| 2005-12-20 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)PLEASE ADJUST THE VALUE ON THE |
| | PERMIT APPLICATION.I UNDERSTAND THAT |
| | THIS AMOUNT IS FOR THE DEMOLITION ONLY, |
| | WHICH WILL BE ON A SEPARATE PERMIT. |
| | |
| | 3.)THE ENERGY CALCS STATE THAT THE |
| | AREA IS 6708, SHEET COV IS 6762. |
| | |
| | 4.)ALTHOUGH THE PLANS REFER TO THE |
| | SECOND STORY AS A MEZZANINE, IT IS NOT A |
| | MEZZANINE BY DEFINITION, FBC502.1. |
| | |
| | 5.)COV, GENERAL NOTE #2 REFERS TO |
| | FBC2001.GOVERNING CODE IS FBC2004 |
| | EFFECTIVE OCTOBER 1, 2005. |
| | |
| | 6.)PROVIDE TOTAL AREA OF THE BUILDING, |
| | FBC EB CODE CHAPTER 3. |
| | |
| | 7.)A CHANGE OF OCCUPANCY IS TO COMPLY |
| | WITH FBC EB CHAPTERS 5 THROUGH 7, FBC EB |
| | 812.1.2. |
| | |
| | 8.)PROVIDE CERTIFICATION IN REGARDS TO |
| | THE FLOOR LOADING, SECOND FLOOR.SHOW |
| | COMPLIANCE WITH FBC TABLE 1607.1. |
| | |
| | 9.)SEE ATTACHED POLICY, ITEMS 13 AND |
| | 14, IN REGARDS TO IMPACT PROTECTION. |
| | USE OF REMOVABLE SHUTTERS ON THE SECOND |
| | FLOOR OF COMMERCIAL BUILDINGS IS |
| | PROHIBITED.USE OF REMOVABLE SHUTTERS |
| | ON THE FIRST FLOOR REQUIRES APPROVAL BY |
| | THE BUILDING OFFICIAL. |
| | |
| | 10.)THERE IS NO ACCESS TO THE TOILET |
| | VESTIBULE.ADDRESS. |
| | |
| | 11.)VERTICAL ACCESSIBILITY REQUIRED, |
| | FBC EB 806, FBC11-4.1.6(1)(B). |
| | |
| | 12.)THE WEST END OF THE MEZZANINE HAS |
| | A 6IN STEP.SEE FBC11-4.1(1)(A).AN |
| | ACCESSIBLE ROUTE SHALL CONNECT |
| | ACCESSIBLE ELEMENTS AND SPACES, |
| | FBC11-4.1.2(2). |
| | |
| | 13.)WHAT WAS LOCATED IN THE AREA |
| | MARKED ?VOID? ON THE PLAN? |
| | |
| | 14.)SHOW THE PROPERTY LINE ON THE |
| | PLAN, OR PROVIDE A SITE PLAN.THE |
| | EXTERIOR STAIR DOOR SHALL NOT OPEN INTO |
| | THE PUBLIC RIGHT-OF-WAY.SEE FBC EB |
| | 812.1.2, FBC EB 605, FBC3202.2. |
| | |
| | 15.)THE AWNING IS TO COMPLY WITH |
| | FBC3202.3.1.SHOW COMPLIANCE ON THE |
| | PLAN. |
| | |
| | 16.)DOES THE ELEVATOR OPEN INTO A |
| | COMMON AREA? |
| | |
| | 17.)PROVIDE A FIRE SPRINKLER |
| | SCHEMATIC, FBC*106.3.5.1.1(5). |
| | |
| | 18.)SPECIFY INTERIOR FINISH |
| | CLASSIFICATION FBC803. |
| | |
| | 19.)SPECIFY WALL FINISH IN THE |
| | BATHROOMS, FBC1210.2. |
| | |
| | 20.)PROVIDE A ROOM DESIGNATION, |
| | MEZZANINE WEST, AT DOOR 21.IF THIS IS |
| | STORAGE PROVIDE INFORMATION AS TO WHAT |
| | WILL BE STORED THERE AND AREA |
| | CALCULATION, SEE FBC302.3.2, FBC309. |
| | |
| | 21.)PROVIDE DETAILS FOR THE EXISTING |
| | STAIRS AND HANDRAILS.SHOW COMPLIANCE |
| | WITH FBC1009, FBC11-4.9. |
| | |
| | 22.)SHOW REQUIRED TENANT SEPARATION ON |
| | THE EXISTING WALLS, FBC708. |
| | |
| | 23.)SHOW MANEUVERING CLEARANCE, PULL |
| | SIDE, FOR DOORS 21, 15, FBC11-4.13.6, |
| | FIGURE 11-25. |
| | |
| | 24.)THE ACCESSIBLE WATER CLOSET SHALL |
| | BE LOCATED IN THE CORNER, DIAGONAL TO |
| | THE DOOR, FBC11-4.17.3 EXCEPTION (2). |
| | |
| | 25.)PROVIDE A DETAIL FOR PENETRATIONS |
| | THROUGH THE TENANT SPACES ABOVE. |
| | |
| | 26.)PROVIDE A MINIMUM CLEARANCE FOR |
| | THE CONDENSING UNIT, M2, FBC TABLE |
| | 1509.7. |
| | |
| | 27.)PRODUCT APPROVALS ARE TO BE |
| | REVIEWED BY DESIGNER OF RECORD, |
| | FBC*106.3.3. |