| 2006-03-22 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | SECOND REVIEW |
| | |
| | COMMENTS FROM FIRST REVIEW: |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | PLEASE KEEP THE NOC PROVIDED IN THE |
| | PERMIT APPLICATION PACKAGE. |
| | |
| | 2.)PLEASE ADJUST THE VALUE ON THE |
| | PERMIT APPLICATION.I UNDERSTAND THAT |
| | THIS AMOUNT IS FOR THE DEMOLITION ONLY, |
| | WHICH WILL BE ON A SEPARATE PERMIT. |
| | |
| | NOT ADDRESSED. |
| | |
| | 3. - 7.)ADDRESSED. |
| | |
| | 8.)PROVIDE CERTIFICATION IN REGARDS TO |
| | THE FLOOR LOADING, SECOND FLOOR.SHOW |
| | COMPLIANCE WITH FBC TABLE 1607.1. |
| | |
| | THE NOTE DOES NOT INDICATE THAT THIS IS |
| | A FLOOR CERTIFICATION.IT APPEARS TO BE |
| | THE DESIGN CRITERIA.AS IT IS EXISTING, |
| | DESIGN CRITERIA DOES NOT SHOW |
| | COMPLIANCE. |
| | |
| | 9. ? 10)ADDRESSED. |
| | |
| | 11.)VERTICAL ACCESSIBILITY REQUIRED, |
| | FBC EB 806, FBC11-4.1.6(1)(B). |
| | |
| | ADDRESSED, BUT PLEASE SHOW SIGNAGE |
| | REQUIRED BY FBC11-4.10.5. |
| | |
| | 12.)THE WEST END OF THE MEZZANINE HAS |
| | A 6IN STEP.SEE FBC11-4.1(1)(A).AN |
| | ACCESSIBLE ROUTE SHALL CONNECT |
| | ACCESSIBLE ELEMENTS AND SPACES, |
| | FBC11-4.1.2(2). |
| | |
| | A CONCRETE RAMP IS NOW SHOWN.INDICATE |
| | ON THE PLAN WHAT THE ADDITIONAL LOAD IS |
| | AND CONFIRM THAT THE EXISTING CONDITIONS |
| | CAN ACCOMDATE THE ADDITIONAL DEAD LOAD. |
| | |
| | SHOW RAMP WIDTH, BOTH RAMPS, |
| | FBC11-4.8.3. |
| | |
| | 13-16.)ADDRESSED. |
| | |
| | 17.)PROVIDE A FIRE SPRINKLER |
| | SCHEMATIC, FBC*106.3.5.1.1(5). |
| | |
| | THIS WAS PROVIDED.CLARIFY AS TO WHY |
| | THERE ARE NOT SPRINKLER HEADS, FIRST |
| | FLOOR, IN THE ENTRY AREA AND CENTER. |
| | ALSO CLARIFY AS TO HOW THE SPRINKLER |
| | HEADS SECOND FLOOR, 28FT ABOVE FINISH |
| | FLOOR, IN THE OPEN AREA WILL BE |
| | EFFFECTIVE. |
| | |
| | 18-19.)ADDRESSED. |
| | |
| | 20.)ADDRESSED. |
| | |
| | 21.)PROVIDE DETAILS FOR THE EXISTING |
| | STAIRS AND HANDRAILS.SHOW COMPLIANCE |
| | WITH FBC1009, FBC11-4.9. |
| | |
| | RESPONSE LETTER STATES THAT THERE ARE |
| | TWO EXITS.ONLY ONE SHOWN ON THE LIFE |
| | SAFETY PLAN FOR BOTH THE FIRST FLOOR AND |
| | THE SECOND FLOOR.EXIT LIGHTS SHOULD BE |
| | SHOWN AT ALL EXITS.THE TWO EXITS ARE |
| | TO BE REMOTELY LOCATED FBC104.2.1(2). |
| | THE DISTANCE BETWEEN THE TWO STAIRS, |
| | SECOND FLOOR DO NOT APPEAR TO BE ONE |
| | THIRD DISTANCE APART.INDICATE ON THE |
| | PLAN THAT BOTH EXITS ARE ACCESSIBLE |
| | (SHOW ELEVATION CHANGE AT DOORWAYS). |
| | |
| | REVISE THE LIFE SAFETY PLAN AND ELECTRIC |
| | PLAN TO CLEARLY SHOW TWO EXITS WHICH DO |
| | NOT EXCEED TRAVEL DISTANCE OR COMMON |
| | PATH OF TRAVEL. |
| | |
| | DETAIL 3A7, THE STAIR RAIL ALSO SERVES |
| | AS A GUARDRAIL.THE HEIGHT IS TO COMPLY |
| | WITH FBC1012.2. |
| | |
| | 22.)SHOW REQUIRED TENANT SEPARATION ON |
| | THE EXISTING WALLS, FBC708. |
| | |
| | NO SEPARATION SHOWN BETWEEN BLDG ELEC |
| | AND THE RENOVATED SPACE. |
| | |
| | SHOW CONTINUITY REQUIRED BY FBC708.4. |
| | |
| | 23-26.)ADDRESSED. |
| | |
| | 27.)PRODUCT APPROVALS ARE TO BE |
| | REVIEWED BY DESIGNER OF RECORD, |
| | FBC*106.3.3. |
| | |
| | NO PRODUCT APPROVALS SUBMITTED.PLEASE |
| | HAVE REVIEWED BY DOR AND SUBMIT. |
| | |
| | NEW COMMENTS: |
| | |
| | 28.)ELEVATOR IS TO CONFORM TO |
| | ASME17.1, FBC30.NOTE THE REQUIREMENT |
| | ON THE PLAN. |
| | |
| | 29.)PROVIDE ELEVATOR SIGNAGE |
| | FBC3002.3. |
| | |
| | 30.)DECLARE OCCUPANCY OF ADJACENT |
| | SPACES, INCLUDING THE THIRD FLOOR.SEE |
| | FBC TABLE 302.3.2.SHOW OCCUPANCY |
| | SEPARATION OR TENANT SEPARATION AND |
| | CONTINUITY FBC706.4. |
| | |
| | 31.)FBC1019.1.5, STORAGE IS SHOWN |
| | UNDER STAIR 2.SHOW REQUIRED FIRE |
| | PROTECTION AND SPRINKLER. |
| | |
| | 32.)SEE ATTACHED FS553(80)(2)(B).A |
| | 4X PLAN REVIEW FEE IS REQUIRED TO BE |
| | CHARGED IF COMMENTS NOT PROPERLY |
| | ADDRESSED A THIRD TIME. |
| | |
| | |
| | |