| 2005-12-07 00:00:00 | 1. COMPLETE CIVIL DRAWINGS ARE TO BE |
| | SUBMITTED ILLUSTRATING FIRE HYDRANTS |
| | AND WATER AND FIRE MAIN SIZES. ALL |
| | BACKFLOW PREVENTION DEVICES ARE TO BE |
| | SHOWN. |
| | |
| | 2. FIRE HYDRANT SPACING IS NOT TO EXCEED |
| | 300-500 FEET APART. |
| | |
| | 3. WET FIRE HYDRANTS ARE REQUIRED PRIOR |
| | TO, DURING, AND AFTER CONSTRUCTION. |
| | |
| | 4. SUITABLE ROADS ARE TO BE PROVIDED |
| | DURING CONSTRUCTION FOR FIRE AND |
| | PARAMEDICAL EQUIPMENT. |
| | |
| | 5. BUILDING ADDRESSES ARE REQUIRED. A |
| | MINIMUM OF AT LEAST 6" HIGH NUMBERS ARE |
| | REQUIRED. |
| | |
| | 6. ALL FIRE HYDRANTS ARE TO BE PROVIDED |
| | WITH PROPER CLEARANCES TO THE FRONT AND |
| | SIDES OF THEM. |
| | |
| | 7. ALL HANDRAILS AND GUARDRAILS ARE TO |
| | MEET PRESCRIPTIVE STRENGTH REQUIREMENTS |
| | PER THE FLORIDA BUILDING CODE AND THE |
| | FLORIDA FIRE PREVENTION CODE. |
| | |
| | 8. PLEASE EXPLAIN STORAGE AREAS NEAR |
| | EXIT STAIRS LOCATED ON THE SECOND FLOOR, |
| | CENTER CORE. |
| | |
| | 9. A COMPLETE AUTOMATIC SUPERVISED FIRE |
| | SPRINKLER SYSTEM IS REQUIRED IN ALL |
| | THREE STORY BUILDINGS. COMPLETE PLANS |
| | AND PERMITS REQUIRED. |
| | |
| | 10. THE FIRE ALARM SYSTEM IS TO BE |
| | MONITORED BY A LICENSED UL LISTED |
| | CENTRAL STATION APPROVED FOR CENTRAL |
| | STATION SERVICE. COMPLETE PLANS AND |
| | PERMITS REQUIRED PRIOR TO INSTALLATION. |
| | |
| | 11.FIRE LINE BACKFLOW DEVICE SHALL BE |
| | EQUIPPED WITH TAMPER SWITCHES, CHAIN AND |
| | LOCKS. |
| | |
| | 12. A REVIEW OF THE CIVIL DRAWINGS |
| | INDICATES THAT ADDITIONAL FIRE HYDRANTS |
| | ARE NEEDED. FIRE DEPARTMENT SPRINKLER |
| | CONNECTIONS SHALL BE LOCATED NO FARTHER |
| | THAN 150 FEET FROM A FIRE HYDRANT. |
| | |
| | 13. THERE APPEARS TO BE NO FIRE HYDRANTS |
| | LOCATED ON THE APPROACH OR INTO THE |
| | COMPLEX. |
| | |
| | 14. ALL SMOKE DETECTORS ARE TO BE |
| | INSTALLED A MINIMUM OF AT LEAST THREE |
| | FEET FROM AIR CONDITIONING DIFFUSERS. |
| | |
| | 15. FIRE ALARM VISIBLE SIGNALS SHALL BE |
| | PROVIDED IN ROOMS DESIGNED FOR THE |
| | HEARING IMPAIRED. |
| | |
| | 16. PLEASE INDICATE INTERIOR FINISH |
| | CLASSIFICATIONS FOR WALLS AND CEILINGS |
| | OF BUILDINGS. |
| | |
| | 17. ALL RESIDENTIAL BUILDINGS ARE TO |
| | COMPLY WITH CHAPTER 30, NEW APARTMENT |
| | BUILDINGS OF NFPA 101, THE LIFE SAFETY |
| | CODE, 2003 EDITION. |
| | |
| | 18. ALL COMMON BUILDING STAIRS ARE TO BE |
| | PROVIDED WITH EMERGENCY LIGHTING |
| | EQUIPMENT. |
| | |
| | 19. PLEASE EXPLAIN EXIT DISCHARGE FROM |
| | COMMON STAIRS. IT APPEARS THAT BOTH |
| | EMPTY INTO THE BUILDING. PLEASE EXPLAIN |
| | WHAT ALLOWS THIS TO OCCUR. |
| | |
| | 20. EMERGENCY INSTRUCTIONS FOR RESIDENTS |
| | OR GUESTS ARE REQUIRED. |
| | |
| | 21. KNOX-BOXES WILL BE REQUIRED FOR THE |
| | COMMON ELEMENTS OF THE BUILDING. |
| | |
| | 22. PORTABLE FIRE EXTINGUISHERS WILL BE |
| | REQUIRED. |
| | |
| | 23. ARE THE GARAGE DOORS PROPERLY RATED. |
| | IT APPEARS THAT THE DOOR SCHEDULE |
| | DISPLAYS 45 MINUTES BUT THE GARAGE WALL |
| | IS OF GREATER VALUE. |
| | |
| | MIKE CARSILLO, CHIEF FIRE PREVENTION |
| | OFFICER |
| | 804-4709 |