Plan Review Notes
Plan Review Notes For Permit 05100006
Permit Number 05100006
Review Stop E
Sequence Number 2
Notes
Date Text
2006-03-07 00:00:00********** UNSAT2ND REVIEW *********
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW ,A ND NEW NOTES, DUE TO CHANGES
 IN PLANS AND FBC.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM FIRST REVIEW WITH NOTES
 FOR 2ND REVIEW DIRECTLY ABOVE.
  
  
 1)NOTE: NOTE #1 OK, HOWEVER PLEASE SEE
 FACP WAS REMOVED FROM STAIR, HOWEVER
 THIS PANEL FOR THIS SPACE IS BEING SHOWN
 OUTSIDE TENANT SPACE? IS THIS PANEL THE
 BASE BLDG PANEL OR TENANT PANEL?
 PLEASE SEE FIRE REVIEW COMMENTS FRO
 LOCATION ETC.
  
 **PLEASE SEE THAT FIRE ALARM
 CONTROL PANEL SHALL "NOT" BE LOCATED IN
 THE STAIRWAY AS SHOWN.
 EQUIPMENT ONLY PERTAINING THE FUNCTION
 OF THE STAIRWAY MAY BE LOCATED IN THOSE
 LOCATIONS.
 PLEASE ALSO SEE NOTES FROM CHIEF FIRE
 MARSHAL.
  
 2)NOTE:NOTE #2 NO. PLEASE SEE
 PHOTOMETRICS SUBMITTED ARE NOT SIGNED,
 DATED OR SEAL BY THE DESIGN PROFESSIONAL
 OR PERSON RESPONSIBLE FOR
 DESIGN/PLANS.106.3.4.3
 PLEASE ALSO SEE MIN LIGHTING LEVELS DO
 NOT SEEM TO HAVE BEEN ACHIEVED.
 PLEASE SEE NFPA-101 7.8.1.3
  
 **PLEASE SEE NFPA-101 2003, 7.8,
 7.9 WHICH REQUIRES A MIN OF 10
 FT/CANDLES AT STAIR EGRESS LOCATIONS.
 PLEASE SEE MIN FT CANDLES UNDER EM
 POWERE REQUIRED AT 1FT/CAN.
 PLEASE PROVIDE BRIEF PHOTO-METRICS FOR
 STAIR/EGRESS LOCATIONS.
  
 3)NOTE:NOTE #3 NO, PLEASE SEE SOME
 CIRCUITING STILL MISSINGON PLANS FOR
 FIXTURES. PLEASE SEE EM LT, REDLINED
 PLANS.
  
 **PLEASE SHOW ALL CIRCUTING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULES.
 PLEASE SEE CIRCUTING FOR EM/EXT LTS
 SHALL BE PER 700.12E WHICH REQUIRES THE
 BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
  
 4)NOTE: NOTE #4 NO, PLEASE SEE CU'S ON
 MECHANICAL PLANS AND OCP INDICATED ON
 "M" SHEETS AND PANEL SCHEDULE. PLANS
 REDLINED. ( 25A, 30A?)
  
 ** PLEASE CORRELAT PANEL SCHEDULE,
 A/C EQUIPMENT AND LOADS.
 PLEASE SEE AHU'S SHOWN AS 3-PHASE IN
 LOADS AND ON SCHEDULE, HOWEVER ALSO
 NOTED AS 2-POLE BRKRS??
 PLEASE SEE LOAD CALCULATIONS ONLY
 INCLUDES LOADS FOR ONE UNIT.
 PLEASE REVISE AS NEEDED.
 PLEASE ALSO CALRIFY WHAT SEEMS TO
 INDICATE 4-CU'S ON PANEL SCHEDULE, YET
 ONLY TWO AHU'S ARE SHOWN?
  
 5)NOTE:NOTE #5 OK, (NOTED AS FUTURE).
  
  
 6)NOTE: NOTE # 6 OK.
  
 NEW NOTES.
  
 7)NOTE: PLEASE SEE 620.23 FOR MIN
 REQUUIRED DEDICATED CIRCUIT(S) FOR
 ELEVATOR EQUIPMENT ADDED TO PLANS.
  
 8)NOTE: PLEASE SEE A BATTERY BACK UP EM
 LT WILL BE REQUIRED IN ELEV EQUIPMENT
 RM,7.8,700.16, ELEV SAFETY CODE.
  
 9)NOTE: PLEASE SEE FBC 2004CHAPTER 13
 FOR COMMERCIAL BLDGS.13-415.1.ABC.1.1&2
 FOR MEANS OF CONTROL FOR LIGHTING, SPACE
 CONTROL ETC.
  
 10)NOTE: PLEASE COMPLETE FIXTURE
 SCHEDULE SUBMITTED. PLEASE SEE FIXTURES
 NOW SHOWN ON PLANS WHICH ARE NOT LABELED
 OR ON FIX SCHEDULE?
  
 11)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO REPEAT
 COMMENTS AND DESIGN PROFESSIONALS.
  
 ** PLEASE SEE ON PREVIOUS REVIEW IT WAS
 REQUESTED TO REMOVE ALL OLD/VOIDED
 SHEETS AND TO INSERT NEW REVISED SHEETS
 INTO SETS AND TO SUBMIT ONE COPY OF THE
 OLD VOIDED SHEETS. THE NEW SHEETS WERE
 INSERTED, HOWEVER THE OLD /VOIDED SHEETS
 WERE NOT SUBMITTED FOR REFERENCE. PLEASE
 KNOW IT WILL HELP IN EXPEDITING THE
 REVIEW PROCESS BY SUBMITTING THE OLD
 SHEETS.
 IT ALSO HELPS THE REVIEW PROCESS OF A
 DETAILED RESPONSE LETTER FROM DESIGN
 PROFESIONAL IS SUBMITTED FOR TRADES
 ALSO. IT WAS NOTED, A DETAILED RESPONSE
 WAS SUBMITTED FOR "A" SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  