| Plan Review Notes For Permit 05091714 |
| Permit Number |
05091714 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-07-06 00:00:00 | DENIED:2001 FBC/CLUBHOUSE | | | | | | PLAN SHEET M-9, PLEASE NOTE, EF-2 IS | | | WITHIN 10 FT OF THE O/A INTAKE LOUVER. | | | PER 2001 FMC 501.3, MECHANICAL EXHAUST | | | SHALL TERMINATE OUTDOORS AT A POINT | | | WHERE IT WILL NOT CAUSE A NUISANCE AND | | | FROM WHICH IT CANNOT BE READILY DRAWN IN | | | BY VENTILATING SYSTEM. | | | | | | EXHAUST SHALL NOT TERMINATE ONTO | | | WALKWAYS PER 2001 FMC 401.5.2. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|