| 2006-12-21 11:32:34 | DENIED:BUILDING #3 / 2001 FBC |
| | |
| | RESPONSE COMMENTS FROM REVIEW DATED 1-31-06: |
| | |
| | COMMENT #1: OK |
| | |
| | COMMENT #2: RESPONSE INDICATES NOTE FOR RETURN AIR |
| | ON SHEETS M15.01 THROUGH M15.03.PLEASE NOTE, THE R/A |
| | INDICATED ON THE PLAN IS CONSIDERED A TRANSFER UNDER |
| | 2001 FMC 601.4 EXCEPTION 2 NOT 1.PLEASE VERIFY GRILLE |
| | SIZE INTO THE MASTER SUITE.ALL AIR INTO THE MATER |
| | SUITE IS TO BE INCLUDED IN THE CALCULATION (I.E., |
| | BATHROOM, CLOSET, ETC.)PLEASE ALSO NOTE WALL CAVITIES |
| | USED FOR TRANSPORTING R/A SHALL BE LINED WITH AN AIR |
| | BARRIER & SEALED IN ACCORDANCE WITH 2001 FBC CHAPTER 13 |
| | SUB-CHAPTER 410.1.ABCD.3.7. |
| | |
| | COMMENT #3:RESPONSE INDICATES AHU CLOSET DOOR IS |
| | NON-COMBUSTIBLE BUT THE DOOR SCHEDULE ON SHEET A9.02 |
| | STILL INDICATES A WOOD DOOR.PLEASE CLARIFY. |
| | |
| | COMMENT #4:RESPONSE STATES THE CLEARANCE AROUND THE |
| | AHU EXCEEDS THE 4" REQUIREMENT UNDER 2001 FMC |
| | 603.1.3.4.THE DETAIL ON PLAN SHEET M15.09 DOES NOT |
| | REFLECT OR ANNOTATE A 4" CLEARANCE.PLEASE ALSO NOTE, |
| | THE CONDENSATE LINE SHALL BE OF NON-COMBUSTIBLE |
| | MATERIAL (NO PVC IN AHU CLOSET). |
| | |
| | COMMENT #5:RESPONSE REFERS TO "CONDENSATE TRAP |
| | DETAIL" ON SHEET M15.09.PER 2001 FMC 307.2.3 & |
| | 307.2.4 AN AUXILIARY DRAIN PAN IS REQUIRED.PLEASE |
| | CONTACT HAROLD MOSER, CHIEF MECHANICAL INSPECTOR WITH |
| | REGARDS TO INSTALLATION OF FLOAT SWITCH IN THE |
| | AUXILIARY DRAIN OUTLET (TRAP).HAROLD MOSER MAY BE |
| | CONTACTED AT (561)805-6732. |
| | |
| | COMMENT #6:OK |
| | |
| | COMMENT #7:OK |
| | |
| | COMMENT #8:OK |
| | |
| | COMMENT #9:OK |
| | |
| | COMMENT #10: OK |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS |