Plan Review Notes
Plan Review Notes For Permit 05091687
Permit Number 05091687
Review Stop E
Sequence Number 2
Notes
Date Text
2006-12-31 19:44:43**** UNSAT2ND REVIEW ********
  
 COURTNEY LAKES BUILDING #3
 N. CONGRESS.
  
 ** PLEASE SEE MANY OF THE SAME COMMENTS FROM THE
 PREVIOUS REVIEW STILL NEED TO BE ADDRESSED.
  
 ** PLEASE SEE AS THREE SEPARATE BUILDING PERMITS AND
 PLANS ARE NOW SEPARATED FOR EACH, PLEASE ALSO SEE NEW
 COMMENTS BASED ONE THE PLANS NOW SUBMITTED INTO EACH
 SET.
  
 ** PLEASE ALSO SEE THERE ARE SOME NEW NOTES BASED ON
 PLANS SUBMITTED.
  
 ** PLEASE SEE BELOW ARE SOME OF THE NOTES FROM THE
 PREVIOUS REVIEW ARE BEING NOTED IF ADDRESSED OR NOT BY
 A "NO, OK, NO/OK, N/A OR SEE NEW ".
 1) NO WILL HAVE FURTHER EXPLANATION IN AN ATTEMPT TO
 BETTER EXPLAIN COMMENT MADE.
 2) OK, WILL HAVE PREVIOUS NOTE REMOVED.
 3) NO/OK, MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL. THIS WILL ALSO BE FOLLOWED
 BY FURTHER EXPLANATION OF PREVIOUS NOTE.
 4) N/A, THIS MEANS THE COMMENT NO LONGER APPLIES TO
 THIS BUILDING AND PREVIOUS NOTE IS REMOVED.
  
 ** PLEASE SEE ALL NEW NOTES WILL BE NOTED AT THE END OF
 PREVIOUS REVIEW COMMENTS AND WILL BE INDICATED WITH
 **** NEW NOTES**.
  
  
 1) NOTE: OK. SEE NOTES.
  
 2) NOTE: OK
  
 3) NOTE:NO, PLEASE SEE RESPONSE MENTIONS PLANS
 DESIGNED UNDER THE CODES AS NOTED, HOWEVER ALL CODES
 RELEVANT TO THE DESIGN IN WHICH THE BUILDING IS
 PERMITTED UNDER SHALL BE STATED ON PLANS. PLEASE SEE
 THIS IS REQUIRED OF ARCHITECTURAL SHEETS AS WELL AS
 ELECTRICAL AND FIRE. PLEASE SEE ANY OTHER NOTES WITH
 RESPECT TO THIS FROM OTHER TRADES.
 THE FOLLOWING SHALL BE STATED. 2002 NEC/NFPA-70, 2002
 NFPA-72, 2003 NFPA-20 AND 2003 NFPA-101. (THE CORRECT
 NFPA-101 IS NOTED )
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE TO CORRECT THE CURRENT NEC/ NFPA-70 IN
 EFFECT.
 PLEASE KNOW, AS OF JULY 1ST, 2003 THE STATE OF FLORIDA
 ADOPTED THE 2002
 NFPA-70 (NEC). PLANS REFERENCE 1999. PLEASE SEE SOME
 ELECTRICAL COMMENTS WHICH WILL AFFECT THIS.
 PLEASE SEE NEXT COMMENT WITH RESPECT TO PERMITS APPLIED
 FOR UNDER THE 2001 FBC BEFORE OCT 1ST, 2005 AND PERMITS
 ON OCT 1ST, 2005.
  
 4) NOTE: N/A, SEE NEW NOTES FOR EACH BUILDING.
  
  
 5) NOTE: N/A, SEE NEW NOTES UNDER EACH BUILDING.
  
 6) NOTE:NO, PLEASE SEE THERE ARE SEVERAL AREAS WHICH
 CIRCUITING IS NOT COMPLETE INCLUDING UNITS FOR SMOKE
 DEVICES AND MANY AREAS OF HOUSE/COMMON AREAS/ SITE ETC.
 PLEASE SEE MANY NEW COMMENTS BASED ON PLANS SUBMITTED.
 PLEASE SHOW ALL AND CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULES. SEE NEW NOTES.
 FBC ADMIN SECTION 104.1.2
  
 PLEASE COMPLETE ALL CIRCUITING ON PLANS IN ORDER TO
 REVIEW CODE COMPLIANCE FOR AREAS OF UNITS AND COMMON
 AREAS.
  
 7) NOTE: NO, SAME COMMENT. THIS IS NOT EXPLAINED ANY
 FURTHER. PLEASE HOWEVER ALSO SEE NEW COMMENTS BASED ON
 PLANS SUBMITTED.
 ** PLEASE KNOW THERE ARE AREAS OF PLANS WITH
 DESIGNATIONS, ITEMS FOR CODE COMPLIANCE FOR CIRCUITING
 TO THOSE AREAS CAN NOT BE VERIFIED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE ROOM AND AREA DESIGNATIONS ON PLANS,
 INCLUSIVE OF ALL UNITS AND COMMON AREAS.
 REVIEW FOR SOME CODE COMPLIANCE ITEMS CAN NOT BE DONE
 AT THIS TIME.
  
 8) NOTE:NO, PLEASE SEE RESPONSE LETTER MENTIONS TO
 SEE SHEET AP E16.00A, YET PLEASE KNOW COMPLETED
 PHOTO-METRICS SHALL BE SUBMITTED IN EACH SUBMITTED
 PLANS FOR EACH BUILDING AS EACH BUILDING IS ITS OWN
 LEGAL RECORD.
 PLEASE ALSO SEE PREVIOUS NOTES, PLEASE SEE ONLY PARTIAL
 PHOTO-METRICS WERE SUBMITTED. PLEASE SEE NOTE WHICH
 REQUIRES ALL UNDER NORMAL AND EMERGENCY AND FOR ALL
 EGRESS AREAS. PLEASE SEE ONLY SOME ARE BEING SHOWN IN
 THE PLANS UNDER BUILDING ONE. PLEASE KNOW THESE CAN BE
 TYPICAL, HOWEVER THEY SHALL ALSO BE SPECIFIC TO EACH
 AREA IF THE LAYOUT OF THESE AREAS CHANGES WHICH THEY
 DO. NOT ALL AREAS ARE THE LIKE.
 PLEASE SEE NEW NOTES ALSO FOR EGRESS FROM UNITS AND
 PLEASE SEE NEW NOTES PERTAINING TO PARKING LOT, AND
 SITE LIGHTING.
 PLEASE KNOW AS THE SWIMMING POOL IS NOT UNDER THIS
 PERMIT FOR THE BUILDING, STAMPED PLANS FROM PALM BEACH
 COUNTY HEALTH DEPT IS NOT REQUIRED AT THIS TIME UNDER
 THIS PERMIT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE COMPLETE PHOTO-METRICS FOR ALL COMMON
 AREAS, GARAGE AREA, COMMON AREA CORRIDORS, STAIR TOWERS
 ETC.
 PLEASE SEE 2003 NFPA-101 7.8.1.3 AND 7.9.2.2 WHICH
 REQUIRE A MIN OF 10FT CANDLES FOR STAIR TOWERS UNDER
 NORMAL OPERATION AS WALK SURFACE AND A MIN OF 1FT
 CANDLE AT WALK SURFACE UNDER EMERGENCY CONDITIONS.
 PLEASE ALSO SEE OTHER WALK AREAS, GARAGE, CORRIDORS ETC
 AND THE MIN OF 1FT CANDLE.
 **PLEASE SEE PALM BEACH COUNTY SECURITY CODE ORDINANCE
 WITH RESPECT TO MIN DESIGN OF PARKING LOT LIGHTING
 LEVELS UNDER NORMAL CONDITIONS. (ONLY NOTED FOR DESIGN)
 NOT REQUIRED. PLEASE SEE ANY REQUIREMENTS FROM INS
 CARRIER WHICH REQUIRES A MIN LEVEL OF LIGHTING.
 ** PLEASE SEE PHOTO-METRICS OR SITE PLAN WAS NOT
 SUBMITTED FOR PROPOSED POOL AREA. THE POOL STRUCTURE IS
 REQUIRED TO BE UNDER A SEPARATE PERMIT. PLEASE KNOW,
 THE PHOTO-METRICS FOR POOL AREA WILL BE REQUIRED AND
 WILL ALSO BE REQUIRED TO BE REVIEWED AND STAMPED BY THE
 PALM BEACH COUNTY HEALTH DEPT FOR ANY PROPOSED
 NIGHT-TIME SWIMMING.
  
 7) NOTE: NO, PLEASE SEE EACH SET OF PLANS SHALL CONTAIN
 A SITE LIGHTING PLAN SHOWING ALL CIRCUITING AND
 CORRELATE WITH EACH OF THE HOUSE PANELS FOR EACH
 BUILDING IN WHICH THEY ARE BEING CIRCUITED TO. PLEASE
 SEE ALL SITE LIGHTING AS SHOWN IN THE SET OF PLANS FOR
 BUILDING ONE. PLEASE SEE THE CIRCUITING AS SHOWN DOES
 NOT CORRELATE WITH HOUSE PANEL FOR BUILDING THREE IN
 ANY WAY. PLEASE SEE HOUSE PANEL FOR THESE CIRCUITS ARE
 IN FACT BLANK AND SHOWS THE WORDING OF "SPACE". PLEASE
 KNOW AT THIS TIME THERE ARE MANY ITEMS PERTAINING TO
 SITE LIGHTING WHICH CAN NOT BE VERIFIED FOR VOLTAGE
 DROP, CIRCUITS, OVER CURRENT PROTECTION, CONDUCTOR
 SIZES ETC.
 PLEASE SEE NO INFORMATION WAS SUBMITTED OR SHOWN FOR
 WIND LOADS ON POLES.
 240.4, 310.16, 408.4, FBC 104.2.1,104.21.2
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NO "ELECTRICAL SITE-PLAN" WAS SUBMITTED FOR
 ANY SITE LIGHTING, LANDSCAPE LIGHTING ETC.
 PLEASE KNOW, IF NOT SUBMITTED UNDER THIS PERMIT AND
 VALUES ADJUSTED ACCORDINGLY, SEPARATE PERMIT , PLANS
 AND FEES WILL BE REQUIRED FOR ALL SITE LIGHTING,
 LANDSCAPE LIGHTING WORK.
 ** ALSO NOTE: IN THAT COMPLETE WIND LOADING
 CALCULATIONS FOR LT POLES INCLUSIVE OF THE ATTACHMENT
 OF LT FIXTURES WILL BE REQUIRED TO BE SUBMITTED WITH
 PLANS AND PERMIT APPLICATION FOR REVIEW.
  
 8) NOTE: NO, PLEASE SEE ONCE AGAIN NOT ALL ROOMS ARE
 DONE AS REQUIRED. PLEASE SEE MAIN ELECTRICAL ROOM FOR
 THIS BUILDING ALONE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INCLUDE AN EMERGENCY BATTERY BACK UP LT OF SOME
 SORT IN ALL ELECTRICAL ROOMS, FIRE PUMP ROOM, AND
 ELEVATOR MACHINE RMS. SOME ARE SHOWN, BUT NOT ALL.
 7.8,7.9, 700.16 ETC
  
 9) NOTE:NO, PLEASE SEE NOT ONLY ARE MANY CIRCUITS NOT
 SHOWN ON PLANS NO CHANGES FOR THE REQUIRED DEDICATED
 CIRCUITS HAVE BEEN MADE. PLEASE SEE PLANS AND CORRELATE
 WITH THE HOUSE PANEL FOR THIS BUILDING.
 PLEASE SEE 620.22,23,24 AND 620.51 ETC
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 620.23, AND 620.24 FOR REQUIRED DEDICATED
 BRANCH CIRCUITS FOR ELEVATOR PITS, AND ELEVATOR MACHINE
 RMS/EQUIPMENT AREAS.
 PLEASE ADJUST HOUSE PANELS AS NEEDED.
  
 10) NOTE: NO, PLEASE SEE NO INFORMATION WAS LOCATED ON
 RISER SHEETS. PLEASE SEE NO INFORMATION WAS SHOWN ON FP
 FOR THE FIRE PUMP, SIZE, FUEL CONSUMPTION, TIME OF
 OPERATION UNDER THE AMOUNT OF FUEL ETC. PLEASE SEE THE
 SPECS/CUT SHEETS SUBMITTED CONTAIN MULTIPLE UNITS AND
 NO REVIEW FOR CODE COMPLIANCE OF THE UNIT FOR EACH
 BUILDING BASED ON THE NUMEROUS PUMPS SUBMITTED. PLEASE
 ALSO SEE MISSING FIRE PUMP CONTROLLER SPECS. PLEASE
 ALSO SEE MISSING THE RELEVANT CODES ON FP SHEETS.
 PLEASE KNOW BASED ON THE PLANS SUBMITTED AND SPEC/CUT
 SHEETS SUBMITTED, REVIEW FOR COMPLIANCE CAN NOT BE DONE
 AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE ELECTRICAL RISER SHOULD "NOTE" FIRE PUMP
 AS DIESEL AS NOTED ON FP SHEETS.
 PLEASE SUBMIT ALL MANUFACTURES SPEC/CUT SHEETS FOR FIRE
 PUMP CONTROLLER AS REVIEW FOR CODE COMPLIANCE UNDER
 2003 NFPA-20 IS REQUIRED.
 PLEASE ALSO SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS
 FOR FUEL TANK.
 PLEASE SEE NFPA-20 9.6.2.2 AS THE FUEL CAPACITY IS
 REQUIRED TO BE SIZED BASE ON THE 100% RATED LOAD FOR A
 MIN OF 8HRS, OR TIME SO DETERMINED BY THE FIRE
 MARSHAL'S OFFICE DEPENDING ON OCCUPANCY.
 FUEL SYSTEMS WILL BE UNDER OTHER TRADE REVIEW(S). (FIRE
 AND MECH).
  
 11) NOTE: NO, RESPONSE MENTIONS THIS WAS DONE, HOWEVER
 PLEASE SEE UNIT PANEL SCHEDULES AND HOUSE PANEL
 SCHEDULE DOES NOT CONTAIN AND CONDUCTOR SIZES. PLEASE
 KNOW BASED ON COMMENTS ABOVE WITH RESPECT TO AREA
 DESIGNATIONS, CIRCUITING MISSING ON PLANS, REVIEW OF
 THIS CAN NOT BE DONE AT THIS TIME.408.4 , FBC 104.1.2
 ADMINSECTION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INCLUDE ALL MINIMUM CONDUCTOR SIZES ON ALL
 PANELS, UNITS AND HOUSE PANELS. REVIEW FOR THESE ITEMS
 OF CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME.
 310.16, 240.4,215.5
  
 12) NOTE:NO, AS CIRCUITING FOR THIS BUILDING IS NOT
 COMPLETE AT THIS TIME, THE OVER CURRENT PROTECTIVE
 DEVICES CAN NOT BE VERIFIED AT THIS TIME. THIS COMMENT
 WAS MAINLY FOR THE OCP DEVICES WHICH WERE BEING SHOWN
 ON BUILDING #1'S PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE GARAGE/HOUSE LIGHTING BEING INDICATED ON 30A
 AND 50A CIRCUITS.
 PLEASE SEE CODE DOES LIMIT THE OCP FOR UNIT FIXTURES
 FOR PROTECTION OF FIXTURES ON A BRANCH CIRCUIT. PLEASE
 ADJUST CIRCUITING AS NEEDED.
 PLEASE ALSO SEE A FIXTURE SCHEDULE CONTAINING WATTAGES,
 VOLTAGES ETC WAS NOT SUBMITTED.
 PLEASE VERIFY IF THESE UNIT FIXTURES ARE RATED TO HAVE
 OCP AT ABOVE MENTIONED.
 240.4, 310.16 ETC
  
 13) NOTE: OK, HOWEVER SEE NOTES.
  
 14) NOTE:NO/OK, PLEASE SEE PART OF THIS COMMENT SEEMS
 TO HAVE BEEN ADDRESSED, HOWEVER PLEASE SEE NOTES ON
 RISER AND RISER NOTES WHICH STILL DO NOT CORRELATE.
 PLEASE SEE SEVERAL NOTE #1'S, YET ON RISER NOTES NOT
 ALL OF THESE NOTE #1'S CAN POSSIBLY APPLY. PLEASE
 ADJUST ALL NOTE SON RISER AND NOTES NOTED AS RISER
 NOTES.
  
 ** PREVIOUS REVIEW NOTE **
 , PLEASE SEE PLEASE SEE MAX OCP TO BE SIZED FOR
 PANELS/EQUIPMENT BEING FED BY SAID OCP.
 PLEASE SEE MANY UNIT PANELS ARE SHOWN AS 100A MLO, WITH
 125A OCP AS LISTED ON RISER ETC.
 PLEASE ALSO SEE RISER NOTE #4 WHICH INDICATES 125A
 2-POLE ETC, HOWEVER PLEASE SEE RISER AS THIS NOTE #4
 COULD NOT BE LOCATED. (APPEARS TO BE MISPRINTED FOR
 "NOTE#7" ON RISER) 240.4,408,310.16,215.5 ETC.
  
 15) NOTE: N/A, NOT PART OF THESE PLANS FOR THIS
 BUILDING. SEE NEW NOTES.
  
 16) NOTE: N/A, NOT PART OF THESE PLANS FOR THIS
 BUILDING. SEE NEW NOTES.
  
 17) NOTE: N/A, NOT PART OF THESE PLANS FOR THIS
 BUILDING. SEE NEW NOTES.
  
 18) NOTE: NO/OK, SOME SHEETS SHOW NOTE, HOWEVER NOT ALL
 FOR UNITS. CIRCUITING IS NOT YET COMPLETE TO REVIEW
 THESE FOR CODE COMPLIANCE. PLEASE LABEL ALL CIRCUITS ON
 PANEL SCHEDULE WHICH CONTAIN AFCI PROTECTION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THESE SHEETS ALSO REFERENCE "ARC FAULT"
 PROTECTION FROM THE 1999 NEC, WHICH ONLY REQUIRED
 PROTECTION OF RECEPTS.
 PLEASE SEE THE 2002 NEC WHICH REQUIRES PROTECTION FOR
 ALL "OUTLETS" IN BEDRMS. THIS IS INCLUSIVE OF RECEPTS,
 LTS, FANS, SMOKE DETECTORS ETC. PLEASE SEE NOTE ON UNIT
 PLANS AND ADJUST.
  
 19) NOTE:THIS IS UNCLEAR AT THIS TIME, AS PERMIT
 APPLICATION FOR BUILDING #3 INDICATES 450 UNITS, YET
 METER CALCULATIONS CONTAINS NOTE OF 40 METERS FOR EACH
 METER CENTER. PLEASE CORRELATE PLANS, PERMIT
 APPLICATIONS AND ADJUST PLANS AS NEEDED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE LOADS, UNITS, PANELS, AND
 BUILDING/METER LOAD CALCULATIONS:
 A) PLEASE SEE PANEL SCHEDULE/LOAD CALCULATIONS FOR UNIT
 "B-3" SHOWN ON
 16.26, HOWEVER THIS UNIT TYPE OR LOADS COULD NOT BE
 LOCATED ON BLDG LOAD CALCULATIONS ON 16.25?
 B) PLEASE ALSO SEE THE SAME COMMENT ABOVE FOR UNIT
 "C-2" WHICH IS ALSO SHOWN ON
 16.26 BUT NOT IN CALCS ON 16.25??
 ** PLEASE ADJUST ALL AS NEEDED.
  
 20) NOTE: OK, HOWEVER STILL NOT ADDED TO RISER, ONLY
 SHOWN IN GROUNDING DETAIL. PLEASE EXPLAIN RATIONAL OF
 TWO GROUNDING ELECTRODE SYSTEMS SHOWN?
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INCLUDE THE REQUIRED FOOTER STEEL ON THE
 GROUNDING ELECTRODE RISER DETAIL. PLEASE ALSO SHOW ON
 RISER.
 250.50.
  
 21) NOTE: NO, PREVIOUS NOTE REQUESTED A NOTE/DETAIL
 WHICH WOULD ACTUALLY PROVIDE A LITTLE MORE INFORMATION
 FOR THIS REQUIREMENT. PLEASE EXPAND ON NOTE.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE PROVIDE A DETAIL/NOTE FOR ALL RACEWAY SEALS AS
 REQUIRED PER
 230.8
  
 22) NOTE: N/A.
  
 23) NOTE: N/A.
  
 24) NOTE: N/A
  
 25) NOTE: OK.
  
 26) NOTE: OK.
  
 27) NOTE: OK.
  
 28) NOTE: NO, PLEASE SEE THE 2001 FBC 905.2 WHICH DOES
 NOT MENTION THE EXCEPTION AS PERMITTED BY NFPA-72. THE
 MORE RESTRICTIVE SHALL APPLY. PLEASE SEE NEW NOTES FOR
 THESE DEVICES AND CIRCUITING.
  
 ** PREVIOUS REVIEW NOTE **
 SMOKE DETECTORS ARE REQUIRED INSIDE AND OUTSIDE ALL
 SLEEPING ROOMS.
 PLEASE SEE 2002 NFPA-72 11.5.3.1
 PLEASE ADJUST NOTE FOR SD'S ON PLANS AS
 SD'S ARE REQUIRED 3' FROM BATH/KITCHEN DOORS, 3' FROM
 SUPPLY AIR DIFFUSERS, 5' FROM R/A GRILLES AND 20' FROM
 KITCHEN COOKING APPLIANCES. W/ EXCEPTIONS FOR DISTANCES
 FROM COOKING APPLIANCES. (PHOTO-ELECTRIC AND RESETTING
 TYPE)
 ** PLEASE SEE PREVIOUS NOTES WITH RESPECT TO ARC FAULT
 PROTECTION OF SD'S AND CIRCUITING.
  
 29) NOTE: N/A PER THIS BUILDING REVIEW.
  
 30) NOTE: NO, AS CIRCUITING IS NOT YET COMPLETE FOR ALL
 COMMON AREAS THIS CAN NOT BE VERIFIED.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE 700.12E FOR CIRCUITING OF ALL EM/EXT LTS,
 WHICH REQUIRES THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT, SHALL BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED
 AHEAD OF ANY LOCAL SWITCHES.
 THIS IS NOTED ON SOME SHEETS, HOWEVER CIRCUITING FOR
 THESE IS NOT SHOWN.
 215.5
  
 31) NOTE: OK.
  
 32) NOTE:NO, PLEASE SE SOME UNITS ARE STILL MISSING
 GFI RECEPTS TO SERVE KITCHEN COUNTER SPACE AS
 REQUIRED.
 UNIT(S) A 1, A-2 ETC. PLEASE GO THROUGH ALL.
  
 **PREVIOUS REVIEW NOTE **
 PLEASE SEE 210.52C1-C5 FOR REQUIRED GFI RECEPTS ALONG
 KITCHEN COUNTER SPACE. PLEASE SEE SOME ARE SHOWN ON
 WHAT APPEARS TO BE A WALL ON THE OTHER SIDE OF THE
 COUNTER SPACE.
 PLEASE SEE B-2, B-4ETC.
 PLEASE SEE OTHER WHICH ARE REQUIRED TO BE WITHIN 2' OF
 THE END OF THE COUNTER SPACE/FROM SINK EDGE ETC. PLEASE
 SEE THESE AREAS REDLINED ON SHEETS.
  
 33) NOTE:NO, PLEASE SEE RESPONSE MENTIONS THIS IS FOR
 SECURITY AND IT IS NOT A PLUG-IN TYPE TRANSFORMER. IF
 THIS IS NOT A PLU-IN TYPE, PLEASE INDICATE ON PLANS
 WHAT TYPE IT IS AND/OR WILL BE. PLEASESUBMIT OR
 RELOCATE THE RECEPTACLES LOCATED ABOVE CLOTHES CLOSET
 SHELVING OR IN THE NEAR VICINITY AS PREVIOUSLY STATED
 THIS AHJ HAS SEEN TOO MANY INSTANCE WHERE FIRES HAVE
 STARTED BASED ON SOME TYPES OF THESE UNITS AND IN THE
 INTEREST OF LIFE SAFETY AND PROPERTY DAMAGE, THESE WILL
 NOT BE PERMITTED AS SHOWN IN SOME UNITS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE WHAT APPEARS TO BE A RECEPT LOCATED IN THE
 CLOTHES CLOSET FOR PERHAPS A LV PLUG-IN TYPE
 TRANSFORMER?
 PLEASE KNOW, THE ONLY LOCATION A RECEPT IS PERMITTED IN
 A CLOTHES CLOSET FOR THIS PURPOSE, MUST BE LOCATED
 DIRECTLY ABOVE DOOR AWAY FROM COMBUSTIBLES.
 MANY PLUG-IN TYPE TRANSFORMERS BECOME VERY HOT AND
 HAVE MELTED OR CAUSED FIRES IN THIS JURISDICTION.
 PLEASE KNOW, MANY ITEMS IN A CLOTHES CLOSET ARE AN
 ACCELERANT.
 THESE RECEPTS MAY BE MOVED TO UTILITY RM IF SO
 DESIRED.
 110.26, 240.24, 90.4 ETC
  
 34) NOTE: OK.
  
 35) NOTE: OK.
  
 ** NEW NOTES FOR THIS REVIEW **
  
 1) NOTE: PLEASE CORRELATE LAYOUT OF THE BUILDING FOR
 ALL ROOMS AND AREAS. PLEASE SEE THE ELECTRICAL PLANS DO
 NOT CORRELATE WITH THE ARCHITECTURAL SHEETS AND THE
 FIRE SPRINKLER SHEETS ALSO HAVE SOME AREAS WHICH DO NOT
 CORRELATE WITH EITHER. PLEASE SEE FOR INSTANCE THE FIRE
 PUMP ROOM LAYOUT.
  
 2) NOTE: PLEASE CORRELATE HOUSE PANEL DESIGNATION ON
 PLANS WITH THE ACTUAL HOUSE PANEL DESIGNATION ON PANEL
 SCHEDULE.
 408.4.
  
 3) NOTE: PLEASE SEE THE THRESHOLD INSPECTION PLANS
 SUBMITTED ALL CONTAIN A RAISED SEAL OVER A PHOTO-COPIED
 SIGNATURE FROM THE ENGINEER. PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA STATUTES
 471.025 AS AN ORIGINAL SIGNATURE IS REQUIRED. PLEASE
 KNOW THESE MAY BE RETAINED BY THIS OFFICE FOR POSSIBLE
 REVIEW FROM THEFLORIDA BOARD OF PROFESSIONAL
 ENGINEERS. IF THERE ARE ANY QUESTIONS ON THIS PLEASE
 CONTACTTHIS OFFICE ORTHE BOARD.
 **THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE.
  
 4) NOTE: PLEASE SEE NFPA-72 DEFINITIONS FOR SMOKE
 DEVICES. IF THESE ARE INDEED (SD) FOR SMOKE DETECTORS
 THEN THEY WOULD DETECT AND CAUSE AN ALARM TO HORN/SIREN
 DEVICE OF SOME TYPE. PLEASE SEE PLANS CALL FOR THESE AS
 120V UNITS, WHICH IF (SA) SMOKE ALARMS WHICH WOULD
 DETECT AND SOUND, THEN THE DESIGNATIONS NEED TO BE
 ADJUSTED ALONE WITH ALL NOTES WHICH CURRENTLY STATE
 SMOKE DETECTORS. PLEASE KNOW THIS WAS NOT A COMMENT ON
 THE PREVIOUS REVIEW, HOWEVER AS INFORMATION WAS GIVEN
 FROM NFPA DIRECTLY, PLANS MUST CONTAIN THE CORRECT
 DESIGNATIONS.
  
 5) NOTE: PLEASE SEE THE BASE FA SYSTEM SHALL BE SHOWN
 AND ALL HORN/STROBE DEVICES SHALL STATE THE MINIMUM
 LEVELS AS REQUIRED PER FBC 11-4.28.1, .2, AND .3(4).
 THIS WAS NOT PART OF THE ELECTRICAL REVIEWERS REVIEW
 WHEN PLANS WERE SUBMITTED PREVIOUSLY HOWEVER THIS HAS
 NOW BECOME PART OF THE ELECTRICAL REVIEWERS REVIEW.
 PLEASE SHOW.
  
 6) NOTE: PLEASE CLARIFY STAIRS SHOWN ON SOME UNITS.
 PLEASE SEE MISSING WHAT WOULD BE EGRESS LIGHTING AND
 CONTROLS IF INSIDE UNIT AND/OR OUTSIDE UNIT. PLEASE SEE
 NEC 210.70, LS 101 7.8, (7.9 WHERE APPLICABLE).
  
 7) NOTE: PLEASE SEE SEVERAL HOUSE CIRCUITS AS NOTED
 ABOVE WITH RESPECT TO CORRELATION OF CIRCUITING SEEM TO
 BE INDICATE ON THESE PLANS TO PANELS WHICH WOULD BE ON
 OTHER BUILDINGS? PLEASE SEE MISSING TRASH COMPACTOR AS
 ONE ITEM ALONE.
 240.4, 310.16, 408.4, ETC
  
 8) NOTE: PLEASE SEE NOTES ABOVE ON PREVIOUS REVIEW AND
 SECOND REVIEW NOTES WITH RESPECT TO ROOM/AREA
 DESIGNATIONS. PLEASE SEE 210.52B1, 210.11C1 AND 220.16
 FOR DINING ROOMS, DINING AREAS, BREAKFAST AREAS,
 KITCHEN AREAS AND THE LIKE. PLEASE SEE THAT SOME
 RECEPTS ARE BEING SHOWN IN AREAS WHICH WOULD APPEAR TO
 BE AREAS OF THE LIKE AS REFERENCED ABOVE, HOWEVER SOME
 OF THESE RECEPTS ARE BEING SHOWN ON LIGHTING CIRCUITS
 OF 15A'S ETC.
 PLEASE ADJUST PLANS FOR PREVIOUS NOTE AND THIS NOTE.
  
 9) NOTE: PLEASE SEE SHEET FOR ELECTRICAL FOR 3RD AND
 4TH FLOORS WHICH ARE SHEETS LABELED AS AP P16.06 FOR
 PLUMBING. PLEASE CORRECT FBC 104.2.1.2
  
 10) NOTE: PLEASE PROVIDE NOTE ON FIRST FLOOR MAIN
 ELECTRICAL ROOM PLANS WHICH WILL REQUIRE DOOR TO
 CONTAIN PANIC HARDWARE.
 110.26/90.4
  
 11) NOTE: PLEASE SEE THE VOLTAGE DROP FOR 30A CU'S, AT
 THIS TIME CAN NOT BE VERIFIED. PLEASE SEE SOME UNITS
 INDICATE #10 ALREADY YET THESE WILL BE OVER 75FT AND
 THERE IS NO NOTE FOR THESE UNITS TO UPGRADE TO #8 OR ?
 PLEASE ADJUST AND PROVIDE ADDITIONAL INFORMATION. FBC
 104.2.1.2, NEC 310.16, 240.4 ETC.
  
 12) NOTE: PLEASE SEE NOTES ABOVE WHICH REQUESTS FOR THE
 RISER NOTES TO CORRELATE WITH THE DESIGNATIONS ON
 RISER. PLEASE SEE NOTE #1.
 104.2.1.2 FBC ADMIN SECTION.
  
 13) NOTE: PLEASE PROVIDE A DETAIL FOR THE ROOF TOP
 DISCONNECT AS BEING NOTED AND HOW THIS WILL BE MOUNTED?
 (NOT TO UNIT)
 440.11. THIS CAN BE A TYPICAL DETAIL.
  
 14) NOTE: PLEASE SEE ATTACHED COPY OF FLORIDA STATUTES
 553.80(2)(B) WITH RESPECT TO REPEAT CODE COMPLIANCE
 COMMENTS. THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
  
 15) NOTE: PLEASE SEE MISSING FIRST FLOORELECTRICAL
 FOR UNITS WITH STAIRS. 210.70,210.52 ETC
  
 *** PLEASE KNOW THAT THERE MAY BE NEW COMMENTS ON THE
 NEXT REVIEW DUE TO INFORMATION NOT SUBMITTED OR
 COORDINATION OF PLANS/INFORMATION SUBMITTED FOR REVIEW
  
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY HAVE AN AFFECT ON ELECTRICAL PLANS.
  
 ** PLEASE KNOW, A TYPE WRITTEN RESPONSE LETTER FROM
 DESIGN PROFESSIONAL(S) FOR EACH COMMENT ON HOW/WHERE
 CORRECTIONS ARE MADE OR IF COMMENTS ON REVIEW WILL HELP
 IN EXPEDITING THE PLAN REVIEW PROCESS. THIS WAS DONE,
 AND SHOULD BE DONE FOR THIS REVIEW AS WELL.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]