| Plan Review Notes For Permit 05100006 |
| Permit Number |
05100006 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-11-10 00:00:00 | 1. DEMOLITION, RENOVATION, AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | 2. DEBRIS SHALL BE REMOVED FROM THE | | | SITE DAILY. | | | | | | 3. NO CUTTING OR WELDING ALLOWED WITHOUT | | | APPROVAL OF THE FIRE PREVENTION BUREAU | | | AND WITH COMPLIANCE WITH NFPA 51B. | | | | | | 4. PLANS DISPLAY RELOCATED FIRE ALARM | | | AND SECURITY PANEL TO BE PLACED INSIDE | | | STAIRWELL. THIS ACTIVITY WILL NOT BE | | | ALLOWED. | | | | | | 5. PLEASE PROVIDE PRESCRIPTIVE STRENGTH | | | REQUIREMENTS FOR ALL GUARDRAILS. LOCATED | | | INFORMATION ON PAGE A-5. | | | | | | 6. A CHANGE OF USE IS OCCURING. ALL NEW | | | MERCANTILE REQUIREMENTS SHALL BE MET. | | | | | | 7. BUILDING ADDRESS REQUIRED ON | | | ELEVATION. A MINIMUM OF AT LEAST 6" | | | HIGH NUMBERS ARE REQUIRED. | | | | | | 8. SEPERATE PLANS AND PERMITS REQUIRED | | | FOR FIRE ALARM SYSTEM EQUIPMENT. | | | | | | 9.SEPERATE PLANS AND PERMITS REQUIRED | | | FOR FIRE SPRINKLER SYSTEM REMODEL. | | | | | | 10. PLEASE PROVIDE A LIFE SAFETY PLAN | | | AND ILLUSTRATE EXITING RATIONALE FOR | | | PROPOSED SPACE. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER |
|