-101 LIFE SAFETY CODE. |
| | PLEASE SEE THE RESPONSE MENTIONED THAT |
| | THIS HAD BEEN ACHIEVED ON BOTH SETS |
| | SUBMITED, HOWEVER AS STATED ON PREVIOUS |
| | REVIEWS: 7.8.1.3 UNDER NORMAL |
| | CONDITIONS, THE LIGHTING LEVELS ARE TO |
| | BE 10FT CANDLES MIN(AVG)(108 LUX)AND |
| | ONLY UNDER EMERGENCY CONDITIONS CAN THE |
| | LIGHTING LEVELS BE REDUCED TO 1FT CANDLE |
| | AVG MIN (10.8LUX). PLEASE SEE STAIR |
| | LOCATIONS DO NOT SHOW THIS. |
| | PLEASE SEE THIS IS NOT SHOWN ON PLANS. |
| | PLEASE SEE ON PREVIOUS REVIEW IT WAS |
| | REQUESTED THE PERSON RESPONSIBLE FOR |
| | LIGHTING DESIGN/PHOTO-METRICS WHICH IS |
| | THE ENGINEER OF RECORD SHALL SIGN,DATE |
| | AND SEAL PLANS. |
| | PLEASE SEE LIGHTING DESIGN IS NOW SHOWN |
| | BY ANOTHER PERSON WHICH IS NOT SIGNED |
| | PER FBC 104.2.1,106.3 ADMINISTRATIVE |
| | SEC. |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS NOTE FOR |
| | THE 2004 FBC CHAPTER 13. |
| | 13-415.1.ABC.1.1, .1.2, .1.3 ETC. |
| | PLEASE SEE A TIME CLOCK IS MENTIONED IN |
| | RESPONSE HOWEVER THIS IS NOT THE ONLY |
| | ITEM REQUIRED. |
| | PLEASE SEE MULTIPLE FLOORS, OVER RIDES, |
| | LOCATIONS, SCHEDULING ETC COULD NOT BE |
| | LOCATED. |
| | PLEASE SEE MORE THAN ONE SYSTEM IS |
| | REQUIRED WHEN MORE THAN ONE FLOOR IS IN |
| | SCOPE ETC. |
| | PLEASE SEE ENERGY CALCS SUBMITTED |
| | INDICATE THE 2001 FBC?, YET PLANS ARE TO |
| | BE UNDER THE 2004 FBC. PLEASE SEE |
| | 13-415.1.AB.1 AND PRESCRIPTIVE METHODS |
| | WHICH MUST BE DONE FOR RENOVATIONS. "C". |
| | |
| | 3) NOTE: PLEASE SEE VALUATION FOR SCOPE |
| | OF WORK HAS STILL NOT BEEN ADJUSTED. |
| | PLEASE SEE FBC ADMINISTRATIVE SECTION AS |
| | ADOPTED BY THE CITY OF WEST PALM BEACH |
| | 108.3. COMPLETE SCOPE PF WORK SHALL |
| | INCLUDE ALL LABOR AND MATERIALS. |
| | PLEASE SEE THE FOLLOWING COMMENT AS THE |
| | FEES WILL BE AFFECTED. |
| | |
| | 4) NOTE: PLEASE SEE A NOTICE WAS GIVEN |
| | ON PREVIOUS REVIEW WITH REFERENCE TO THE |
| | FS 553.80(2)(B) WITH RESPECT TO REPEAT |
| | COMMENTS THREE OR MORE TIMES. |
| | PLEASE SEE A 4X FEE FOR THE PLAN REVIEW |
| | PORTION OF THE EMIT FEE HAS NOW BEEN |
| | ASSESSED AND SHALL BE PAID BEFORE |
| | RE-SUBMITTING PLANS FOR THE NEXT REVIEW. |
| | PLEASE KNOW THE VALUE FOR SCOPE OF WORK |
| | WILL BE ASSESSED BY THIS DEPARTMENT |
| | WHICH WILL AFFECT THIS FINE. |
| | |
| | ** |
| | NEW NOTES; |
| | |
| | 5) NOTE: PLEASE SEE PLANS NOW PLANS ARE |
| | BEING SUBMITTED DONE BY AN ENGINEER AND ENGINEERING |
| | FIRM. |
| | PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002 |
| | WHICH REQUIRES THE PRINTED |
| | NAME AND LICENSE NUMBER OF SAID ENGINEER |
| | ON TITLE BLOCKS. THIS SAME SECTION ALSO |
| | REQUIRES A CERTIFICATE OF AUTHORIZATION |
| | NUMBER FOR SAID ENGINEERING FIRM AS |
| | REQUIRED PER FS 471.023 |
| | |
| | 6) NOTE: PLEASE SEE ELECTRICAL PLANS |
| | ALSO CONTAIN A "STAMP" FOR THE SIGNATURE |
| | OF THE SAID ENGINEER WHICH UNDER FS |
| | 471.025, FAC 61G15-23.002 IS REQUIRED TO |
| | BE ORIGINAL SIGNATURE AND DATED. |
| | PLEASE SEE ONLY THE DATE IS IN ORIGINAL |
| | "WET" INK. |
| | PLEASE KNOW, STAMPS FOR SIGNATURES ARE |
| | NOT PERMITTED UNDER FS/ FAC. |
| | PLEASE ALSO KNOW, BOTH SETS OF |
| | ELECTRICAL PLANS AND ORIGINAL ELECTRICAL |
| | PLANS DONE BY THE ARCHITECT ARE ALL |
| | BEING RETAINED FOR FILE AND POSSIBLE |
| | REVIEW BY THE FLORIDA BOARD OF ENGINEERS |
| | AND STATE'S LEGAL COUNSEL. |
| | |
| | ** PLEASE KNOW, IT IS STRONGLY SUGGESTED |
| | A MEETING BE HELD TO GO OVER COMMENTS |
| | AND QUESTIONS BEFORE RE-SUBMITTING |
| | PLANS. |
| | THIS MAY HELP ALLEVIATE DELAYS IN |
| | PROJECT AND THE HELP EXPEDITE THE |
| | REVIEWS WHEN PLANS ARE BROUGHT BACK IN |
| | FOR REVIEW. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |