2007-10-30 15:27:09REVIEW #: 3
 ACTION: DENIED
  
 FBC 2001 CODES W/ 2003 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. OK
  
 2. RETURN AIR TRANSFERS AND JUMPERS ARE STILL NOT
 DESIGNED TO MEET THE EXCEPTIONS AS LISTED UNDER FBC,M
 601.4. EXAMPLE: UNIT B2 SHOWS AN 8 INCH ROUND (50
 SQ.IN) R/A JUMPER FOR 7 INCH (38.5 SQ.IN) AND 4 INCH
 (13 SQ.IN) ROUND SUPPLY DROPS IN MASTER BEDROOM. THE
 R/A JUMPER MUST BE 1.5 TIMES THE SIZE OF THE SUPPLY
 DROPS IN THE MASTER TO MEET EXCEPTION 1 UNDER FBC,M
 601.4. THE 7IN PLUST THE 4IN DUCTS TOTAL 51.5 SQ. IN.
 THE TRANSFER IS SMALLER THAN THE TWO SUPPLY DUCTS
 RATHER THAN 1.5 TIMES LARGER. THE EXCEPTION HAS NOT
 BEEN MET. IF THE DESIGNER CHOOSES NOT TO DESIGN TO MEET
 THE EXCEPTIONS, A FIELD TEST WILL BE REQUIRED AT FINAL
 INSPECTION TO DEMONSTRATE A MAX. PRESSURE DIFFERENTIAL
 OF 0.01IN. W.C. ACROSS THE CLOSED BEDROOM DOORS AS
 REQUIRED BY FBC,M 601.4.
  
 3. OK
  
 4. OK
  
 5. M15.06: CONDENSATE TRAP DETAIL FOR NON-DUCTED RETURN
 UNITS, THE SECONDARY DRAIN LINE FROM THE AUXILIARY
 DRAIN PAN SHALL NOT BE CONNECTED TO THE PRIMARY
 CONDENSATE RISER. A SEPARATE DRAIN LINE SHALL EXTEND
 FROM THE PAN TO A CONSPICUOUS POINT AND SERVE AS AN
 ALARM WHICH INDICATES THAT THE PRIMARY DRAIN IS
 RESTRICTED.AS AN ALTERNATIVE TO A SEPARATE DRAIN
 LINE, AN APPROVED WATER LEVEL DETECTOR OR FLOAT SWITCH
 DEVICE SHALL BE USED TO CONTROL OVERFLOW BY
 AUTOMATICALLY SHUTTING DOWN THE EQUIPMENT OR APPLIANCE
 THAT PRODUCES THE CONDENSATE. THE FLOAT SWITCH ON THE
 SECONDARY DRAIN OUTLET AT THE AHU MAY BE INSTALLED
 (ALTHOUGH IT'S NOT NECESSARY) BUT IT CAN NOT REPLACE
 THE SEPARATE SECONDARY DRAIN LINE OR THE FLOAT SWITCH
 REQUIRED ON THE AUXILIARY DRAIN PAN. THE FLOAT SWITCH
 ON THE SECONDARY DRAIN OUTLET AT THE AHU IS ACCEPTABLE
 AS OVERFLOW PROTECTION ONLY ON THE DUCTED RETURN UNITS
 WHERE AN AUXILIARY DRAIN PAN CAN NOT BE INSTALLED UNDER
 THE AHU. FBC,M 307.2.3 AND 307.2.4
  
 6 THROUGH 10: OK
  