2006-12-21 11:32:34DENIED:BUILDING #3 / 2001 FBC
  
 RESPONSE COMMENTS FROM REVIEW DATED 1-31-06:
  
 COMMENT #1: OK
  
 COMMENT #2: RESPONSE INDICATES NOTE FOR RETURN AIR
 ON SHEETS M15.01 THROUGH M15.03.PLEASE NOTE, THE R/A
 INDICATED ON THE PLAN IS CONSIDERED A TRANSFER UNDER
 2001 FMC 601.4 EXCEPTION 2 NOT 1.PLEASE VERIFY GRILLE
 SIZE INTO THE MASTER SUITE.ALL AIR INTO THE MATER
 SUITE IS TO BE INCLUDED IN THE CALCULATION (I.E.,
 BATHROOM, CLOSET, ETC.)PLEASE ALSO NOTE WALL CAVITIES
 USED FOR TRANSPORTING R/A SHALL BE LINED WITH AN AIR
 BARRIER & SEALED IN ACCORDANCE WITH 2001 FBC CHAPTER 13
 SUB-CHAPTER 410.1.ABCD.3.7.
  
 COMMENT #3:RESPONSE INDICATES AHU CLOSET DOOR IS
 NON-COMBUSTIBLE BUT THE DOOR SCHEDULE ON SHEET A9.02
 STILL INDICATES A WOOD DOOR.PLEASE CLARIFY.
  
 COMMENT #4:RESPONSE STATES THE CLEARANCE AROUND THE
 AHU EXCEEDS THE 4" REQUIREMENT UNDER 2001 FMC
 603.1.3.4.THE DETAIL ON PLAN SHEET M15.09 DOES NOT
 REFLECT OR ANNOTATE A 4" CLEARANCE.PLEASE ALSO NOTE,
 THE CONDENSATE LINE SHALL BE OF NON-COMBUSTIBLE
 MATERIAL (NO PVC IN AHU CLOSET).
  
 COMMENT #5:RESPONSE REFERS TO "CONDENSATE TRAP
 DETAIL" ON SHEET M15.09.PER 2001 FMC 307.2.3 &
 307.2.4 AN AUXILIARY DRAIN PAN IS REQUIRED.PLEASE
 CONTACT HAROLD MOSER, CHIEF MECHANICAL INSPECTOR WITH
 REGARDS TO INSTALLATION OF FLOAT SWITCH IN THE
 AUXILIARY DRAIN OUTLET (TRAP).HAROLD MOSER MAY BE
 CONTACTED AT (561)805-6732.
  
 COMMENT #6:OK
  
 COMMENT #7:OK
  
 COMMENT #8:OK
  
 COMMENT #9:OK
  
 COMMENT #10: OK
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL AT [email protected].
  