| 2006-07-18 00:00:00 | ***DENIED*** |
| | |
| | PLEASE NOTE THAT A RESPONSE LETTER |
| | ADDRESSING THE FIRE REVIEW WAS NOT FOUND |
| | WITH THIS SUBMITTAL. PLEASE BE ADVISED |
| | THAT THIS WILL HELP EXPEDITE THE PLAN |
| | REVIEW PROCESS. |
| | |
| | 1) COMPLETE CIVIL DRAWINGS ARE TO BE |
| | SUBITTED ILLUSTRATING FIRE HYDRANTS AND |
| | WATER AND FIRE MAIN SIZES. ALL BACK FLOW |
| | PREVENTION DEVICES ARE TO BE SHOWN. |
| | |
| | 2) FIRE HYDRANT SPACING IS NOT TO EXCEED |
| | 300-500' APART. |
| | |
| | 3) WET FIRE HYDRANTS ARE REQUIRED PRIOR |
| | TO, DURING AND AFTER CONSTRUCTION. |
| | |
| | 4) SUITABLE ROADS ARE TO BE PROVIDED |
| | DURING CONSTRUCTION FOR EMERGENCY |
| | EQUIPMENT. |
| | |
| | 5) BUILDING ADDRESSES ARE REQUIRED. A |
| | MINIMUM OF AT LEAST 6" HIGH NUMBERS ARE |
| | REQUIRED. |
| | |
| | 6) ALL FIRE HYDRANTS ARE TO BE PROVIDED |
| | WITH PROPER CLEARANCES TO THE FRONT AND |
| | SIDES OF THEM. |
| | |
| | 7) ALL HANDRAILS AND GUARDS ARE TO MEET |
| | PRESCIPTIVE STRENGTH REQUIREMENTS PER |
| | THE FLORIDA BUILDING CODE AND THE |
| | FLORIDA FIRE PREVENTION CODE. |
| | |
| | 8) PLEASE EXPLAIN STORAGE AREAS NEAR |
| | EXIT STAIRS LOCATED ON THE SECOND FLOOR, |
| | CENTER CORE. |
| | |
| | 9) A COMPLETE AUTOMATIC SUPERVISED FIRE |
| | SPRINKLER SYSTEM IS REQUIRED IN ALL (3) |
| | STORY BUILDINGS. PLEASE COMPLETE PLANS |
| | AND PERMITS AS REQUIRED. |
| | |
| | 10) THE FIRE ALARM SYSTEM IS TO BE |
| | MONITORED BY A LICENSED UL LISTED |
| | CENTRAL STATION APPROVED FOR CENTRAL |
| | STATION SERVICE. COMPLETE PLANS AND |
| | PERMITS REQUIRED PRIOR TO INSTALLATION. |
| | |
| | 11) FIRE LINE BACKFLOW DEVICE SHALL BE |
| | EQUIPPED WITH TAMPER SWITCHES, CHAIN AND |
| | LOCK. |
| | |
| | 12) A REVIEW OF THE CIVIL DRAWINGS |
| | INDICATE THAT ADDITIONAL FIRE HYDRANTS |
| | ARE NEEDED. FIRE DEPARTMENT SPRINKLER |
| | CONNECTIONS SHALL BE LOCATED NO FURTHER |
| | THAN 150' FROM A FIRE HYDRANT. |
| | |
| | 13) THERE APPEARS TO BE NO FIRE HYDRANTS |
| | LOCATED ON THE APPROACH OR INTO THE |
| | COMPLEX. |
| | |
| | 14) ALL SMOKE DETECTORS ARE TO BE |
| | INSTALLED A MINIMUM OF (3)' FROM HVAC |
| | DIFFUSERS. |
| | |
| | 15) FIRE ALARM VISIBLE SIGNALS SHALL BE |
| | PROVIDED IN ROOMS DESIGNED FOR THE |
| | HEARING IMPAIRED. |
| | |
| | 16)PLEASE INDICATE THE MINIMUM INTERIOR |
| | FINISH CLASSIFICATION FOR WALLS AND |
| | CEILINGS. |
| | |
| | 17) ALL RESIDENTIAL BUILDINGS ARE TO |
| | COMPLY WITH CHAPTER 30, NFPA 101, 2003 |
| | EDITION. |
| | |
| | 18) ALL COMMON BUILDING STAIRS ARE TO BE |
| | PROVIDED WITH EMERGENCY LIGHTING |
| | EQUIPMENT. |
| | |
| | 19) PLEASE EXPLAIN EXIT DISCHARGE FROM |
| | COMMON STAIRS. IT APPEARS THAT BOTH |
| | EMPTY INTO THE BUILDING. PLEASE EXPLAIN |
| | WHAT ALLOWS THIS TO OCCUR. |
| | |
| | 20) EMERGENCY INSTRUCTIONS FOR RESIDENTS |
| | OR GUESTS ARE REQUIRED. |
| | |
| | 21) KNOX BOXES WILL BE REQUIRED FOR THE |
| | COMMON ELEMENTS OF THE BUILDING. |
| | |
| | 22) PORTABLE FIRE EXTINGUISHERS WITH BE |
| | REQUIRED. |
| | |
| | 23) ARE THE GARAGE DOORS PROPERLY RATED? |
| | IT APPEARS THAT THE DOOR SCHEDULE |
| | DISPLAYS 45 MINUTES BUT THE GARAGE WALL |
| | IS OF GREATER VALUE. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLAN REVIEW (561) 805-6722 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |