| 2005-11-17 00:00:00 | ********** UNSAT ************** |
| | |
| | |
| | 1)NOTE: PLEASE SEE THAT FIRE ALARM |
| | CONTROL PANEL SHALL "NOT" BE LOCATED IN |
| | THE STAIRWAY AS SHOWN. |
| | EQUIPMENT ONLY PERTAINING THE FUNCTION |
| | OF THE STAIRWAY MAY BE LOCATED IN THOSE |
| | LOCATIONS. |
| | PLEASE ALSO SEE NOTES FROM CHIEF FIRE |
| | MARSHAL. |
| | |
| | 2)NOTE: PLEASE SEE NFPA-101 2003, 7.8, |
| | 7.9 WHICH REQUIRES A MIN OF 10 |
| | FT/CANDLES AT STAIR EGRESS LOCATIONS. |
| | PLEASE SEE MIN FT CANDLES UNDER EM |
| | POWERE REQUIRED AT 1FT/CAN. |
| | PLEASE PROVIDE BRIEF PHOTO-METRICS FOR |
| | STAIR/EGRESS LOCATIONS. |
| | |
| | 3)NOTE: PLEASE SHOW ALL CIRCUTING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULES. |
| | PLEASE SEE CIRCUTING FOR EM/EXT LTS |
| | SHALL BE PER 700.12E WHICH REQUIRES THE |
| | BRANCH CIRCUIT FEEDING THE UNIT |
| | EQUIPMENT SHALL BE THE SAME BRANCH |
| | CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD |
| | OF ANY LOCAL SWITCHES. |
| | |
| | 4)NOTE: PLEASE CORRELAT PANEL SCHEDULE, |
| | A/C EQUIPMENT AND LOADS. |
| | PLEASE SEE AHU'S SHOWN AS 3-PHASE IN |
| | LOADS AND ON SCHEDULE, HOWEVER ALSO |
| | NOTED AS 2-POLE BRKRS?? |
| | PLEASE SEE LOAD CALCULATIONS ONLY |
| | INCLUDES LOADS FOR ONE UNIT. |
| | PLEASE REVISE AS NEEDED. |
| | PLEASE ALSO CALRIFY WHAT SEEMS TO |
| | INDICATE 4-CU'S ON PANEL SCHEDULE, YET |
| | ONLY TWO AHU'S ARE SHOWN? |
| | |
| | 5)NOTE: PLEASE SEE WATER HEATER IS SHOWN |
| | AS A 5KW UNIT ON A 1-POLE 25A BRKR? |
| | PLEASE ADJUST.(MISPRINT). |
| | |
| | 6)NOTE: PLEASE VERIFY PLANS AND RISER AS |
| | PLANS INDICATE (2) PANEL "B"'S BEING |
| | LOCATED AT LOCATION, ONE BEING RELOCATED |
| | AND ONE BEING ABANDONED? |
| | RISER DOES NOT INCLUDE THE 2ND PANEL |
| | "B". |
| | PLEASE NOTE, IF CIRCUITS FROM THIS |
| | ABANDONED PANEL ARE BEING RELOCATED?? |
| | 215.5 |
| | |
| | ** PLEASE SEE ANY POSSIBLE NOTES FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD/VOIDED SHEETS SHOULD BE |
| | SUBMITTED BACK WITH NEW SETS FOR |
| | REFERENCE OF OLD/VOIDED SHEETS. |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |