2006-06-13 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 SECOND REVIEW
  
 COMMENTS FROM FIRST REVIEW:
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 PLEASE KEEP THE NOC PROVIDED IN THE
 PERMIT APPLICATION PACKAGE.
  
 2-7.)ADDRESSED.
  
 8.)PROVIDE CERTIFICATION IN REGARDS TO
 THE FLOOR LOADING, SECOND FLOOR.SHOW
 COMPLIANCE WITH FBC TABLE 1607.1.
  
 3RD REVIEW - THE NEW NOTE REFERS TO "IN
 ACCORANCE WITH SBC TABLE".WRONG CODE;
 NO TABLE REFERENCED.
  
 9. - 10)ADDRESSED.
  
 11.)VERTICAL ACCESSIBILITY REQUIRED,
 FBC EB 806, FBC11-4.1.6(1)(B).
  
 ADDRESSED, BUT PLEASE SHOW SIGNAGE
 REQUIRED BY FBC11-4.10.5.
  
 3RD REVIEW - PROVIDE SIGNAGE
 INFORMATION.A CODE REFERENCE WAS
 PROVIDED, BUT NO DETAIL OR SPECIFICATION
 PROVIDED.
  
 12-27.)PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD,
 FBC*106.3.3.
  
 NO PRODUCT APPROVALS SUBMITTED.PLEASE
 HAVE REVIEWED BY DOR AND SUBMIT.
  
 CODE COMPLIANCE CANNOT BE DETERMINED
 UNTIL DESIGN PRESSURE ISSUES RESOLVED.
 PRODUCT APPROVALS ARE TO BE REVIEWED BY
 DESIGNER OF RECORD, NOT ADDRESSED.
  
 NEW COMMENTS:
  
 28-31.) ADDRESSED.
  
 32.)SEE ATTACHED FS553(80)(2)(B).A
 4X PLAN REVIEW FEE IS REQUIRED TO BE
 CHARGED IF COMMENTS NOT PROPERLY
 ADDRESSED A THIRD TIME.
  
 3RD REVIEW - 4X FEE CHARGED.NOTE THAT
 THIS FEE WILL BE CHARGED EVERY TIME IF
 COMMENTS NOT ADDRESSED.
  
 33.)THE HANDWRITTEN NUMBER FOR THE
 REVIEION TO THE AREA CALCS IS NOT THE
 SAME ON ALL SHEETS.ARE THERE OTHER
 DISCRPEANCIES?
  
 34.)CHANGES HANDWRITTEN TO THE PLAN
 ARE TO BE INITIALLED.
  
 35.)REMOVE OLD DATA FROM THE PLAN.
 THE OLD "DESIGN DATA" IS STILL ON THE
 PLAN WITH A CLOUD THAT STATES "DELETE".
 DELETE FROM THE PLAN.A NEW ONE HAS
 BEEN PASTED.INCORPORATE PROPERLY INTO
 THE SHEET.THIS IS NOT AN ACCEPTABLE
 WAY TO CHANGE A SEALED DRAWING AS THERE
 IS NO WAY TO TELL WHO MADE THIS CHANGE,
 AFTER THE SHEET WAS SIGNED AND SEALED.
  
 36.)BUILDING TYPE SHOULD INDICATE TYPE
 A OR B, FBC6.
  
 37.)HOW HAVE YOU DETERMINED DESIGN
 PRESSURES?SOME ARE THE SAME AS TABLE
 1609.6 FBC, BUT THIS BUILDING IS OVER
 30'.LARGER OPENINGS ON THE FIRST FLOOR
 HAVE DPS HIGHER THAN SMALLER OPENINGS.
  
 38.)INCORRECT CODE ON ENERGY CALCS.