| 2006-01-13 00:00:00 | DENIED: |
| | PLANS REVIEWED UNDER THE 2004 FBC. |
| | PLANS DO NOT INDICATE WHICH CODE THE |
| | BUIDLINGS ARE DESIGNED. |
| | |
| | 1.PROVIDE BUILDING TYPE, INDICATE |
| | PROTECTED OR UNPROTECTED. |
| | |
| | 2.PLAN SHEET A2 SEPARATION BETWEEN THE |
| | GARAGE AND THE RESIDENCE IS INDICATED AS |
| | A 2 HOUR SEPARATION ACCORDING TO THE |
| | WALL TYPE LISTED ON PLAN SHEET A-26. |
| | MECHANICAL PLAN M1 INDICATES DUCTWORK |
| | PENETRATING RATED WALL WITHOUT |
| | PROTECTION.PLEASE INDICATE ON THE |
| | PLANS COMPLIANCE WITH ALL THE |
| | REQUIREMENTS LISTED UNDER 2004 FMC |
| | 607.5.3 EXCEPTIONS 1 AND 2. |
| | |
| | 3.PLANS SHEET M-1 INDICATES BATHROOM |
| | EXHAUST PENETRATING THROUGH 2ND & 3RD |
| | FLOORS TO THE ROOF.PLEASE INDICATE |
| | PROTECTION THROUGH RATED FLOOR. |
| | |
| | 4.PLAN SHEET M-3 & M-5 INDICATES |
| | REFRIGERANT LINES & EXHAUST DUCT IN A |
| | "CHASE".PLEASE CLARIFY IN THE "CHASE" |
| | IS RATED.SHOW COMPLIANCE WITH 2004 FMC |
| | 607.5.5.1.PLEASE NOTE, FIRE DAMPERS & |
| | ACCESS DOORS ARE REQUIRED TO BE |
| | INDENTIFFIED ON PLANS PER 2004 FMC |
| | 607.8. |
| | |
| | 5.PLEASE NOTE, EXHAUST DUCT SHALL |
| | COMPLY WITH 2004 FMC 501.4. |
| | |
| | 6.PLAN SHEET M-1 INDICATES "MATCH |
| | LINE" M-2.M-2, M-4 & M-6 WERE NOT |
| | SUBMITTED FOR |
| | REVIEW. |
| | |
| | 7.PLAN SHEET M-3, DRYER EXHAUST |
| | APPEARS TO EXCEED THE 25FT REQUIREMENT |
| | IN 504.6 OF THE 2004 FMC. |
| | |
| | 8.PLAN SHEET M-3 & M-5 INDICATES |
| | REFRIGERANT LINES & EXHAUST DUCT IN A |
| | "CHASE".PLEASE CLARIFY IF THE "CHASE" |
| | IS RATED.SHOW COMPLIANCE WITH 2004 FMC |
| | 607.5.5.1.PLEASE NOTE, FIRE DAMPERS & |
| | ACCESS DOORS ARE REQUIRED TO BE |
| | IDENTIFIED ON PLANS PER 2004 FMC 607.8. |
| | |
| | 9.PLEASE PROVIDE A DETAIL OF THE |
| | TERMINATION OF REFRIGERANT LINES & |
| | EXHAUST DUCT LOCATED ON THE ROOF IN THE |
| | HVAC EQUIPMENT ROOM. |
| | |
| | 10. PER 2004 FMC 501.2, EXHAUST AIR |
| | SHALL BE DISCHARGED TO THE OUTDOORS AT A |
| | POINT WHERE IT WILL NOT CREATE A |
| | NUISANCE OR CANNOT BE READLY DRAWN IN BY |
| | THE VENTILATING SYSTEM. |
| | |
| | 11. PLAN SHEET M-3 AHU-L DUCT PENETRATES |
| | FLOOR AND CEILING PLEASE SHOW COMPLIANCE |
| | WITH 2004 FMC 607.6. |
| | |
| | 12. PLEASE CLARIFY THE HVAC EQUIPMENT |
| | ROOMS LOCATED ON THE ROOF.THE |
| | CONDENSING UNITS ARE LOCATED IN THE |
| | EQUIPMENT ROOMS.WILL THIS BE ENCLOSED? |
| | PLEASE PROVIDE MANUFACTURER SUBMITTAL |
| | FOR THE CONDENSERS INDICATING THEY ARE |
| | PERMITTED TO BE INSTALLED IN AN ENCLOSED |
| | AREA WHICH ESSENTIALLY IS INDOORS. |
| | |
| | 13. PLEASE PROVIDE DETAIL OF THE |
| | MOUNTING OF THE CONDENSING UNITS. |
| | |
| | 14. PLEASE PROVIDE OUTSIDE AIR |
| | CALCULATIONS IN ACCORDANCE WITH 2004 FMC |
| | 403.3. |
| | |
| | 15. PLAN SHEET M-3 RETURN AIR FROM THE |
| | BEDROOM AREAS ARE NOT SIZED PROPERLY. |
| | RETURN AIR "JUMPERS" SHALL COMPLY WITH |
| | 2004 FMC 601.4 EXCEPTION #1. |
| | |
| | 16. PLAN SHEET M-3 THE MASTER SUITE |
| | SHALL BE SIZED IN ACCORDANCE WITH 2004 |
| | FMC 601.4 EXCEPTION 1 AND 3.PLEASE |
| | REVISE. |
| | |
| | 17. PLAN SHEET M-5 RETURN AIR FROM THE |
| | BOTH BEDROOMS SHALL COMPLY WITH 2004 FMC |
| | 601.4 EXCEPTION 1 AND 3. |
| | |
| | 18. AUH DETAIL DOES NOT INDICATE |
| | OVERFLOW PROTECTION PER 2004 FMC |
| | 307.2.3. |
| | |