2007-11-07 15:04:55***PROVISO***
  
 COMMENTS HAVE BEEN ADDRESSED FROM THE PREVIOUS REVIEW.
 PLEASE SEE ADDITIONAL COMMENTS:
  
 1) DESIGN CRITERIA REFERS TO NFPA 13 AND SHEET FP 13.02
 REFERS TO NFPA 13R IN SHEET NOTES. PLEASE CORRELATE OR
 EXPLAIN.
  
 2) PLEASE SEE CORRECTION FROM PREVIOUS REVIEW COMMENTS.
 MULTI-FAMILY RESIDENTIAL BUILDINGS TO COMPLY WITH
 COMMERCIAL REQUIREMENTS FOR ADDRESSING. MINIMUM OF 6"
 IN HEIGHT AND 1" IN WIDTH. SEPARATE UNIT CHARACTERS TO
 COMPLY WITH 3" REQUIREMENT.
  
 3) PLANS DON'T SEEM TO ILLUSTRATE ANY POST INDICATING
 VALVE DETAIL. A NOTE DOES REFERENCE PIV TAMPER SWITCHES
 ON SHEET FP 13.10. WHAT MEANS WILL BE PROVIDED WHERE
 THE STATUS OF (1) BUILDING WON'T IMPACT OTHER
 BUILDINGS? PLEASE PROVIDE DETAIL AND ILLUSTRATE ON FP
 SITE PLAN.
  
 4) PLEASE INDICATE IF ANY ELEVATORS WILL MEET
 REQUIREMENTS FOR STRETCHER ACCESSIBILITY.
  
  
 PLANS WILL BE STAMPED WHEN RETURNED AND ADDRESSED FOR
 FIRE COMMENTS IN ADDITION TO OTHER REVIEW NOTES.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW