| 2006-07-05 00:00:00 | DENIED:2001 FBC/ BUILDING #1 |
| | RESPONSE TO COMMENTS DATED 1/13/06 |
| | |
| | COMMENT #1 - OK |
| | COMMENT #2 - OK |
| | COMMENT #3 - OK |
| | COMMENT #4 - OK PLEASE CLARIFY PLAN |
| | SHEET M-8 EXHAUST DUCT ROOF CAP DETAIL. |
| | WILL EACH TOILET EXHAUST TERMINATE TO |
| | THE OUTDOORS OR WILL THIS BE A |
| | 'SUB-DUCT' METHOD? |
| | COMMENT #5 - OK |
| | COMMENT #6 - OK |
| | COMMENT #7 - PLEASE DNOTE, THE 2001 FMC |
| | DOES NOT GIVE THE OPTION FOR THE |
| | INSTALLATION OF BOOSTER FANS ON THE |
| | DRYER EXHAUST.THIS MUST BE SUBMITTED |
| | TO THE BUILDING OFFICAL UNDER "ALTERNATE |
| | MATERIALS & METHODS" 2001 AMENDMENTS TO |
| | THE 2001 FBC 103.7.1.PLEASE PROVIDE |
| | SUBMITTAL FOR THE BOOSTER FAN.NOTE #3 |
| | ON M-3 INDICATES THE BOOSTER FAN IS |
| | "MANUFACTURER'S RECOMMENDED" UL LISTED |
| | BOOSTER FAN.PLEASE ALSO PROVIDE A |
| | LETTER FROM AN ENGINEER EMPLOYED BY THE |
| | MANUFACTURER GIVING THE MANUFACTURER'S |
| | APPROVAL FOR THIS INSTALLATION. |
| | COMMENT #8 - OK |
| | COMMENT #9- PLEASE NOTE, SHAFT |
| | ENCLOSING THE REFRIGERANT LINES SHALL BE |
| | VENTED IN ACCORDANCE WITH ASHRAE 15-1992 |
| | SECTUIB 11.12.3 (B). |
| | COMMENT #10 - OK |
| | COMMENT #11 - AHU-L DUCT SHALL BE IN A |
| | RATED SHAFT IN ACCORDANCE WITH 2001 FMC |
| | 607.4. |
| | COMMENT #12 - OK |
| | COMMENT #13 - RESPONSE INDICATES PRODUCT |
| | APPROVAL FOR THE CONDENSING UNIT STANDS |
| | IS ATTACHED TO THE PLANS.PLEASE NOTE, |
| | PRODUCT APPROVAL IS NOT ATTACHED TO |
| | PERMIT APPLICATION OR PLAN.PLEASE |
| | PROVIDE FLORIDA STATE PRODUCT APPROVAL. |
| | COMMENT #14 - OK |
| | COMMENT #15 - OK |
| | COMMENT #16 - OK |
| | COMMENT #17 - OK |
| | COMMENT #18 - RESPONSE INDICATES FLOAT |
| | SWITCH FOR OVERFLOW PROTECTION.PLEASE |
| | INDICATE LOCATION OF THE FLOAT SWITCH. |
| | PLEASE NOTE, FLOAT SWITCH IS NOT TO BE |
| | INSTALLED IN THE PRIMARY DRAIN PAN.IT |
| | SHALL BE INSTALLED IN THE OVERFLOW OR |
| | SECONDARY DRAIN SHOULD THIS UNIT BE A |
| | BOTTOM RETURN. SHOULD THE RETURN BE |
| | LOCATED IN THE SIDE AN AUXILIARY DRAIN |
| | PAN WILL BE REQUIRED. |
| | |
| | ****************NEW COMMENTS************ |
| | 19. PLAN SHEET M-3 NOTE 2 INDICATES |
| | RETURN AIR THROUGH LOUVERED DOOR AT THE |
| | AHU CLOSET.PLEASE NOTE, LOUVERED DOOR |
| | & FRAME SHALL BE NON-COMBUSTIBLE AS |
| | REQUIRED PER 2001 FMC 602.2.1. |
| | |
| | 20. PLAN SHEET M-5 SHOWS REFRIGERANT |
| | LINES THROUGH THE STAIRWELL.PER 2001 |
| | FBC 1006.1.3.1 THIS IS PROHIBITED. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATT KRAUSS AT (561)805-6719. |