| 2006-10-11 10:03:16 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 BUILDING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | FROM PREVIOUS REVIEW. THE COMMENT NUMBER |
| | SHALL STAY THE SAME AS THE FIRST REVIEW: |
| | |
| | A. OK |
| | B. OK |
| | 1. OK |
| | 2. OK |
| | |
| | 3. SHT AP/A5.12 SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS PER |
| | SECTIONS 1106 & 1107 AND ALL |
| | SUBSECTIONS. SHOW SF DRAINED FOR EACH |
| | AREA ALONG WITH 1/2 AREA OF ALL VERTICAL |
| | WALLS, INCLUDING PARAPETS, AND THE AREA |
| | OF ANY ROOFS THAT DRAIN ONTO THE ROOF |
| | AREAS FROM ABOVE. - SHOW THE LOCATION OF |
| | ALL SECONDARY ROOF DRAINS OR SCUPPERS. |
| | IF SCUPPERS ARE USED, SUBMIT A DETAIL |
| | SHOWING HEIGHT, WIDTH, AND DISTANCE TO |
| | FLOW LINE OFF THE ROOF. SECTION 1503.4.2 ****RESPONSE |
| | NOTED, BUT SHEETS A5.05, |
| | A5.13, A5.25 WERE NOT SUBMITTED, AND NO CALCULATIONS |
| | WITH INFORMATION REQUESTED |
| | HAS BEEN LOCATED. |
| | |
| | 4. SHTS AP/A5.61 & AP/A5.62 INDICATE |
| | SPECIFICATION "A" OR "B" FOR EACH UNIT |
| | OR BATHROOM AS REQUIRED IN FHA DESIGN |
| | MANUAL PAGES 7.34 & 7.35. - LAVS SHALL |
| | BE A MINIMUM OF 2' OFF THE WALL IN ORDER |
| | TO BE CENTERED ON THE 48" LENGTH OF THE |
| | CLEAR FLOOR SPACE. PLEASE INDICATE ON |
| | PLANS. FHA DESIGN MANUAL PAGES 7.47 AND |
| | 7.48. - WATER CLOSET OPENING SHALL BE A |
| | MINIMUM OF 33" WITH THE WATER CLOSET 18" |
| | OFF ONE FIXTURE AND 15" OFF THE OTHER |
| | FIXTURE TO THE CENTER OF THE W/C. FHA |
| | DESIGN MANUAL PAGES 7.43, 7.44, & 7.45. ****RESPONSE |
| | NOTED, BUT SPECIFICATION |
| | "A" OR "B" HAS NOT BEEN INDICATED. ALSO |
| | THE WATER CLOSET OPENING MEASUREMENTS |
| | HAS NOT BEEN SHOWN ON THE FLOOR PLAN. |
| | |
| | 5. SHT AP/A5.56 INDICATE MATERIAL FOR |
| | GRAB BAR BLOCKING. SECTION 104.2.1. |
| | ***RESPONSE NOTED, (SEE AP A5.56), BUT |
| | SHT AP/A5.56 HAS NOT BEEN SUBMITTED. |
| | PLEASE CLARIFY. |
| | |
| | 6. OK |
| | 7. OK |
| | |
| | 8. SUBMIT A DETAIL FOR THE COMMON USE |
| | TOILET ROOMS SHOWING COMPLIANCE WITH |
| | SECTIONS 11-4.16, 11-4.19, & 11-4.22 AND |
| | ALL SUBSECTIONS. |
| | ****RESPONSE NOTED, (SEE SHEET A5.70 AND |
| | A5.71), BUT THOSE SHEETS HAVE NOT BEEN |
| | SUBMITTED. |
| | |
| | 9. SHTS AP/P14.02 UNITS B3 & B4 MAXIMUM |
| | 4 FU ON A 2" WET VENT IN MASTER BATH. |
| | TABLE 909.3. |
| | ****RESPONSE NOTED, BUT NOT THE RISER |
| | DIAGRAM DOES NOT REFLECT THE FLOOR PLAN |
| | AS THE FLOOR PLAN SHOWS 3" AND THE RISER |
| | DIAGRAM SHOWS 2-1/2" FOR THE WET VENT. |
| | CORRELATE RISER AND FLOOR PLAN. SECTION |
| | 104.2.1. |
| | |
| | 10. OK |
| | |
| | 11. SHT AP/P14.26 OFFSETS IN THE SANT. |
| | SHALL BE SHOWN ON EITHER BLDG. DRAIN |
| | ISOMETRIC RISER DIAGRAM, OR SANT. RISER |
| | DIAGRAMS. SECTION 104.2.1. |
| | ****RESPONSE NOTED, BUT WHEN THE SANT. |
| | RISER FROM UNDERGROUND IS ABOVE THE |
| | CEILING OF THE FIRST FLOOR, THE RISER |
| | SPLITS AND OFFSETS INTO OTHER RISERS. |
| | (EXAMPLE RISER 2,3,6 COMES OUT OF THE |
| | GROUND AND OFFSETS ABOVE THE CEILING AND |
| | SPLITS INTO THREE SEPARATE RISERS. |
| | BUILDING DRAIN ISOMETRIC RISER SHALL |
| | REFLECT THIS PIPING. SECTION 104.3.1.1. |
| | |
| | 12. OK |
| | 13. OK |
| | |
| | 14. AN RPZV BACKFLOW IS REQUIRED ON THE |
| | WATER SERVICE TO THE BUILDING. SECTION |
| | 608.13.2. |
| | ****RESPONSE NOTED, BUT COMMENT NOT |
| | ADDRESSED. EACH BUILDING IS REQUIRED TO |
| | HAVE ITS OWN RPZV BACKFLOW. INDICATE ON |
| | PLANS AT THE WATER SERVICE TO THE |
| | BUILDING. |
| | |
| | 15. SUBMIT A WATER LAYOUT FOR BUILDING |
| | AND WATER RISER DIAGRAMS. SHOW ALL PIPE |
| | SIZES, VALVES, WATER HAMMER ARRESTORS, |
| | (INSTALLED IN AN "EFFECTIVE RANGE" NOT |
| | IN THE CEILING). SECTIONS 104.3.1.1, |
| | 606.1, 606.2, 608.13.2 & PDI-WH 201. |
| | ****RESPONSE NOTED, BUT THE WATER RISER |
| | DIAGRAM SHALL BE SUBMITTED IN ISOMETRIC |
| | FORM. WATER HAMMER ARRESTORS AND |
| | REQUIRED VALVES CAN NOT BE SHOWN ON A |
| | FLAT PIPING LAYOUT. |
| | |
| | 16. SUBMIT A BUILDING SANITARY DRAIN |
| | ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE |
| | SIZES, TRAPS, OFFSETS, RISER LOCATIONS |
| | WITH RISER NUMBERS, DFU'S AS THEY |
| | ACCUMULATE IN THE SYSTEM ETC. SECTION |
| | 104.3.1.1. |
| | ***COMMENT RESPONSE NOTED, BUT COMMENT |
| | NOT ADDRESSED. |
| | |
| | 17. SUBMIT A BUILDING STORM DRAIN |
| | ISOMETRIC RISER DIAGRAM, SHOWING ALL |
| | PIPE SIZES, RISER LOCATIONS WITH RISER |
| | NUMBERS, AND SQUARE FEET AS IT |
| | ACCUMULATES IN THE SYSTEM. SECTION |
| | 104.3.1.1. |
| | ****RESPONSE NOTED, BUT NOT ADDRESSED. |
| | SEE COMMENT RESPONSE TO COMMENT #10. |
| | |
| | 18. OK |
| | |
| | **************NEW COMMENTS************** |
| | |
| | 1B. ALL ARCHITECTURAL SHEETS. THE TITLE |
| | BLOCK SHALL CONTAIN THE PRINTED NAME OF |
| | THE PERSON SEALING THE DOCUMENT. FAC 61G1-16.004(6) & |
| | FS F81.2055. |
| | |
| | 2B. SHT AP P14.04 PIPING FOR THE |
| | FIXTURES ON THE SECOND THRU 4TH FLOORS |
| | SHALL BE SHOWN ON THE FLOOR PLAN WITH |
| | THE FIXTURES, (SHT P14.05). SECTION |
| | 104.2.1.3. |
| | |
| | 3B. SHTS AP A5.60, AP A5.61, AP A5.62 |
| | REFER TO SHEET A5.58. THIS SHEET HAS NOT |
| | BEEN SUBMITTED. PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | |
| | 4B. SUBMIT A DETAIL FOR THE DOWNSPOUTS |
| | AND THE COLLECTOR HEAD AT THE TOP. |
| | INDICATE SIZE OF DOWNSPOUT, LENGTH, |
| | WIDTH & HEIGHT OF COLLECTOR HEAD. |
| | INDICATE ON ROOF PLAN SQUARE FOOTAGE |
| | DRAINING INTO EACH DOWNSPOUT. |
| | |
| | 5B. SECONDARY DRAINAGE AND SEPARATE |
| | SYSTEMS ARE REQUIRED FOR THE ROOF |
| | DRAINAGE PER SECTIONS 1107.1 & 1107.2. |
| | PLEASE INDICATE THE LOCATION AND SIZE OF |
| | THE SECONDARY ROOF DRAINAGE. SUBMIT A |
| | DETAIL FOR THE SECONDARY ROOF DRAINS. |
| | |
| | 6B. SHT AP A5.32 ROOF PLAN SHOWS UNITS |
| | AND FIXTURES. PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | |