| 2005-12-25 00:00:00 | ************ UNSAT ************* |
| | |
| | |
| | DIXIE MEWS / AQUA TERRACE |
| | |
| | 1)NOTE: PLEASE PROVIDE SIGNED, DATED AND |
| | SEALED PLANS BY ARCHITECT AND |
| | ENGINEER(S) OF RECORD. |
| | FS 481.221 AND 471.025 |
| | PLEASE SEE PLANS CONTAIN SOME SORT OF |
| | "CORPORATE SEAL' WHICH IS NOT |
| | ACCEPTABLE. |
| | PLEASE KNOW THIS IS REQUIRED OF ALL |
| | SHEETS AND FOR ALL TRADE REVIEWS WHETHER |
| | OR NOT COMMENT IS MADE BY OTHER |
| | REVIEWER(S). |
| | |
| | 2)NOTE: PLEASE COMPLETE AND INCLUDE ALL |
| | INFORMATION ON SAID TITLE BLOCKS FOR |
| | ARCHITECTUAL AND ENGINEERING FIRMS. |
| | PLEASE SEE FLORIDA ADMINISTRATIVE CODES |
| | 61G1-16.004 (ARCH) AND 61G15-23.002 |
| | (ENG). |
| | PLEASE KNOW THIS IS REQUIRED FOR ALL |
| | SHEETS AND FOR ALL TRADES. |
| | |
| | 3)NOTE: PLEASE SEE THERE IS REFERENCE TO |
| | BLDGS AS "TOWNHOUSES", PLEASE SEE THESE |
| | DO NOT APPEAR TO BE FEE SIMPLE? |
| | PLEASE SEE BUILDING AND ZONING COMMENTS |
| | AS THIS WOULD COMPLETELY CHANGE |
| | ELECTRICAL DESIGN IF INDEED FEE SIMPLE |
| | "TOWNHOUSES". |
| | |
| | 4)NOTE: PLEASE VERIFY CLEARENCES FOR |
| | ELECTRICAL SERVICE PER 110.26, |
| | APPEARS TO SHOW DOORS WHICH WILL SLIDE |
| | OPEN ON EACH SIDE, HOWEVER THIS WILL |
| | ALWAYS CREATE A COMMON POINT IN THE |
| | CENTER WHICH WOULD NOT MEET CODE. |
| | PLEASE PROVIDE AN ELEVATION AS HEIGHT |
| | AND WIDTH IS TO BE VERIFIED. |
| | PLEASE ALSO VERIFY IT APPEARS THIS |
| | ROOM/AREA IS ALSO THE GRESS FROM COMMON |
| | STAIR TOWER AND LOBBY AREA? |
| | PLEASE SEE BLDG REVIEW COMMENTS FOR FIRE |
| | SEPARATION AS STAIRS EXIT INTO THIS AREA |
| | AND NO DOORS ARE SHOWN WHICH MAY ALLOW |
| | EXITING BACK INTO COMMON LOBBY AREA |
| | PLEASE SEE THIS IS SHOWING SWITCHING FOR |
| | LTS? |
| | PLEASE ALSO SEE NEXT COMMENT WITH |
| | RESPECT TO THE CIRCUIT SHOWN. |
| | |
| | 5)NOTE: PLEASE SEE HOUSE CIRCUIT SHOWN |
| | FOR ELEVATOR MACHINE ROOM IS ALSO SHOWN |
| | FEEDING OTHER AREAS. PLEASE SEE 620.23 |
| | WHICH REQUIRES THE BRANCH CIRCUIT FOR |
| | LTS AND RECEPTS TO BE DEDICATED. |
| | PLEASE ADJUST. |
| | |
| | 6)NOTE: PLEASE PROVIDE PHOTOMETRICS FOR |
| | COMMON AREAS FOR EGRESS LIGHTING. PLEASE |
| | SEE THIS WOULD INCLUDE LOBBY AREAS, |
| | STAIR TOWERS, SHOW ALL FT CANDLES TO THE |
| | EXIT/PUBLIC RIGHT OF WAY. |
| | PLEASE SEE 2003 NFPA-101 7.8 AND 7.9 |
| | WHICH REQUIRES 10 FT CANDLES UNDER |
| | NORMAL POWERE AND A MIN OF 1FT CANDLE |
| | UNDER EM POWER. |
| | PLEASE ALSO SEE FURTHER COMMENTS WIHT |
| | RESPECT TO FIXTURES. |
| | |
| | 7)NOTE: PLEASE PROVIDE A FIXTURE |
| | SCHEDULE FOR ALL FIXTURES. PLEASE SEE |
| | COMPLIANCE FOR STAIR TOWERS, CLOSETS ETC |
| | NEED TO BE VERIFIED. |
| | 215.5 |
| | |
| | 8)NOTE: PLEASE COMPLETE A/C CU LAYOUT ON |
| | ROOFTOP PLANS FOR ALL UNITS. 8 SHOWN |
| | WHICH SHOULD SHOW A TOTAL OF 16 UNITS TO |
| | CORRELATE WITH PANEL SCHEDULES AND |
| | UNITS. |
| | PLEASE ALSO CLARIFY CU DETAIL WHICH IS |
| | SHOWING THEDISCONNECTS BEING MOUNTED |
| | TO THE CU? |
| | PLEASE VERIFY OCP SHOWN AT 40A'S?(TYP) |
| | PLEASE SEE M-SHEETS WHICH SHOW MORE THAN |
| | ONE TYPE OF UNIT. 15A'S, 30A'S ETC. |
| | PLEASE ADJUST DISCONNECT DETAIL AS |
| | NEEDED. |
| | PLEASE SEE IF CHANGING OUT UNIT, UNIT |
| | WOULD STILL HAVE POWER COMING TO UNIT. |
| | |
| | 9)NOTE: PLEASE SHOW THE CONDUCTORS FROM |
| | HOUSE GUTTER TO EACH DISCONNECT. |
| | 215.5 |
| | |
| | 10)NOTE: PLEASE VERIFY WITH THE FIRE |
| | MARSHAL'S OFFICE IF INDEED THE UNIT SD'S |
| | WILL BE TIED INTO BASE BLDG PROTECTION |
| | SYSTEM. |
| | PLEASE KNOW, IF THESE ARE 120V WIRED |
| | INLINE IN UNITS, THEN CIRCUITING WILL BE |
| | REQUIRED ALONG WITH ARC FAULT |
| | PROTECTION. |
| | 215.5,210.12 |
| | THIS WOULD ALSO BE AFFECTED BY THE |
| | "TOWNHOUSE" DECLARATION. |
| | |
| | 11)NOTE: PLEASE PROVIDE ALL AREA AND |
| | ROOM DESIGNATIONS ON PLANS FOR UNITS. |
| | NEED TO VERIFY CIRCUITING. |
| | 215.5 |
| | |
| | 12)NOTE: PLEASE INCLUDE ELECTRICAL |
| | CONNECTION FOR JACUZZI, WILL THIS BE A |
| | HARDWIRED UNIT WITH A DISCONNECTING |
| | MEANS OR A RECEPT? |
| | PANEL SCHEDULE SHOWS THE GFI PROTECTION. |
| | PLEASE ALSO SEE ONLY THE CIRCUIT IS |
| | SHOWN ON PLANS. |
| | PLEASE SHOW THE ACCESS, PLEASE SEE SOME |
| | CIRCUIT #'S SHOWN APPEAR TO BE LOCATED |
| | AT THE REAR OF THE UNIT. IS THERE A |
| | CLOSET ACCESS.? |
| | |
| | 13)NOTE: PLEASE VERIFY IN SOME UNITS A |
| | RECEPT IS BEING SHOWN IN CLOSET? CIRCUIT |
| | #1. |
| | PLEASE KNOW, IF THIS IS FOR A PLUG IN |
| | TYOE TRANSFORMER, THE LOCATION OF THE |
| | RECEPT WOULD ONLY BE PERMITTED DIRECTLY |
| | ABOVE THE DOOR OR RECEPT FOR ANY |
| | TRANSFORMER WOULD BE REQUIRED TO BE |
| | MOVED. |
| | PLEASE KNOW, THE PLUG IN TYPE |
| | TRANSFORMERS, MANY CONTAING OCP ETC |
| | BECOME EXTREMELY HOT AND HAVE MELTED IN |
| | THIS AND OTHER JURISTICTIONS CAUSING |
| | MANY FIRES. |
| | THE COMBUSTIBLES IN CLOSET AREA WOULD |
| | ONLY ACT AS AN ACCELERANT. |
| | |
| | 14)NOTE: PLEASE SEE OTHER CLOSETS, |
| | MOSTLY IN UPPER UNITS ARE SHOWING LTS |
| | WHICH DO NOT MEET MIN CLEARENCE |
| | REQUIREMENTS PER 410.8. PLEASE ALSO SEE |
| | PREVIOUS COMMENT WITH RESPECT TO THE |
| | FIXTURE SCHEDULE TO BE PROVIDED FOR |
| | REVIEW. |
| | |
| | 15)NOTE: PLEASE SEE SOME UNITS APPEAR TO |
| | SHOW SOME SORT OF CEILING LINE , AS IF |
| | THE HALL AREA CEILING MAY BE LOWER THAN |
| | ACTUAL BEDRM CEILING HEIGHTS? |
| | PLEASE SEE NFPA-72 11.8.3.5 WHICH |
| | REQUIRES ALL SD'S TO BE LOCATED AT THE |
| | HIGHEST POINT POSSIBLE ON A FLAT |
| | CEILING. |
| | IF WALL MOUNTED, THEN THIS WOULD REQUIRE |
| | THESE TO BE LOCATED WITHIN 12" OF |
| | CEILING BUT NOT CLOSER THAN 4" IF INDEED |
| | THE CEILINGS IN BEDRMS ARE HIGHER, |
| | PLEASE MOVE SD'S TO BE LOCATED TO MEET |
| | CODE. |
| | |
| | 16)NOTE: PLEASE SEE A "NOTE" ON E-4 |
| | WHICH MENTIONS A "CONTINUOUS ROW OF |
| | FLOUR LTS" ETC TO BE MOUNTED IN COVE? |
| | PLEASE KNOW, THESE COULD NOT BE LOCATED |
| | ON 2ND FLR OF UNITS AS NOTED. |
| | ONLY LOCATED ON E-3 2ND FLR COMMON AREA. |
| | |
| | 17)NOTE: PLEASE SEE 210.52 FOR RECEPTS |
| | MISSING FOR 2' OR MORE OF WALL SPACE. |
| | PLEASE SEE MOST IF THESE LOCATIONS ARE |
| | REDLINED ON PLANS. (SEE MOSTLY 3RD FLR. |
| | |
| | 18)NOTE: PLEASE CLARIFYLOCATIONS OF |
| | WASHER/DRYERS ON 3RD FLR UNITS. PLANS |
| | SHOW THE LOCATION OF RECEPT FOR DRYERS, |
| | HOWEVER WITH THE LAYOUT AS SHOWN, THE |
| | DRYER WOULD NOT FIT IN THESE LOCATIONS?? |
| | |
| | 19)NOTE: PLEASE SEE 3RD FLR UNITS WHICH |
| | SHOW LIGHTING BEING CIRCUITED TO THE |
| | DINING RM / SMALL APPLIANCE CIRCUIT. |
| | PLEASE SEE 210.52B1 WHICH ONLY PERMITS |
| | THE RECEPTS WITH SOME EXCEPTIONS, |
| | HOWEVER LTS AS SHOWN MAY NOT BE ON THIS |
| | CIRCUIT. PLEASE ADJUST. |
| | |
| | 20)NOTE: PLEASE SEE TOP FLR UNIT, WHICH |
| | DOES NOT SEEM TO SHOW A FIXTURE AT THE |
| | END OF THE SW LEG IN WHAT APPEARS TO BE |
| | A BEDRM. |
| | (MISPRINT). |
| | |
| | 21)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | PLEASE SEE IT IS NOTED FORALL BUT |
| | HOUSE MAIN DISCONNECT. |
| | |
| | 22)NOTE: PLEASE VERIFY THE CONNECTION |
| | POINT AS NOTED FOR GROUNDING ELECTRODE |
| | CONDUCTOR TO THE REBAR/FOOTER STEEL. |
| | IT IS UNCLEAR WHAT "THREE SETS OF WRAP |
| | TO BOND"? THIS METHOD IS UNCLEAR AND NOT |
| | KNOWN. |
| | PLEASE PROVIDE THE PERMITTED CONNECTION |
| | AS SET-FORTH IN THE NEC. 250.50 OR |
| | PROVIDE FUTHER DETAIL FOR THIS. |
| | ABOVE IS NOTED AS ALL CONNECTIONS BEING |
| | EXOTHERMIC, IS THIS FOR THIS LOCAITON |
| | ALSO? |
| | |
| | 23)NOTE: PLEASE SEE PANEL "P" WHICH |
| | SHOWS THE LOAD FOR GEN LT AND RECEPTS, |
| | HOWEVER THERE SEEMS TO BE SOME SORT OF |
| | NUMERICAL NOTE ADDED TO THE CIRCUITS 2 |
| | AND 4? |
| | MISPRINT? CLARIFY. |
| | |
| | 24)NOTE: PLEASE SEE "CLUBHOUSE" PERMIT |
| | #05091714 FOR REVIEW. |
| | |
| | 25)NOTE: PLEASE PLACE NOTE ON PLANS FOR |
| | ALL SD'S TO BE INSTALLED PER 2002 |
| | NFPA-72 11.8.3.5 |
| | |
| | 26)NOTE: PLEASE MAKE NOTE FOR ALL MIN |
| | FAIR HOUSING ACT REQUIREMENTS FOR DEVICE |
| | HEIGHTS. |
| | 24 CFR 100.205 |
| | |
| | ** PLEASE SEE ONE SET OF PLANS HAS MUCH |
| | OF THE ABOVE REDLINED FOR AREAS OF |
| | COMMENTS. THIS MAY HELP IN AREAS AS |
| | NOTED. (RECEPTS ETC) |
| | |
| | ** PLEASE KNOW, A RESPONSE LETTER WITH |
| | RESPECT TO COMMENTS AND WHAT ACTIONS |
| | WERE TAKEN WOULD GREATLY HELP IN |
| | EXPEDITING THE PLAN REVIEW PROCESS. |
| | PLEASE KEEP IN MIND TO CLOUD/TRIANGLE |
| | ANY REVISED LOCATIONS ON PLANS. |
| | |
| | ** PLEASE SEE COMMENTS FROM OTHER TRADES |
| | WHICH MAY HAVE AN AFFECT ON ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2005-12-24 00:00:00 | IN ELEC FOR REVIEW, |
| | REVIEW IN PROGRESS. |
| | PLANS WILL GO INTO "F" STATUS AND REVIEW |
| | NOTES WILL FOLLOW. |
| | REVIEW IN PROGRESS |