Plan Review Notes
Plan Review Notes For Permit 05100006
Permit Number 05100006
Review Stop B
Sequence Number 1
Notes
Date Text
2005-12-20 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)PLEASE ADJUST THE VALUE ON THE
 PERMIT APPLICATION.I UNDERSTAND THAT
 THIS AMOUNT IS FOR THE DEMOLITION ONLY,
 WHICH WILL BE ON A SEPARATE PERMIT.
  
 3.)THE ENERGY CALCS STATE THAT THE
 AREA IS 6708, SHEET COV IS 6762.
  
 4.)ALTHOUGH THE PLANS REFER TO THE
 SECOND STORY AS A MEZZANINE, IT IS NOT A
 MEZZANINE BY DEFINITION, FBC502.1.
  
 5.)COV, GENERAL NOTE #2 REFERS TO
 FBC2001.GOVERNING CODE IS FBC2004
 EFFECTIVE OCTOBER 1, 2005.
  
 6.)PROVIDE TOTAL AREA OF THE BUILDING,
 FBC EB CODE CHAPTER 3.
  
 7.)A CHANGE OF OCCUPANCY IS TO COMPLY
 WITH FBC EB CHAPTERS 5 THROUGH 7, FBC EB
 812.1.2.
  
 8.)PROVIDE CERTIFICATION IN REGARDS TO
 THE FLOOR LOADING, SECOND FLOOR.SHOW
 COMPLIANCE WITH FBC TABLE 1607.1.
  
 9.)SEE ATTACHED POLICY, ITEMS 13 AND
 14, IN REGARDS TO IMPACT PROTECTION.
 USE OF REMOVABLE SHUTTERS ON THE SECOND
 FLOOR OF COMMERCIAL BUILDINGS IS
 PROHIBITED.USE OF REMOVABLE SHUTTERS
 ON THE FIRST FLOOR REQUIRES APPROVAL BY
 THE BUILDING OFFICIAL.
  
 10.)THERE IS NO ACCESS TO THE TOILET
 VESTIBULE.ADDRESS.
  
 11.)VERTICAL ACCESSIBILITY REQUIRED,
 FBC EB 806, FBC11-4.1.6(1)(B).
  
 12.)THE WEST END OF THE MEZZANINE HAS
 A 6IN STEP.SEE FBC11-4.1(1)(A).AN
 ACCESSIBLE ROUTE SHALL CONNECT
 ACCESSIBLE ELEMENTS AND SPACES,
 FBC11-4.1.2(2).
  
 13.)WHAT WAS LOCATED IN THE AREA
 MARKED ?VOID? ON THE PLAN?
  
 14.)SHOW THE PROPERTY LINE ON THE
 PLAN, OR PROVIDE A SITE PLAN.THE
 EXTERIOR STAIR DOOR SHALL NOT OPEN INTO
 THE PUBLIC RIGHT-OF-WAY.SEE FBC EB
 812.1.2, FBC EB 605, FBC3202.2.
  
 15.)THE AWNING IS TO COMPLY WITH
 FBC3202.3.1.SHOW COMPLIANCE ON THE
 PLAN.
  
 16.)DOES THE ELEVATOR OPEN INTO A
 COMMON AREA?
  
 17.)PROVIDE A FIRE SPRINKLER
 SCHEMATIC, FBC*106.3.5.1.1(5).
  
 18.)SPECIFY INTERIOR FINISH
 CLASSIFICATION FBC803.
  
 19.)SPECIFY WALL FINISH IN THE
 BATHROOMS, FBC1210.2.
  
 20.)PROVIDE A ROOM DESIGNATION,
 MEZZANINE WEST, AT DOOR 21.IF THIS IS
 STORAGE PROVIDE INFORMATION AS TO WHAT
 WILL BE STORED THERE AND AREA
 CALCULATION, SEE FBC302.3.2, FBC309.
  
 21.)PROVIDE DETAILS FOR THE EXISTING
 STAIRS AND HANDRAILS.SHOW COMPLIANCE
 WITH FBC1009, FBC11-4.9.
  
 22.)SHOW REQUIRED TENANT SEPARATION ON
 THE EXISTING WALLS, FBC708.
  
 23.)SHOW MANEUVERING CLEARANCE, PULL
 SIDE, FOR DOORS 21, 15, FBC11-4.13.6,
 FIGURE 11-25.
  
 24.)THE ACCESSIBLE WATER CLOSET SHALL
 BE LOCATED IN THE CORNER, DIAGONAL TO
 THE DOOR, FBC11-4.17.3 EXCEPTION (2).
  
 25.)PROVIDE A DETAIL FOR PENETRATIONS
 THROUGH THE TENANT SPACES ABOVE.
  
 26.)PROVIDE A MINIMUM CLEARANCE FOR
 THE CONDENSING UNIT, M2, FBC TABLE
 1509.7.
  
 27.)PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD,
 FBC*106.3.3.