Plan Review Notes
Plan Review Notes For Permit 05091687
Permit Number 05091687
Review Stop P
Sequence Number 2
Notes
Date Text
2006-10-11 10:03:16DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW. THE COMMENT NUMBER
 SHALL STAY THE SAME AS THE FIRST REVIEW:
  
 A. OK
 B. OK
 1. OK
 2. OK
  
 3. SHT AP/A5.12 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS. SHOW SF DRAINED FOR EACH
 AREA ALONG WITH 1/2 AREA OF ALL VERTICAL
 WALLS, INCLUDING PARAPETS, AND THE AREA
 OF ANY ROOFS THAT DRAIN ONTO THE ROOF
 AREAS FROM ABOVE. - SHOW THE LOCATION OF
 ALL SECONDARY ROOF DRAINS OR SCUPPERS.
 IF SCUPPERS ARE USED, SUBMIT A DETAIL
 SHOWING HEIGHT, WIDTH, AND DISTANCE TO
 FLOW LINE OFF THE ROOF. SECTION 1503.4.2 ****RESPONSE
 NOTED, BUT SHEETS A5.05,
 A5.13, A5.25 WERE NOT SUBMITTED, AND NO CALCULATIONS
 WITH INFORMATION REQUESTED
 HAS BEEN LOCATED.
  
 4. SHTS AP/A5.61 & AP/A5.62 INDICATE
 SPECIFICATION "A" OR "B" FOR EACH UNIT
 OR BATHROOM AS REQUIRED IN FHA DESIGN
 MANUAL PAGES 7.34 & 7.35. - LAVS SHALL
 BE A MINIMUM OF 2' OFF THE WALL IN ORDER
 TO BE CENTERED ON THE 48" LENGTH OF THE
 CLEAR FLOOR SPACE. PLEASE INDICATE ON
 PLANS. FHA DESIGN MANUAL PAGES 7.47 AND
 7.48. - WATER CLOSET OPENING SHALL BE A
 MINIMUM OF 33" WITH THE WATER CLOSET 18"
 OFF ONE FIXTURE AND 15" OFF THE OTHER
 FIXTURE TO THE CENTER OF THE W/C. FHA
 DESIGN MANUAL PAGES 7.43, 7.44, & 7.45. ****RESPONSE
 NOTED, BUT SPECIFICATION
 "A" OR "B" HAS NOT BEEN INDICATED. ALSO
 THE WATER CLOSET OPENING MEASUREMENTS
 HAS NOT BEEN SHOWN ON THE FLOOR PLAN.
  
 5. SHT AP/A5.56 INDICATE MATERIAL FOR
 GRAB BAR BLOCKING. SECTION 104.2.1.
 ***RESPONSE NOTED, (SEE AP A5.56), BUT
 SHT AP/A5.56 HAS NOT BEEN SUBMITTED.
 PLEASE CLARIFY.
  
 6. OK
 7. OK
  
 8. SUBMIT A DETAIL FOR THE COMMON USE
 TOILET ROOMS SHOWING COMPLIANCE WITH
 SECTIONS 11-4.16, 11-4.19, & 11-4.22 AND
 ALL SUBSECTIONS.
 ****RESPONSE NOTED, (SEE SHEET A5.70 AND
 A5.71), BUT THOSE SHEETS HAVE NOT BEEN
 SUBMITTED.
  
 9. SHTS AP/P14.02 UNITS B3 & B4 MAXIMUM
 4 FU ON A 2" WET VENT IN MASTER BATH.
 TABLE 909.3.
 ****RESPONSE NOTED, BUT NOT THE RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN
 AS THE FLOOR PLAN SHOWS 3" AND THE RISER
 DIAGRAM SHOWS 2-1/2" FOR THE WET VENT.
 CORRELATE RISER AND FLOOR PLAN. SECTION
 104.2.1.
  
 10. OK
  
 11. SHT AP/P14.26 OFFSETS IN THE SANT.
 SHALL BE SHOWN ON EITHER BLDG. DRAIN
 ISOMETRIC RISER DIAGRAM, OR SANT. RISER
 DIAGRAMS. SECTION 104.2.1.
 ****RESPONSE NOTED, BUT WHEN THE SANT.
 RISER FROM UNDERGROUND IS ABOVE THE
 CEILING OF THE FIRST FLOOR, THE RISER
 SPLITS AND OFFSETS INTO OTHER RISERS.
 (EXAMPLE RISER 2,3,6 COMES OUT OF THE
 GROUND AND OFFSETS ABOVE THE CEILING AND
 SPLITS INTO THREE SEPARATE RISERS.
 BUILDING DRAIN ISOMETRIC RISER SHALL
 REFLECT THIS PIPING. SECTION 104.3.1.1.
  
 12. OK
 13. OK
  
 14. AN RPZV BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE BUILDING. SECTION
 608.13.2.
 ****RESPONSE NOTED, BUT COMMENT NOT
 ADDRESSED. EACH BUILDING IS REQUIRED TO
 HAVE ITS OWN RPZV BACKFLOW. INDICATE ON
 PLANS AT THE WATER SERVICE TO THE
 BUILDING.
  
 15. SUBMIT A WATER LAYOUT FOR BUILDING
 AND WATER RISER DIAGRAMS. SHOW ALL PIPE
 SIZES, VALVES, WATER HAMMER ARRESTORS,
 (INSTALLED IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING). SECTIONS 104.3.1.1,
 606.1, 606.2, 608.13.2 & PDI-WH 201.
 ****RESPONSE NOTED, BUT THE WATER RISER
 DIAGRAM SHALL BE SUBMITTED IN ISOMETRIC
 FORM. WATER HAMMER ARRESTORS AND
 REQUIRED VALVES CAN NOT BE SHOWN ON A
 FLAT PIPING LAYOUT.
  
 16. SUBMIT A BUILDING SANITARY DRAIN
 ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE
 SIZES, TRAPS, OFFSETS, RISER LOCATIONS
 WITH RISER NUMBERS, DFU'S AS THEY
 ACCUMULATE IN THE SYSTEM ETC. SECTION
 104.3.1.1.
 ***COMMENT RESPONSE NOTED, BUT COMMENT
 NOT ADDRESSED.
  
 17. SUBMIT A BUILDING STORM DRAIN
 ISOMETRIC RISER DIAGRAM, SHOWING ALL
 PIPE SIZES, RISER LOCATIONS WITH RISER
 NUMBERS, AND SQUARE FEET AS IT
 ACCUMULATES IN THE SYSTEM. SECTION
 104.3.1.1.
 ****RESPONSE NOTED, BUT NOT ADDRESSED.
 SEE COMMENT RESPONSE TO COMMENT #10.
  
 18. OK
  
 **************NEW COMMENTS**************
  
 1B. ALL ARCHITECTURAL SHEETS. THE TITLE
 BLOCK SHALL CONTAIN THE PRINTED NAME OF
 THE PERSON SEALING THE DOCUMENT. FAC 61G1-16.004(6) &
 FS F81.2055.
  
 2B. SHT AP P14.04 PIPING FOR THE
 FIXTURES ON THE SECOND THRU 4TH FLOORS
 SHALL BE SHOWN ON THE FLOOR PLAN WITH
 THE FIXTURES, (SHT P14.05). SECTION
 104.2.1.3.
  
 3B. SHTS AP A5.60, AP A5.61, AP A5.62
 REFER TO SHEET A5.58. THIS SHEET HAS NOT
 BEEN SUBMITTED. PLEASE CLARIFY. SECTION
 104.2.1.
  
 4B. SUBMIT A DETAIL FOR THE DOWNSPOUTS
 AND THE COLLECTOR HEAD AT THE TOP.
 INDICATE SIZE OF DOWNSPOUT, LENGTH,
 WIDTH & HEIGHT OF COLLECTOR HEAD.
 INDICATE ON ROOF PLAN SQUARE FOOTAGE
 DRAINING INTO EACH DOWNSPOUT.
  
 5B. SECONDARY DRAINAGE AND SEPARATE
 SYSTEMS ARE REQUIRED FOR THE ROOF
 DRAINAGE PER SECTIONS 1107.1 & 1107.2.
 PLEASE INDICATE THE LOCATION AND SIZE OF
 THE SECONDARY ROOF DRAINAGE. SUBMIT A
 DETAIL FOR THE SECONDARY ROOF DRAINS.
  
 6B. SHT AP A5.32 ROOF PLAN SHOWS UNITS
 AND FIXTURES. PLEASE CLARIFY. SECTION
 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6713
 E-MAIL [email protected]