| 2007-09-20 08:19:00 | |
| | ** DENIED 3RD REVIEW** |
| | |
| | ** PLEASE SEE THERE ARE SOME ITEMS FROM PREVIOUS REVIEW |
| | WHICH ARE STILL IN NEED OF ADDRESSING. PLEASE ALSO SEE |
| | THERE ARE SOME NEW COMMENTS BASED ON REVISED |
| | PLANS/PLANS AND DOCUMENTS NOW SUBMITTED. |
| | ** SOME ITEMS COULD HAVE BEEN REDLINED/PROVISO, HOWEVER |
| | MANY OF THESE ARE IN NEED OF ADDRESSING AT THIS TIME. |
| | |
| | 1) NOTE:PLEASE SEE THE PLANS DO NOT INDICATE FIXTURE |
| | DESIGNATIONS FOR ALL LIGHTING. PLEASE SEE THERE ARE |
| | SEVERAL AREAS INCLUDING FIRST FLOOR AND OTHER FLOORS |
| | WHERE FIXTURES ARE STILL MISSING DESIGNATIONS. PLEASE |
| | SEE THE FIXTURE LEGEND COULD NOT BE COORDINATED WITH |
| | THESE AT THIS TIME. |
| | PLEASE SEE COMMON AREAS WHICH THE LEGEND ON ELECTRICAL |
| | PLANS COULD NOT BE FOUND. |
| | PLEASE SEE THE INFORMATION ON THE INPUT DATA REPORT FOR |
| | EXTERIOR LIGHTING ALSO NEEDS TO CORRELATE WITH PLANS. |
| | THE LIGHTING, TYPES, NUMBER OF FIXTURES, ETC IS NOT |
| | STATED ON THE IDR AS ON PLANS. |
| | PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED AS THE |
| | INPUT DATA REPORT DOES NOT CORRELATE WITH ALL |
| | ELECTRICAL LIGHTING FOR INTERIOR LIGHTING WHICH IS ON |
| | PLANS. PLEASE SEE MISSING A SUBSTANTIAL AMOUNT OF |
| | LIGHTING ON THE INPUT DATA REPORT. |
| | 13-415.0, 415.1.ABCD, 415.1.A, 415.2 |
| | |
| | 2) NOTE: PLEASE SEE ONLY ONE COPY OF THE ENERGY |
| | CALCULATIONS (1.22 VERSION) SUBMITTED ACTUALLY CONTAINS |
| | AN ORIGINAL SIGNATURE AND DATE. PLEASE SEE THAT TWO |
| | SETS CONTAIN A RAISED SEAL OVER A PHOTO-COPIED |
| | SIGNATURE AND THE THIRD DOES NOT CONTAIN A RAISED |
| | SEALED OR ORIGINAL SIGNATURE. |
| | **PLEASE KNOW THIS COMMENT HAS BEEN MADE TO THIS DESIGN |
| | PROFESSIONAL ON SEVERAL PROJECTS SUBMITTED TO THIS |
| | JURISDICTION. THIS COMMENT WILL ALSO BE UNDER BUILDINGS |
| | 1 AND 3. |
| | PLEASE KNOW THIS OFFICE IS RETAINING ALL COPIES |
| | SUBMITTED FOR POSSIBLE SUBMISSION TO THE FLORIDA BOARD |
| | OF ENGINEERS. |
| | THIS IS A FLORIDA STATUTE AND IS ALSO STATED IN THE |
| | FLORIDA ADMINISTRATIVE CODE.FS 471.025, FAC |
| | 61G15-23.002, FBC 103.1. |
| | ** WHEN PLANS WERE RE-SUBMITTED THIS REVIEWER NOTICED |
| | THE INCORRECT VERSION ON THE CALCULATIONS SUBMITTED AND |
| | NEW CALCULATIONS WITH THE CORRECT VERSION WAS SENT VIA |
| | FED-EX. PLEASE SEE THAT THE ONES DONE UNDER THE 2004 |
| | FBC WERE ALSO NOT SIGNED, DATED AND SEALED CORRECTLY |
| | AND AS REQUIRED BY THE FLORIDA STATUTES. THIS SHOWS |
| | SAME NON-COMPLIANCE ON MULTIPLE SETS OF DOCUMENTS. |
| | ** PLEASE BE SURE TO GO OVER ALL AND CORRECT. |
| | |
| | 3) NOTE: PLEASE SEE INFORMATION FOR SITE LIGHTING POLES |
| | DO NOT CONTAIN THE MINIMUM WIND LOAD INFORMATION. |
| | PLEASE KNOW IF THIS INFORMATION IS NOT COMPLETE UNDER |
| | BASE PLANS, THESE WILL BE REQUIRED TO BE UNDER SEPARATE |
| | PERMITS, PLANS AND FEES. |
| | PLEASE KNOW HOWEVER THE LIGHTING INFORMATION AS NOTED |
| | ABOVE IN NOTE #1 FOR THE ENERGY CALCULATIONS WILL STILL |
| | NEED TO BE CORRECTED. |
| | PLEASE IDENTIFY THE CIRCUITS AS SHOWN ON PLANS TO WHICH |
| | BUILDING HOUSE PANEL THEY TERMINATE. PLEASE SEE THIS IS |
| | DONE FOR THE SITE LIGHTING CIRCUITS FOR BUILDING #2 BUT |
| | NOT THE OTHERS. |
| | |
| | 4) NOTE: PLEASE SEE THE SYMBOL LEGEND STILL INDICATES |
| | *SMOKE DETECTORS*. THIS COULD BE REDLINED IF AND WHEN |
| | ALL OTHER COMMENTS AS ADDRESSED. PLEASE KNOW IF THERE |
| | ARE ANY COMMENTS HOWEVER WHICH MAY AFFECT THE SAME |
| | SHEET(S), PLEASE CORRECT AT THIS TIME. E16.01 THIS |
| | COULD BE REDLINED ON THIS SHEET IF NOT OTHER CHANGES IS |
| | MADE. |
| | |
| | 5) NOTE: PLEASE BE SURE TO CORRELATE ALL LAYOUTS FOR |
| | UNITS AS THE ELECTRICAL PLANS SEEM TO HAVE DIFFERENT |
| | LAYOUT(S) FOR SOME UNITS. PLEASE SEE C-3 FOR EXAMPLE ON |
| | 16.03, 16.04. |
| | PLEASE CORRELATE THE TWO AS THESE LAYOUTS DO NOT MATCH |
| | AT THIS TIME. |
| | PLEASE SEE ANY CHANGES IN LIGHTING ETC. PLEASE ALSO BE |
| | SURE TO COORDINATE WITH THE A-SHEETS. |
| | FBC 104.1.2 (2001) ADMIN SECTION FOR ADDITIONAL |
| | INFORMATION AND COORDINATION OF PLANS. |
| | |
| | 6) NOTE: PLEASE SEE DISHWASHER AND DISPOSAL WHICH IS |
| | BEING SHOWN WITH A J-BOX. ARE THESE ITEMS GOING TO BE |
| | HARDWIRED? |
| | PLEASE SEE 422.30, 422.31 FOR REQUIRED DISCONNECTING |
| | MEANS. |
| | ARE THESE NOT CORD AND PLUG TYPE APPLIANCES WHICH WOULD |
| | PLUG IN? |
| | |
| | 7) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS AND PLEASE |
| | KNOW THERE ARE SEVERAL A-SHEETS ON THE REVIEWED SET |
| | WHICH WERE NOT SEALED WITH THE RAISED EMBOSSED SEAL AS |
| | REQUIRED UNDER FS 481.221, FAC 61G1-16.002 |
| | |
| | 8) NOTE: PLEASE SEE THE LIGHT FIXTURE OUTSIDE FIRE PUMP |
| | ROOM WILL BE REQUIRED TO BE BATTERY BACK UP. THIS IS |
| | SHOWN AS A *J* FIXTURE. AS NO FIXTURE LEGEND WAS |
| | SUBMITTED THIS CAN NOT BE VERIFIED AT THIS TIME. |
| | PLEASE ALSO SEE ARE OUT SIDE ELEVATOR EQUIPMENT AREA |
| | AND MAIN ELECTRICAL ROOM WILL ALSO REQUIRE AN EMERGENCY |
| | BATTERY BACK UP LIGHTING FIXTURE OF SOME KIND. |
| | NEC 700.12E, 700.16, LS-101 7.8, 7.9 |
| | |
| | 9) NOTE: PLEASE SEE RISER NOTE #10 WHICH MENTIONS |
| | CONDUCTORS BEING INSTALLED BY POWER COMPANY HOWEVER |
| | PLEASE KNOW THE POWER COMPANY (FPL) FLORIDA POWER AND |
| | LIGHT SHOULD BE CONSULTED. |
| | IT IS KNOWN TO THIS OFFICE THAT THESE CONDUCTORS AFTER |
| | THE METERING DEVICES ARE NOT INSTALLED BY THE POWER |
| | COMPANY AND IN FACT THERE ARE SEVERAL TIMES THE SERVICE |
| | ENTRANCE CONDUCTORS FROM THE TRANSFORMERS TO THE |
| | SERVICE METERS AND MAINS ARE ACTUALLY OWNER SUPPLIED. |
| | THIS WOULD PLACE ALL CONDUITS AND CONDUCTORS UNDER THE |
| | NEC FOR CODE COMPLIANCE. |
| | PLEASE ADJUST RISER FOR CONDUCTORS ETC. |
| | 240.4, 310.16 |
| | FBC 106.3.5.1.2 |
| | |
| | 10) NOTE: PLEASE CLARIFY THE FIRE PUMP AND INFORMATION |
| | AS REQUESTED ON THE PREVIOUS REVIEWS. |
| | PLEASE SEE NO INFORMATION WAS SUBMITTED WITH RESPECT TO |
| | THE MINIMUM FUEL REQUIREMENTS AND SIZE OF TANK. PLEASE |
| | SEE NO TIMES AT 100% RUNNING IS SHOWN. |
| | PLEASE SEE NFPA-20 9.6.2.2 AND SEE COMMENTS FROM FIRE |
| | MARSHAL. |
| | PLEASE SEE THE FUEL NOTE WHICH IS ON SHEET FP13.09 #3, |
| | DOES NOT CONTAIN THE TEXT FOR CODE. |
| | PLEASE SEE THE MINIMUM ON THE BASE BUILDING IS REQUIRED |
| | AT THIS TIME. |
| | PLEASE SEE THE PREVIOUS NOTES WHICH REQUESTED THIS SAME |
| | INFORMATION. |
| | PLEASE SEE THE FP SHEETS INDICATE A DIESEL FIRE PUMP, |
| | YET THE SUBMITTALS WHICH WERE SUBMITTED WITH PLANS |
| | INDICATE AN ELECTRICAL FIRE PUMP. |
| | PLEASE SUBMIT THE ACTUAL DOCUMENTATION AND CORRELATE |
| | WITH PLANS. |
| | 110.3, 90.7, NFPA-70 695, NFPA-20 2003 |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | |
| | *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS |
| | OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. |
| | IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY |
| | WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, |
| | PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND |
| | THIS REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-09-18 16:30:27 | 2007-09-18 16:30:27 |
| | |
| | REVIEW COMMENCED ON BLDG #3 |
| 2007-09-16 13:06:51 | 2007-09-16 13:06:51 |
| | |
| | IN ELEC FOR REVIEW |