| 2007-11-16 09:16:46 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 BUILDING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | FROM PREVIOUS REVIEW. THE COMMENT NUMBER |
| | SHALL STAY THE SAME AS THE FIRST REVIEW: |
| | |
| | ******FROM PREVIOUS REVIEWS: 3RD REVIEW****** |
| | |
| | A. OK |
| | B. OK |
| | 1. OK |
| | 2. OK |
| | |
| | 3. SHT AP/A5.12 SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS PER |
| | SECTIONS 1106 & 1107 AND ALL |
| | SUBSECTIONS. SHOW SF DRAINED FOR EACH |
| | AREA ALONG WITH 1/2 AREA OF ALL VERTICAL |
| | WALLS, INCLUDING PARAPETS, AND THE AREA |
| | OF ANY ROOFS THAT DRAIN ONTO THE ROOF |
| | AREAS FROM ABOVE. - SHOW THE LOCATION OF |
| | ALL SECONDARY ROOF DRAINS OR SCUPPERS. |
| | IF SCUPPERS ARE USED, SUBMIT A DETAIL |
| | SHOWING HEIGHT, WIDTH, AND DISTANCE TO |
| | FLOW LINE OFF THE ROOF. SECTION 1503.4.2 ****RESPONSE |
| | NOTED, BUT SHEETS A5.05, |
| | A5.13, A5.25 WERE NOT SUBMITTED, AND NO CALCULATIONS |
| | WITH INFORMATION REQUESTED |
| | HAS BEEN LOCATED. |
| | ******RESONSE NOTED, BUT THE SECONDARY ROOF DRAINAGE |
| | HAS NOT BEEN PROPERLY ADDRESSED. WHEN THE DOWNSPOUT HAS |
| | A BLOCKAGE, AND WHILE IT IS TRUE THAT THE STORM WATER |
| | CAN DRAIN OVER THE TOP OF THE COLLECTOR HEAD, THE |
| | CONCERN IS THAT WHEN THE SCUPPER OPENING IS BLOCKED |
| | THEN NEITHER THE PRIMARY NOR THE SECONDARY ROOF DRAIN |
| | WILL BE ABLE TO WORK. SECTION 1107.2 SEPARATE SYSTEMS |
| | ARE REQUIRED AND THE OVERFLOW SCUPPER SHALL BE SIZED |
| | PER SECTION 1107.3. |
| | |
| | 4. SHTS AP/A5.61 & AP/A5.62 INDICATE |
| | SPECIFICATION "A" OR "B" FOR EACH UNIT |
| | OR BATHROOM AS REQUIRED IN FHA DESIGN |
| | MANUAL PAGES 7.34 & 7.35. - LAVS SHALL |
| | BE A MINIMUM OF 2' OFF THE WALL IN ORDER |
| | TO BE CENTERED ON THE 48" LENGTH OF THE |
| | CLEAR FLOOR SPACE. PLEASE INDICATE ON |
| | PLANS. FHA DESIGN MANUAL PAGES 7.47 AND |
| | 7.48. - WATER CLOSET OPENING SHALL BE A |
| | MINIMUM OF 33" WITH THE WATER CLOSET 18" |
| | OFF ONE FIXTURE AND 15" OFF THE OTHER |
| | FIXTURE TO THE CENTER OF THE W/C. FHA |
| | DESIGN MANUAL PAGES 7.43, 7.44, & 7.45. ****RESPONSE |
| | NOTED, BUT SPECIFICATION |
| | "A" OR "B" HAS NOT BEEN INDICATED. ALSO |
| | THE WATER CLOSET OPENING MEASUREMENTS |
| | HAS NOT BEEN SHOWN ON THE FLOOR PLAN. ******RESPONSE |
| | NOTED, BUT SPECIFICATION "A" OR "B" HAS NOT BEEN |
| | INDICATED. |
| | |
| | 5. OK |
| | 6. OK |
| | 7. OK |
| | 8. OK N/A |
| | 9. OK |
| | 10. OK |
| | 11. OK |
| | 12. OK |
| | 13. OK |
| | |
| | 14. AN RPZV BACKFLOW IS REQUIRED ON THE |
| | WATER SERVICE TO THE BUILDING. SECTION |
| | 608.13.2. |
| | ****RESPONSE NOTED, BUT COMMENT NOT |
| | ADDRESSED. EACH BUILDING IS REQUIRED TO |
| | HAVE ITS OWN RPZV BACKFLOW. INDICATE ON |
| | PLANS AT THE WATER SERVICE TO THE |
| | BUILDING. |
| | ******RESPONSE NOTED, BUT THERPZV BACKFLOW FOR THIS |
| | BUILDING IS NOT INDICATED ON SHEET 10 OF THE CIVIL |
| | PLANS. |
| | |
| | 15. SUBMIT A WATER LAYOUT FOR BUILDING |
| | AND WATER RISER DIAGRAMS. SHOW ALL PIPE |
| | SIZES, VALVES, WATER HAMMER ARRESTORS, |
| | (INSTALLED IN AN "EFFECTIVE RANGE" NOT |
| | IN THE CEILING). SECTIONS 104.3.1.1, |
| | 606.1, 606.2, 608.13.2 & PDI-WH 201. |
| | ****RESPONSE NOTED, BUT THE WATER RISER |
| | DIAGRAM SHALL BE SUBMITTED IN ISOMETRIC |
| | FORM. WATER HAMMER ARRESTORS AND |
| | REQUIRED VALVES CAN NOT BE SHOWN ON A |
| | FLAT PIPING LAYOUT. |
| | ******RESPONSE NOTED, BUT THIS IS UNIT ISOMETRIC RISER |
| | DIAGRAMS ONLY. PLEASE SUBMIT THE WATER MAIN PIPING FROM |
| | THE ENTRANCE OF THE BUILDING, ALL HORIZONTAL MAINS, ALL |
| | RISERS THRU THE 5TH FLOOR. (ALL PIPING OTHER THAT UNIT |
| | RISER DIAGRAMS IN ISOMETRIC RISER DIAGRAM FORM). |
| | |
| | 16. SUBMIT A BUILDING SANITARY DRAIN |
| | ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE |
| | SIZES, TRAPS, OFFSETS, RISER LOCATIONS |
| | WITH RISER NUMBERS, DFU'S AS THEY |
| | ACCUMULATE IN THE SYSTEM ETC. SECTION |
| | 104.3.1.1. |
| | ***COMMENT RESPONSE NOTED, BUT COMMENT |
| | NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT THE RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN WHERE THE LAST TWO BRANCH LINES |
| | CONNECT TO THE BUILDING DRAIN, AT THE FLOOR DRAIN, AND |
| | THE RISER PRIOR TO THE FLOOR DRAIN. ALSO THE FLOOR |
| | DRAIN IS NOT VENTED AS PIPED ON THE FLOOR PLAN.-- |
| | SHOW CLEANOUTS REQUIRED BY SECTION 708.3.3 ON THE RISER |
| | DIAGRAM AND THE FLOOR PLAN.--NO RISER DESIGNATION |
| | NUMBERS WERE GIVEN FOR THE RISERS. THIS IS REQUIRED TO |
| | TRACK THE RISERS FROM THE BUILDING DRAIN THRU THE 5TH |
| | FLOOR. |
| | |
| | 17. SUBMIT A BUILDING STORM DRAIN |
| | ISOMETRIC RISER DIAGRAM, SHOWING ALL |
| | PIPE SIZES, RISER LOCATIONS WITH RISER |
| | NUMBERS, AND SQUARE FEET AS IT |
| | ACCUMULATES IN THE SYSTEM. SECTION |
| | 104.3.1.1. |
| | ****RESPONSE NOTED, BUT NOT ADDRESSED. ******RESPONSE |
| | NOTED, BUT THE STORM ISOMETRIC RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN. SOME PIPE SIZES ARE DIFFERENT, |
| | CLEANOUTS, ETC.--P-TRAPS ARE NOT REQUIRED IN THE |
| | STORM PIPING SYSTEM.--SHOW ALL CLEANOUTS REQUIRED |
| | BY SECTION 1101.8. |
| | |
| | 18. OK |
| | |
| | **************NEW COMMENTS************** |
| | |
| | 1B. ALL ARCHITECTURAL SHEETS. THE TITLE |
| | BLOCK SHALL CONTAIN THE PRINTED NAME OF |
| | THE PERSON SEALING THE DOCUMENT. FAC 61G1-16.004(6) & |
| | FS F81.2055. |
| | ******RESPONSE NOTED, BUT SHT GN/A1.04 IS STILL MISSING |
| | THE PRINTED NAME. |
| | |
| | 2B. SHT AP P14.04 PIPING FOR THE |
| | FIXTURES ON THE SECOND THRU 4TH FLOORS |
| | SHALL BE SHOWN ON THE FLOOR PLAN WITH |
| | THE FIXTURES, (SHT P14.05). SECTION |
| | 104.2.1.3. |
| | ******RESPONSE NOTED, BUT MANY RISER NUMBERS ARE NOT |
| | SHOWN AS WELL AS THE PIPING IN ABOUT 6 OR 7 UNITS IS |
| | NOT SHOWN. |
| | |
| | 3B. OK |
| | |
| | 4B. SUBMIT A DETAIL FOR THE DOWNSPOUTS |
| | AND THE COLLECTOR HEAD AT THE TOP. |
| | INDICATE SIZE OF DOWNSPOUT, LENGTH, |
| | WIDTH & HEIGHT OF COLLECTOR HEAD. |
| | INDICATE ON ROOF PLAN SQUARE FOOTAGE |
| | DRAINING INTO EACH DOWNSPOUT. |
| | ******RESPONSE NOTED, BUT THE DETAIL DOES NOT SHOW |
| | LENGHT, WIDTH OR HEIGHT. SUBMIT AN ELEVATION DETAIL |
| | SHOWING THESE MEASUREMENTS AS WELL AS A CUT SECTION. |
| | SECTION 1106.3. |
| | |
| | 5B. SECONDARY DRAINAGE AND SEPARATE |
| | SYSTEMS ARE REQUIRED FOR THE ROOF |
| | DRAINAGE PER SECTIONS 1107.1 & 1107.2. |
| | PLEASE INDICATE THE LOCATION AND SIZE OF |
| | THE SECONDARY ROOF DRAINAGE. SUBMIT A |
| | DETAIL FOR THE SECONDARY ROOF DRAINS. ******RESPONSE |
| | NOTED, BUT THE INTENT OF THE CODE SECTION HAS NOT BEEN |
| | ADDRESSED. WHEN THE DOWNSPOUT HAS A BLOCKAGE, AND WHILE |
| | IT IS TRUE THAT THE STORM WATER CAN DRAIN OVER THE TOP |
| | OF THE COLLECTOR HEAD, THE CONCERN IS THAT WHEN THE |
| | SCUPPER OPENING IS BLOCKED THEN NEITHER THE PRIMARY NOR |
| | THE SECONDARY ROOF DRAIN WILL BE ABLE TO WORK. SECTION |
| | 1107.2 SEPARATE SYSTEMS ARE REQUIRED AND THE OVERFLOW |
| | SCUPPER SHALL BE SIZED PER SECTION 1107.3. SHOW THE |
| | LOCATION OF THE EMERGENCY OVERFLOW SCUPPERS. |
| | |
| | 6B. OK |
| | |
| | ********NEW COMMENTS 3RD REVIEW******** |
| | |
| | 1C. THE STRUCTURAL SHEETS ONE SET HAVE NOT BEEN SIGNED, |
| | SEALED & DATED. FAC 61G15-23.002(1) & FS 471.025. |
| | |
| | 2C. SOME ARCHITECTURAL SHEETS IN ONE SET HAVE NOT BEEN |
| | SIGNED, SEALED & DATED. FAC 61G1-16.003, FAC |
| | 61G1-16.004(5) & FS 481.2055. |
| | |
| | 3C. SHT AP/P14.01 AND OTHER PLUMBING SHEETS REVISION 1 |
| | HAS BEEN DELETED FROM THE TITLE BLOCK REVISION INDEX. |
| | PLEASE SHOW THE COMPLETE HISTORY OF REVISIONS ON THE |
| | REVISION INDEX FOR ACCURATE RECORD KEEPING. SECTION |
| | 104.2.1.3. |
| | |
| | 4C. SHT AP/P14.03 THE FLOOR DRAIN IN THE PUMP ROOM CAN |
| | NOT DRAIN TO STORM. ARTICLE III SECTION 90-203 CITY WPB |
| | MUNICIPAL CODE. CONNECT ALL FLOOR DRAINS TO THE |
| | SANITARY SYSTEM. |
| | |
| | 5C. SHT AP/P14.08 STORM ISOMETRIC RISER DIAGRAM DOES |
| | NOT REFLECT THE FLOOR PLAN. SOME PIPE SIZES ARE |
| | DIFFERENT, CLEANOUTS, ETC.--P-TRAPS ARE NOT |
| | REQUIRED IN THE STORM PIPING SYSTEM.--SHOW ALL |
| | CLEANOUTS REQUIRED BY SECTION 1101.8. |
| | |
| | 6C. SHT AP/P14.10 WATER HEATER DETAIL. A FULL OPEN |
| | VALVE IS REQUIRED ON THE SUPPLY LINE TO THE WATER |
| | HEATER. SECTION 606.1(7). PLEASE SHOW ON DETAIL.-- |
| | SANITARY RISER #7 HAS 24 DFU'S, NOT 20 AS INDICATED. |
| | TABLE 709.1. PLEASE CORRECT DFU'S. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |