Plan Review Notes
Plan Review Notes For Permit 05091695
Permit Number 05091695
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-12-07 00:00:001. COMPLETE CIVIL DRAWINGS ARE TO BE
 SUBMITTED ILLUSTRATING FIRE HYDRANTS
 AND WATER AND FIRE MAIN SIZES. ALL
 BACKFLOW PREVENTION DEVICES ARE TO BE
 SHOWN.
  
 2. FIRE HYDRANT SPACING IS NOT TO EXCEED
 300-500 FEET APART.
  
 3. WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING, AND AFTER CONSTRUCTION.
  
 4. SUITABLE ROADS ARE TO BE PROVIDED
 DURING CONSTRUCTION FOR FIRE AND
 PARAMEDICAL EQUIPMENT.
  
 5. BUILDING ADDRESSES ARE REQUIRED. A
 MINIMUM OF AT LEAST 6" HIGH NUMBERS ARE
 REQUIRED.
  
 6. ALL FIRE HYDRANTS ARE TO BE PROVIDED
 WITH PROPER CLEARANCES TO THE FRONT AND
 SIDES OF THEM.
  
 7. ALL HANDRAILS AND GUARDRAILS ARE TO
 MEET PRESCRIPTIVE STRENGTH REQUIREMENTS
 PER THE FLORIDA BUILDING CODE AND THE
 FLORIDA FIRE PREVENTION CODE.
  
 8. PLEASE EXPLAIN STORAGE AREAS NEAR
 EXIT STAIRS LOCATED ON THE SECOND FLOOR,
 CENTER CORE.
  
 9. A COMPLETE AUTOMATIC SUPERVISED FIRE
 SPRINKLER SYSTEM IS REQUIRED IN ALL
 THREE STORY BUILDINGS. COMPLETE PLANS
 AND PERMITS REQUIRED.
  
 10. THE FIRE ALARM SYSTEM IS TO BE
 MONITORED BY A LICENSED UL LISTED
 CENTRAL STATION APPROVED FOR CENTRAL
 STATION SERVICE. COMPLETE PLANS AND
 PERMITS REQUIRED PRIOR TO INSTALLATION.
  
 11.FIRE LINE BACKFLOW DEVICE SHALL BE
 EQUIPPED WITH TAMPER SWITCHES, CHAIN AND
 LOCKS.
  
 12. A REVIEW OF THE CIVIL DRAWINGS
 INDICATES THAT ADDITIONAL FIRE HYDRANTS
 ARE NEEDED. FIRE DEPARTMENT SPRINKLER
 CONNECTIONS SHALL BE LOCATED NO FARTHER
 THAN 150 FEET FROM A FIRE HYDRANT.
  
 13. THERE APPEARS TO BE NO FIRE HYDRANTS
 LOCATED ON THE APPROACH OR INTO THE
 COMPLEX.
  
 14. ALL SMOKE DETECTORS ARE TO BE
 INSTALLED A MINIMUM OF AT LEAST THREE
 FEET FROM AIR CONDITIONING DIFFUSERS.
  
 15. FIRE ALARM VISIBLE SIGNALS SHALL BE
 PROVIDED IN ROOMS DESIGNED FOR THE
 HEARING IMPAIRED.
  
 16. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS
 OF BUILDINGS.
  
 17. ALL RESIDENTIAL BUILDINGS ARE TO
 COMPLY WITH CHAPTER 30, NEW APARTMENT
 BUILDINGS OF NFPA 101, THE LIFE SAFETY
 CODE, 2003 EDITION.
  
 18. ALL COMMON BUILDING STAIRS ARE TO BE
 PROVIDED WITH EMERGENCY LIGHTING
 EQUIPMENT.
  
 19. PLEASE EXPLAIN EXIT DISCHARGE FROM
 COMMON STAIRS. IT APPEARS THAT BOTH
 EMPTY INTO THE BUILDING. PLEASE EXPLAIN
 WHAT ALLOWS THIS TO OCCUR.
  
 20. EMERGENCY INSTRUCTIONS FOR RESIDENTS
 OR GUESTS ARE REQUIRED.
  
 21. KNOX-BOXES WILL BE REQUIRED FOR THE
 COMMON ELEMENTS OF THE BUILDING.
  
 22. PORTABLE FIRE EXTINGUISHERS WILL BE
 REQUIRED.
  
 23. ARE THE GARAGE DOORS PROPERLY RATED.
 IT APPEARS THAT THE DOOR SCHEDULE
 DISPLAYS 45 MINUTES BUT THE GARAGE WALL
 IS OF GREATER VALUE.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709