| 2006-03-07 00:00:00 | ********** UNSAT2ND REVIEW ********* |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW ,A ND NEW NOTES, DUE TO CHANGES |
| | IN PLANS AND FBC. |
| | PLEASE SEE NOTES BELOW ARE TAKEN |
| | DIRECTLY FROM FIRST REVIEW WITH NOTES |
| | FOR 2ND REVIEW DIRECTLY ABOVE. |
| | |
| | |
| | 1)NOTE: NOTE #1 OK, HOWEVER PLEASE SEE |
| | FACP WAS REMOVED FROM STAIR, HOWEVER |
| | THIS PANEL FOR THIS SPACE IS BEING SHOWN |
| | OUTSIDE TENANT SPACE? IS THIS PANEL THE |
| | BASE BLDG PANEL OR TENANT PANEL? |
| | PLEASE SEE FIRE REVIEW COMMENTS FRO |
| | LOCATION ETC. |
| | |
| | **PLEASE SEE THAT FIRE ALARM |
| | CONTROL PANEL SHALL "NOT" BE LOCATED IN |
| | THE STAIRWAY AS SHOWN. |
| | EQUIPMENT ONLY PERTAINING THE FUNCTION |
| | OF THE STAIRWAY MAY BE LOCATED IN THOSE |
| | LOCATIONS. |
| | PLEASE ALSO SEE NOTES FROM CHIEF FIRE |
| | MARSHAL. |
| | |
| | 2)NOTE:NOTE #2 NO. PLEASE SEE |
| | PHOTOMETRICS SUBMITTED ARE NOT SIGNED, |
| | DATED OR SEAL BY THE DESIGN PROFESSIONAL |
| | OR PERSON RESPONSIBLE FOR |
| | DESIGN/PLANS.106.3.4.3 |
| | PLEASE ALSO SEE MIN LIGHTING LEVELS DO |
| | NOT SEEM TO HAVE BEEN ACHIEVED. |
| | PLEASE SEE NFPA-101 7.8.1.3 |
| | |
| | **PLEASE SEE NFPA-101 2003, 7.8, |
| | 7.9 WHICH REQUIRES A MIN OF 10 |
| | FT/CANDLES AT STAIR EGRESS LOCATIONS. |
| | PLEASE SEE MIN FT CANDLES UNDER EM |
| | POWERE REQUIRED AT 1FT/CAN. |
| | PLEASE PROVIDE BRIEF PHOTO-METRICS FOR |
| | STAIR/EGRESS LOCATIONS. |
| | |
| | 3)NOTE:NOTE #3 NO, PLEASE SEE SOME |
| | CIRCUITING STILL MISSINGON PLANS FOR |
| | FIXTURES. PLEASE SEE EM LT, REDLINED |
| | PLANS. |
| | |
| | **PLEASE SHOW ALL CIRCUTING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULES. |
| | PLEASE SEE CIRCUTING FOR EM/EXT LTS |
| | SHALL BE PER 700.12E WHICH REQUIRES THE |
| | BRANCH CIRCUIT FEEDING THE UNIT |
| | EQUIPMENT SHALL BE THE SAME BRANCH |
| | CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD |
| | OF ANY LOCAL SWITCHES. |
| | |
| | 4)NOTE: NOTE #4 NO, PLEASE SEE CU'S ON |
| | MECHANICAL PLANS AND OCP INDICATED ON |
| | "M" SHEETS AND PANEL SCHEDULE. PLANS |
| | REDLINED. ( 25A, 30A?) |
| | |
| | ** PLEASE CORRELAT PANEL SCHEDULE, |
| | A/C EQUIPMENT AND LOADS. |
| | PLEASE SEE AHU'S SHOWN AS 3-PHASE IN |
| | LOADS AND ON SCHEDULE, HOWEVER ALSO |
| | NOTED AS 2-POLE BRKRS?? |
| | PLEASE SEE LOAD CALCULATIONS ONLY |
| | INCLUDES LOADS FOR ONE UNIT. |
| | PLEASE REVISE AS NEEDED. |
| | PLEASE ALSO CALRIFY WHAT SEEMS TO |
| | INDICATE 4-CU'S ON PANEL SCHEDULE, YET |
| | ONLY TWO AHU'S ARE SHOWN? |
| | |
| | 5)NOTE:NOTE #5 OK, (NOTED AS FUTURE). |
| | |
| | |
| | 6)NOTE: NOTE # 6 OK. |
| | |
| | NEW NOTES. |
| | |
| | 7)NOTE: PLEASE SEE 620.23 FOR MIN |
| | REQUUIRED DEDICATED CIRCUIT(S) FOR |
| | ELEVATOR EQUIPMENT ADDED TO PLANS. |
| | |
| | 8)NOTE: PLEASE SEE A BATTERY BACK UP EM |
| | LT WILL BE REQUIRED IN ELEV EQUIPMENT |
| | RM,7.8,700.16, ELEV SAFETY CODE. |
| | |
| | 9)NOTE: PLEASE SEE FBC 2004CHAPTER 13 |
| | FOR COMMERCIAL BLDGS.13-415.1.ABC.1.1&2 |
| | FOR MEANS OF CONTROL FOR LIGHTING, SPACE |
| | CONTROL ETC. |
| | |
| | 10)NOTE: PLEASE COMPLETE FIXTURE |
| | SCHEDULE SUBMITTED. PLEASE SEE FIXTURES |
| | NOW SHOWN ON PLANS WHICH ARE NOT LABELED |
| | OR ON FIX SCHEDULE? |
| | |
| | 11)NOTE: PLEASE SEE COPY OF FS |
| | 553.80(2)(B) WITH RESPECT TO REPEAT |
| | COMMENTS AND DESIGN PROFESSIONALS. |
| | |
| | ** PLEASE SEE ON PREVIOUS REVIEW IT WAS |
| | REQUESTED TO REMOVE ALL OLD/VOIDED |
| | SHEETS AND TO INSERT NEW REVISED SHEETS |
| | INTO SETS AND TO SUBMIT ONE COPY OF THE |
| | OLD VOIDED SHEETS. THE NEW SHEETS WERE |
| | INSERTED, HOWEVER THE OLD /VOIDED SHEETS |
| | WERE NOT SUBMITTED FOR REFERENCE. PLEASE |
| | KNOW IT WILL HELP IN EXPEDITING THE |
| | REVIEW PROCESS BY SUBMITTING THE OLD |
| | SHEETS. |
| | IT ALSO HELPS THE REVIEW PROCESS OF A |
| | DETAILED RESPONSE LETTER FROM DESIGN |
| | PROFESIONAL IS SUBMITTED FOR TRADES |
| | ALSO. IT WAS NOTED, A DETAILED RESPONSE |
| | WAS SUBMITTED FOR "A" SHEETS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |