| 2006-01-25 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHTS 1 THRU 7 (CIVIL) SHEETS, THE |
| | CERTIFICATE OF AUTHORIZATION IS REQUIRED |
| | ON THE TITLE BLOCK OF EACH SHEET. FAC |
| | 61G15-23.003 & FS 471.025. |
| | 2. SHT 1 OF 7 PROPOSED CLUBHOUSE SHOWS |
| | NO SANT. OR WATER SERVICE. PLEASE |
| | CLARIFY. SECTION 104.2.1. |
| | 3. SHT 1 & 2 OF 7 AN RPZV BACKFLOW IS |
| | REQUIRED ON THE WATER SERVICE OF EACH |
| | BUILDING. SECTION 608.13.2. |
| | 4. SHT SP-1, SP-2, A1 THRU A.28 |
| | ARCHITECTS BUSINESS NUMBER IS REQUIRED |
| | IN THE TITLE BLOCK OF EACH SHEET. FAC |
| | 61G1-16.004(2) & FS 481.219. |
| | 5. SHT A-7 SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS. SHOW |
| | THE SF OF EACH DRAINED AREA, WITH 1/2 |
| | AREA OF ALL VERTICAL WALLS INCLUDING |
| | PARAPETS, AND AREA OFF ROOFS THAT DRAIN |
| | ONTO THE ROOF AREAS FROM ABOVE IN |
| | CALCULATIONS. SHOW THE LOCATION OF ALL |
| | SECONDARY ROOF DRAINS/SCUPPERS. INDICATE |
| | THE SF OF STAIR ROOF, AND SHOW THE SIZE |
| | OF THE GUTTERS, SIZE OF DOWNSPOUTS, |
| | SLOPE OF GUTTERS AND INDICATE HIGH POINT |
| | OF GUTTERS. SECTIONS 1106 & 1107 AND ALL |
| | SUBSECTIONS. |
| | 6. SHT A.18 LAVS IN THE POWDER ROOMS OF |
| | THE TOWNHOUSES SHALL BE COVERED PER FHA |
| | DESIGN MANUAL PAGES 7, 7.33, & 7.35 |
| | EXCEPTION. LAV SHALL BE CENTERED ON THE |
| | 48" LENGTH OF THE PARALLEL CLEAR FLOOR |
| | SPACE, OR BE A FRONTAL APPROACH. PAGE |
| | 7.47. LAVS SHALL BE 34" TO RIM PER PAGE |
| | 7.52. (SEE DETAIL #2). |
| | 7. SHT A.18 FIRST DETAIL #3, SHOWER |
| | CLEAR FLOOR SPACE SHALL BE PARALLEL TO |
| | THE FIXTURE AND FLUSH WITH THE CONTROL |
| | WALL. PAGE 7.56. LAV PARALLEL CLEAR |
| | FLOOR SPACE SHALL BE CENTERED ON THE LAV |
| | A MINIMUM OF 2' OFF THE WALL. INDICATE |
| | MEASUREMENT FROM WALL TO CENTER OF LAV |
| | FOR ALL DETAILS. |
| | 8. SHT A.18 DETAIL #4, A 60" DIAMETER |
| | TURNING CIRCLE IS REQUIRED IN A "U" |
| | SHAPED KITCHEN THAT HAS A SINK, RANGE, |
| | OR COOKTOP AT ITS BASE. THIS IS IN |
| | ADDITION TO THE CLEAR FLOOR SPACE. PAGE |
| | 7.9. |
| | 9. SHT A.19 ALL BATHROOM DETAILS, SHOW |
| | HEIGHT OF LAVS. ALL W/C'S TO BE 18" OFF |
| | WALL TO CENTER OF FIXTURE & MEASUREMENTS |
| | FOR ALL W/C OPENINGS TO SHOWN ON PLANS. |
| | MINIMUM 33" REQUIRED. SEE PAGES 7.43, |
| | 7.44, 7.45, & 7.46. |
| | 10. ALL E,M & P SHEETS. ENGINEERS SHALL |
| | LEGIBLY INDICATE THEIR NAME AND LICENSE |
| | NUMBER ON EACH SHEET. FAC |
| | 61G15-23.002(2) & FAC 471.025. |
| | 11. SHTS P-3 & P-4 SHOWS 4" UP TO THE |
| | 3RD FLOOR FOR THE SANT. RISER. P-5 & P-6 |
| | SHOW 3" ON ALL. PLEASE CORRELATE SECTION |
| | 104.2.1. |
| | 12. SHT P-7 SHOW 3" RWLS ROOF DRAINS |
| | ISOMETRIC AS "3" RWL BELOW SLAB" PLEASE |
| | CLARIFY. SECTION 104.2.1. |
| | 13. SHT P-7 SHOW THE LOCATION OF ALL |
| | SECONDARY ROOF DRAINS/SCUPPERS. SHOW THE |
| | SIZE OF EACH DRAIN OR THE HEIGHT & WIDTH |
| | OF EACH SCUPPER, PIPING WITH SIZING, |
| | MEASUREMENT OFF THE ROOF TO THE FLOW |
| | LINE ETC. SECTIONS 104.2.1, 1106, & 1107 |
| | 14. SHT P-8 SANT. RISER DIAGRAM |
| | ISOMETRIC DOES NOT REFLECT THE FLOOR |
| | PLANS. THE RISER NUMBERS ARE OPPOSITE OF |
| | THE FLOOR PLANS. THE LAYOUTS OF SOME |
| | UNITS ON THE 1ST FLOOR DO NOT REFLECT |
| | THE FLOOR PLAN. THE SECOND FLOOR RISER |
| | DOES NOT REFLECT THE FLOOR PLAN AS THEY |
| | ARE OPPOSITE OF THE FLOOR PLAN ON MOST |
| | RISERS, AND SOME RISERS ARE MISSING |
| | FIXTURES & RISERS. 3RD FLOOR RISERS ARE |
| | OPPOSITE OF FLOOR PLAN. CORRELATE THE |
| | RISER DIAGRAMS WITH THE FLOOR PLANS, |
| | CHECK ALL PIPE SIZES WITH FLOOR PLANS. |
| | INDICATE DFUS AS THEY ACCUMULATE IN THE |
| | SYSTEM.SECTION 104.2.1 AND TABLE |
| | 710.1(1). |
| | 15. SHTS P-9 & P-10 WATER RISER DIAGRAM |
| | ISOMETRIC DOES NOT REFLECT THE FLOOR |
| | PLAN. RISER SHOWS 1" COLD WATER SERVICE |
| | UP TO PENTHOUSE LEVEL, BUT FLOOR PLAN |
| | SHOWS 1-1/2" COLD WATER SERVICE UP TO |
| | PENTHOUSE LEVEL ON SHTS P-1 THRU P-4. |
| | PLEASE CORRELATE FLOOR PLANS AND RISER |
| | DIAGRAMS. |
| | 16. SHTS P-9 & P-10 WATER RISER DIAGRAM |
| | ISOMETRICS, AIR CHAMBERS ARE NOT |
| | APPROVED. AND WATER HAMMER ARRESTORS |
| | REQUIRED BY SECTION 604.9, (W/M, ICE |
| | MAKER, DISHWASHER), SHALL BE LOCATED |
| | NEAR THE FIXTURES IN AN "EFFECTIVE |
| | RANGE" NOT IN THE CEILING AS SHOWN. |
| | PDI-WH 201 AND MANUF. INSTALLATION |
| | INSTRUCTIONS. |
| | 17. SHT P-9 SHOWN THE WATER HEATERS IN |
| | AN EMERGENCY PAN, WHERE AS P-10 SHOWS NO |
| | PAN. W/H'S ON THE FIRST FLOOR ARE DO NOT |
| | REQUIRE A HEATER PAN UNLESS THEY ARE ON |
| | A SHELF. PLEASE CLARIFY. SECTIONS |
| | 104.2.1. & 504.8. |
| | 18. SUBMIT A WATER HEATER DETAIL SHOWING |
| | ALL PIPE SIZES, VALVES, THERMAL |
| | EXPANSION CONTROL, P/T VALVE SHOWING |
| | PIPING AND INDICATING THE TERMINATION |
| | POINT. SECTIONS 104.2.1, 504.7.1, AND |
| | 607.3.2. |
| | 19. SHT P-11 PLUMBING GENERAL NOTES: |
| | E-22 AIR CHAMBERS ARE NOT APPROVED. |
| | DELETE FROM REFERENCE. SECTION 604.9. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |