Plan Review Notes
Plan Review Notes For Permit 05091687
Permit Number 05091687
Review Stop E
Sequence Number 3
Notes
Date Text
2007-09-20 08:19:00 
 ** DENIED 3RD REVIEW**
  
 ** PLEASE SEE THERE ARE SOME ITEMS FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING. PLEASE ALSO SEE
 THERE ARE SOME NEW COMMENTS BASED ON REVISED
 PLANS/PLANS AND DOCUMENTS NOW SUBMITTED.
 ** SOME ITEMS COULD HAVE BEEN REDLINED/PROVISO, HOWEVER
 MANY OF THESE ARE IN NEED OF ADDRESSING AT THIS TIME.
  
 1) NOTE:PLEASE SEE THE PLANS DO NOT INDICATE FIXTURE
 DESIGNATIONS FOR ALL LIGHTING. PLEASE SEE THERE ARE
 SEVERAL AREAS INCLUDING FIRST FLOOR AND OTHER FLOORS
 WHERE FIXTURES ARE STILL MISSING DESIGNATIONS. PLEASE
 SEE THE FIXTURE LEGEND COULD NOT BE COORDINATED WITH
 THESE AT THIS TIME.
 PLEASE SEE COMMON AREAS WHICH THE LEGEND ON ELECTRICAL
 PLANS COULD NOT BE FOUND.
 PLEASE SEE THE INFORMATION ON THE INPUT DATA REPORT FOR
 EXTERIOR LIGHTING ALSO NEEDS TO CORRELATE WITH PLANS.
 THE LIGHTING, TYPES, NUMBER OF FIXTURES, ETC IS NOT
 STATED ON THE IDR AS ON PLANS.
 PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED AS THE
 INPUT DATA REPORT DOES NOT CORRELATE WITH ALL
 ELECTRICAL LIGHTING FOR INTERIOR LIGHTING WHICH IS ON
 PLANS. PLEASE SEE MISSING A SUBSTANTIAL AMOUNT OF
 LIGHTING ON THE INPUT DATA REPORT.
 13-415.0, 415.1.ABCD, 415.1.A, 415.2
  
 2) NOTE: PLEASE SEE ONLY ONE COPY OF THE ENERGY
 CALCULATIONS (1.22 VERSION) SUBMITTED ACTUALLY CONTAINS
 AN ORIGINAL SIGNATURE AND DATE. PLEASE SEE THAT TWO
 SETS CONTAIN A RAISED SEAL OVER A PHOTO-COPIED
 SIGNATURE AND THE THIRD DOES NOT CONTAIN A RAISED
 SEALED OR ORIGINAL SIGNATURE.
 **PLEASE KNOW THIS COMMENT HAS BEEN MADE TO THIS DESIGN
 PROFESSIONAL ON SEVERAL PROJECTS SUBMITTED TO THIS
 JURISDICTION. THIS COMMENT WILL ALSO BE UNDER BUILDINGS
 1 AND 3.
 PLEASE KNOW THIS OFFICE IS RETAINING ALL COPIES
 SUBMITTED FOR POSSIBLE SUBMISSION TO THE FLORIDA BOARD
 OF ENGINEERS.
 THIS IS A FLORIDA STATUTE AND IS ALSO STATED IN THE
 FLORIDA ADMINISTRATIVE CODE.FS 471.025, FAC
 61G15-23.002, FBC 103.1.
 ** WHEN PLANS WERE RE-SUBMITTED THIS REVIEWER NOTICED
 THE INCORRECT VERSION ON THE CALCULATIONS SUBMITTED AND
 NEW CALCULATIONS WITH THE CORRECT VERSION WAS SENT VIA
 FED-EX. PLEASE SEE THAT THE ONES DONE UNDER THE 2004
 FBC WERE ALSO NOT SIGNED, DATED AND SEALED CORRECTLY
 AND AS REQUIRED BY THE FLORIDA STATUTES. THIS SHOWS
 SAME NON-COMPLIANCE ON MULTIPLE SETS OF DOCUMENTS.
 ** PLEASE BE SURE TO GO OVER ALL AND CORRECT.
  
 3) NOTE: PLEASE SEE INFORMATION FOR SITE LIGHTING POLES
 DO NOT CONTAIN THE MINIMUM WIND LOAD INFORMATION.
 PLEASE KNOW IF THIS INFORMATION IS NOT COMPLETE UNDER
 BASE PLANS, THESE WILL BE REQUIRED TO BE UNDER SEPARATE
 PERMITS, PLANS AND FEES.
 PLEASE KNOW HOWEVER THE LIGHTING INFORMATION AS NOTED
 ABOVE IN NOTE #1 FOR THE ENERGY CALCULATIONS WILL STILL
 NEED TO BE CORRECTED.
 PLEASE IDENTIFY THE CIRCUITS AS SHOWN ON PLANS TO WHICH
 BUILDING HOUSE PANEL THEY TERMINATE. PLEASE SEE THIS IS
 DONE FOR THE SITE LIGHTING CIRCUITS FOR BUILDING #2 BUT
 NOT THE OTHERS.
  
 4) NOTE: PLEASE SEE THE SYMBOL LEGEND STILL INDICATES
 *SMOKE DETECTORS*. THIS COULD BE REDLINED IF AND WHEN
 ALL OTHER COMMENTS AS ADDRESSED. PLEASE KNOW IF THERE
 ARE ANY COMMENTS HOWEVER WHICH MAY AFFECT THE SAME
 SHEET(S), PLEASE CORRECT AT THIS TIME. E16.01 THIS
 COULD BE REDLINED ON THIS SHEET IF NOT OTHER CHANGES IS
 MADE.
  
 5) NOTE: PLEASE BE SURE TO CORRELATE ALL LAYOUTS FOR
 UNITS AS THE ELECTRICAL PLANS SEEM TO HAVE DIFFERENT
 LAYOUT(S) FOR SOME UNITS. PLEASE SEE C-3 FOR EXAMPLE ON
 16.03, 16.04.
 PLEASE CORRELATE THE TWO AS THESE LAYOUTS DO NOT MATCH
 AT THIS TIME.
 PLEASE SEE ANY CHANGES IN LIGHTING ETC. PLEASE ALSO BE
 SURE TO COORDINATE WITH THE A-SHEETS.
 FBC 104.1.2 (2001) ADMIN SECTION FOR ADDITIONAL
 INFORMATION AND COORDINATION OF PLANS.
  
 6) NOTE: PLEASE SEE DISHWASHER AND DISPOSAL WHICH IS
 BEING SHOWN WITH A J-BOX. ARE THESE ITEMS GOING TO BE
 HARDWIRED?
 PLEASE SEE 422.30, 422.31 FOR REQUIRED DISCONNECTING
 MEANS.
 ARE THESE NOT CORD AND PLUG TYPE APPLIANCES WHICH WOULD
 PLUG IN?
  
 7) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS AND PLEASE
 KNOW THERE ARE SEVERAL A-SHEETS ON THE REVIEWED SET
 WHICH WERE NOT SEALED WITH THE RAISED EMBOSSED SEAL AS
 REQUIRED UNDER FS 481.221, FAC 61G1-16.002
  
 8) NOTE: PLEASE SEE THE LIGHT FIXTURE OUTSIDE FIRE PUMP
 ROOM WILL BE REQUIRED TO BE BATTERY BACK UP. THIS IS
 SHOWN AS A *J* FIXTURE. AS NO FIXTURE LEGEND WAS
 SUBMITTED THIS CAN NOT BE VERIFIED AT THIS TIME.
 PLEASE ALSO SEE ARE OUT SIDE ELEVATOR EQUIPMENT AREA
 AND MAIN ELECTRICAL ROOM WILL ALSO REQUIRE AN EMERGENCY
 BATTERY BACK UP LIGHTING FIXTURE OF SOME KIND.
 NEC 700.12E, 700.16, LS-101 7.8, 7.9
  
 9) NOTE: PLEASE SEE RISER NOTE #10 WHICH MENTIONS
 CONDUCTORS BEING INSTALLED BY POWER COMPANY HOWEVER
 PLEASE KNOW THE POWER COMPANY (FPL) FLORIDA POWER AND
 LIGHT SHOULD BE CONSULTED.
 IT IS KNOWN TO THIS OFFICE THAT THESE CONDUCTORS AFTER
 THE METERING DEVICES ARE NOT INSTALLED BY THE POWER
 COMPANY AND IN FACT THERE ARE SEVERAL TIMES THE SERVICE
 ENTRANCE CONDUCTORS FROM THE TRANSFORMERS TO THE
 SERVICE METERS AND MAINS ARE ACTUALLY OWNER SUPPLIED.
 THIS WOULD PLACE ALL CONDUITS AND CONDUCTORS UNDER THE
 NEC FOR CODE COMPLIANCE.
 PLEASE ADJUST RISER FOR CONDUCTORS ETC.
 240.4, 310.16
 FBC 106.3.5.1.2
  
 10) NOTE: PLEASE CLARIFY THE FIRE PUMP AND INFORMATION
 AS REQUESTED ON THE PREVIOUS REVIEWS.
 PLEASE SEE NO INFORMATION WAS SUBMITTED WITH RESPECT TO
 THE MINIMUM FUEL REQUIREMENTS AND SIZE OF TANK. PLEASE
 SEE NO TIMES AT 100% RUNNING IS SHOWN.
 PLEASE SEE NFPA-20 9.6.2.2 AND SEE COMMENTS FROM FIRE
 MARSHAL.
 PLEASE SEE THE FUEL NOTE WHICH IS ON SHEET FP13.09 #3,
 DOES NOT CONTAIN THE TEXT FOR CODE.
 PLEASE SEE THE MINIMUM ON THE BASE BUILDING IS REQUIRED
 AT THIS TIME.
 PLEASE SEE THE PREVIOUS NOTES WHICH REQUESTED THIS SAME
 INFORMATION.
 PLEASE SEE THE FP SHEETS INDICATE A DIESEL FIRE PUMP,
 YET THE SUBMITTALS WHICH WERE SUBMITTED WITH PLANS
 INDICATE AN ELECTRICAL FIRE PUMP.
 PLEASE SUBMIT THE ACTUAL DOCUMENTATION AND CORRELATE
 WITH PLANS.
 110.3, 90.7, NFPA-70 695, NFPA-20 2003
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS
 OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE.
 IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY
 WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR,
 PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND
 THIS REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-18 16:30:272007-09-18 16:30:27
  
 REVIEW COMMENCED ON BLDG #3
2007-09-16 13:06:512007-09-16 13:06:51
  
 IN ELEC FOR REVIEW