| Plan Review Notes For Permit 05100006 |
| Permit Number |
05100006 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-03-29 00:00:00 | ******PROVISO****** | | | | | | 1) WORK SHALL COMPLY WITH NFPA 101, 2003 | | | EDITION CHAPTER 36. | | | | | | 2) IN ADDITION TO THE HEIGHT | | | REQUIREMENT, ADDRESS SHALL BE | | | CONTRASTING TO THE BACKGROUND. | | | | | | 3) FOR NEW INSTALLATIONS, DUCT SMOKE | | | DETECTORS SHALL CAUSE A GENERAL FIRE | | | ALARM IN ACCORDANCE WITH LOCAL | | | REQUIREMENTS. | | | | | | PLANS WILL BE STAMPED WHEN RESUBMITTED | | | FOR OTHER REVIEW COMMENTS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|