| Date |
Text |
| 2006-12-31 19:44:43 | **** UNSAT2ND REVIEW ******** |
| | |
| | COURTNEY LAKES BUILDING #3 |
| | N. CONGRESS. |
| | |
| | ** PLEASE SEE MANY OF THE SAME COMMENTS FROM THE |
| | PREVIOUS REVIEW STILL NEED TO BE ADDRESSED. |
| | |
| | ** PLEASE SEE AS THREE SEPARATE BUILDING PERMITS AND |
| | PLANS ARE NOW SEPARATED FOR EACH, PLEASE ALSO SEE NEW |
| | COMMENTS BASED ONE THE PLANS NOW SUBMITTED INTO EACH |
| | SET. |
| | |
| | ** PLEASE ALSO SEE THERE ARE SOME NEW NOTES BASED ON |
| | PLANS SUBMITTED. |
| | |
| | ** PLEASE SEE BELOW ARE SOME OF THE NOTES FROM THE |
| | PREVIOUS REVIEW ARE BEING NOTED IF ADDRESSED OR NOT BY |
| | A "NO, OK, NO/OK, N/A OR SEE NEW ". |
| | 1) NO WILL HAVE FURTHER EXPLANATION IN AN ATTEMPT TO |
| | BETTER EXPLAIN COMMENT MADE. |
| | 2) OK, WILL HAVE PREVIOUS NOTE REMOVED. |
| | 3) NO/OK, MEANS PART OF THE COMMENT MAY HAVE BEEN |
| | ADDRESSED, HOWEVER NOT ALL. THIS WILL ALSO BE FOLLOWED |
| | BY FURTHER EXPLANATION OF PREVIOUS NOTE. |
| | 4) N/A, THIS MEANS THE COMMENT NO LONGER APPLIES TO |
| | THIS BUILDING AND PREVIOUS NOTE IS REMOVED. |
| | |
| | ** PLEASE SEE ALL NEW NOTES WILL BE NOTED AT THE END OF |
| | PREVIOUS REVIEW COMMENTS AND WILL BE INDICATED WITH |
| | **** NEW NOTES**. |
| | |
| | |
| | 1) NOTE: OK. SEE NOTES. |
| | |
| | 2) NOTE: OK |
| | |
| | 3) NOTE:NO, PLEASE SEE RESPONSE MENTIONS PLANS |
| | DESIGNED UNDER THE CODES AS NOTED, HOWEVER ALL CODES |
| | RELEVANT TO THE DESIGN IN WHICH THE BUILDING IS |
| | PERMITTED UNDER SHALL BE STATED ON PLANS. PLEASE SEE |
| | THIS IS REQUIRED OF ARCHITECTURAL SHEETS AS WELL AS |
| | ELECTRICAL AND FIRE. PLEASE SEE ANY OTHER NOTES WITH |
| | RESPECT TO THIS FROM OTHER TRADES. |
| | THE FOLLOWING SHALL BE STATED. 2002 NEC/NFPA-70, 2002 |
| | NFPA-72, 2003 NFPA-20 AND 2003 NFPA-101. (THE CORRECT |
| | NFPA-101 IS NOTED ) |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE BE SURE TO CORRECT THE CURRENT NEC/ NFPA-70 IN |
| | EFFECT. |
| | PLEASE KNOW, AS OF JULY 1ST, 2003 THE STATE OF FLORIDA |
| | ADOPTED THE 2002 |
| | NFPA-70 (NEC). PLANS REFERENCE 1999. PLEASE SEE SOME |
| | ELECTRICAL COMMENTS WHICH WILL AFFECT THIS. |
| | PLEASE SEE NEXT COMMENT WITH RESPECT TO PERMITS APPLIED |
| | FOR UNDER THE 2001 FBC BEFORE OCT 1ST, 2005 AND PERMITS |
| | ON OCT 1ST, 2005. |
| | |
| | 4) NOTE: N/A, SEE NEW NOTES FOR EACH BUILDING. |
| | |
| | |
| | 5) NOTE: N/A, SEE NEW NOTES UNDER EACH BUILDING. |
| | |
| | 6) NOTE:NO, PLEASE SEE THERE ARE SEVERAL AREAS WHICH |
| | CIRCUITING IS NOT COMPLETE INCLUDING UNITS FOR SMOKE |
| | DEVICES AND MANY AREAS OF HOUSE/COMMON AREAS/ SITE ETC. |
| | PLEASE SEE MANY NEW COMMENTS BASED ON PLANS SUBMITTED. |
| | PLEASE SHOW ALL AND CORRELATE WITH THE SUBMITTED PANEL |
| | SCHEDULES. SEE NEW NOTES. |
| | FBC ADMIN SECTION 104.1.2 |
| | |
| | PLEASE COMPLETE ALL CIRCUITING ON PLANS IN ORDER TO |
| | REVIEW CODE COMPLIANCE FOR AREAS OF UNITS AND COMMON |
| | AREAS. |
| | |
| | 7) NOTE: NO, SAME COMMENT. THIS IS NOT EXPLAINED ANY |
| | FURTHER. PLEASE HOWEVER ALSO SEE NEW COMMENTS BASED ON |
| | PLANS SUBMITTED. |
| | ** PLEASE KNOW THERE ARE AREAS OF PLANS WITH |
| | DESIGNATIONS, ITEMS FOR CODE COMPLIANCE FOR CIRCUITING |
| | TO THOSE AREAS CAN NOT BE VERIFIED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE ROOM AND AREA DESIGNATIONS ON PLANS, |
| | INCLUSIVE OF ALL UNITS AND COMMON AREAS. |
| | REVIEW FOR SOME CODE COMPLIANCE ITEMS CAN NOT BE DONE |
| | AT THIS TIME. |
| | |
| | 8) NOTE:NO, PLEASE SEE RESPONSE LETTER MENTIONS TO |
| | SEE SHEET AP E16.00A, YET PLEASE KNOW COMPLETED |
| | PHOTO-METRICS SHALL BE SUBMITTED IN EACH SUBMITTED |
| | PLANS FOR EACH BUILDING AS EACH BUILDING IS ITS OWN |
| | LEGAL RECORD. |
| | PLEASE ALSO SEE PREVIOUS NOTES, PLEASE SEE ONLY PARTIAL |
| | PHOTO-METRICS WERE SUBMITTED. PLEASE SEE NOTE WHICH |
| | REQUIRES ALL UNDER NORMAL AND EMERGENCY AND FOR ALL |
| | EGRESS AREAS. PLEASE SEE ONLY SOME ARE BEING SHOWN IN |
| | THE PLANS UNDER BUILDING ONE. PLEASE KNOW THESE CAN BE |
| | TYPICAL, HOWEVER THEY SHALL ALSO BE SPECIFIC TO EACH |
| | AREA IF THE LAYOUT OF THESE AREAS CHANGES WHICH THEY |
| | DO. NOT ALL AREAS ARE THE LIKE. |
| | PLEASE SEE NEW NOTES ALSO FOR EGRESS FROM UNITS AND |
| | PLEASE SEE NEW NOTES PERTAINING TO PARKING LOT, AND |
| | SITE LIGHTING. |
| | PLEASE KNOW AS THE SWIMMING POOL IS NOT UNDER THIS |
| | PERMIT FOR THE BUILDING, STAMPED PLANS FROM PALM BEACH |
| | COUNTY HEALTH DEPT IS NOT REQUIRED AT THIS TIME UNDER |
| | THIS PERMIT. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE COMPLETE PHOTO-METRICS FOR ALL COMMON |
| | AREAS, GARAGE AREA, COMMON AREA CORRIDORS, STAIR TOWERS |
| | ETC. |
| | PLEASE SEE 2003 NFPA-101 7.8.1.3 AND 7.9.2.2 WHICH |
| | REQUIRE A MIN OF 10FT CANDLES FOR STAIR TOWERS UNDER |
| | NORMAL OPERATION AS WALK SURFACE AND A MIN OF 1FT |
| | CANDLE AT WALK SURFACE UNDER EMERGENCY CONDITIONS. |
| | PLEASE ALSO SEE OTHER WALK AREAS, GARAGE, CORRIDORS ETC |
| | AND THE MIN OF 1FT CANDLE. |
| | **PLEASE SEE PALM BEACH COUNTY SECURITY CODE ORDINANCE |
| | WITH RESPECT TO MIN DESIGN OF PARKING LOT LIGHTING |
| | LEVELS UNDER NORMAL CONDITIONS. (ONLY NOTED FOR DESIGN) |
| | NOT REQUIRED. PLEASE SEE ANY REQUIREMENTS FROM INS |
| | CARRIER WHICH REQUIRES A MIN LEVEL OF LIGHTING. |
| | ** PLEASE SEE PHOTO-METRICS OR SITE PLAN WAS NOT |
| | SUBMITTED FOR PROPOSED POOL AREA. THE POOL STRUCTURE IS |
| | REQUIRED TO BE UNDER A SEPARATE PERMIT. PLEASE KNOW, |
| | THE PHOTO-METRICS FOR POOL AREA WILL BE REQUIRED AND |
| | WILL ALSO BE REQUIRED TO BE REVIEWED AND STAMPED BY THE |
| | PALM BEACH COUNTY HEALTH DEPT FOR ANY PROPOSED |
| | NIGHT-TIME SWIMMING. |
| | |
| | 7) NOTE: NO, PLEASE SEE EACH SET OF PLANS SHALL CONTAIN |
| | A SITE LIGHTING PLAN SHOWING ALL CIRCUITING AND |
| | CORRELATE WITH EACH OF THE HOUSE PANELS FOR EACH |
| | BUILDING IN WHICH THEY ARE BEING CIRCUITED TO. PLEASE |
| | SEE ALL SITE LIGHTING AS SHOWN IN THE SET OF PLANS FOR |
| | BUILDING ONE. PLEASE SEE THE CIRCUITING AS SHOWN DOES |
| | NOT CORRELATE WITH HOUSE PANEL FOR BUILDING THREE IN |
| | ANY WAY. PLEASE SEE HOUSE PANEL FOR THESE CIRCUITS ARE |
| | IN FACT BLANK AND SHOWS THE WORDING OF "SPACE". PLEASE |
| | KNOW AT THIS TIME THERE ARE MANY ITEMS PERTAINING TO |
| | SITE LIGHTING WHICH CAN NOT BE VERIFIED FOR VOLTAGE |
| | DROP, CIRCUITS, OVER CURRENT PROTECTION, CONDUCTOR |
| | SIZES ETC. |
| | PLEASE SEE NO INFORMATION WAS SUBMITTED OR SHOWN FOR |
| | WIND LOADS ON POLES. |
| | 240.4, 310.16, 408.4, FBC 104.2.1,104.21.2 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE NO "ELECTRICAL SITE-PLAN" WAS SUBMITTED FOR |
| | ANY SITE LIGHTING, LANDSCAPE LIGHTING ETC. |
| | PLEASE KNOW, IF NOT SUBMITTED UNDER THIS PERMIT AND |
| | VALUES ADJUSTED ACCORDINGLY, SEPARATE PERMIT , PLANS |
| | AND FEES WILL BE REQUIRED FOR ALL SITE LIGHTING, |
| | LANDSCAPE LIGHTING WORK. |
| | ** ALSO NOTE: IN THAT COMPLETE WIND LOADING |
| | CALCULATIONS FOR LT POLES INCLUSIVE OF THE ATTACHMENT |
| | OF LT FIXTURES WILL BE REQUIRED TO BE SUBMITTED WITH |
| | PLANS AND PERMIT APPLICATION FOR REVIEW. |
| | |
| | 8) NOTE: NO, PLEASE SEE ONCE AGAIN NOT ALL ROOMS ARE |
| | DONE AS REQUIRED. PLEASE SEE MAIN ELECTRICAL ROOM FOR |
| | THIS BUILDING ALONE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INCLUDE AN EMERGENCY BATTERY BACK UP LT OF SOME |
| | SORT IN ALL ELECTRICAL ROOMS, FIRE PUMP ROOM, AND |
| | ELEVATOR MACHINE RMS. SOME ARE SHOWN, BUT NOT ALL. |
| | 7.8,7.9, 700.16 ETC |
| | |
| | 9) NOTE:NO, PLEASE SEE NOT ONLY ARE MANY CIRCUITS NOT |
| | SHOWN ON PLANS NO CHANGES FOR THE REQUIRED DEDICATED |
| | CIRCUITS HAVE BEEN MADE. PLEASE SEE PLANS AND CORRELATE |
| | WITH THE HOUSE PANEL FOR THIS BUILDING. |
| | PLEASE SEE 620.22,23,24 AND 620.51 ETC |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 620.23, AND 620.24 FOR REQUIRED DEDICATED |
| | BRANCH CIRCUITS FOR ELEVATOR PITS, AND ELEVATOR MACHINE |
| | RMS/EQUIPMENT AREAS. |
| | PLEASE ADJUST HOUSE PANELS AS NEEDED. |
| | |
| | 10) NOTE: NO, PLEASE SEE NO INFORMATION WAS LOCATED ON |
| | RISER SHEETS. PLEASE SEE NO INFORMATION WAS SHOWN ON FP |
| | FOR THE FIRE PUMP, SIZE, FUEL CONSUMPTION, TIME OF |
| | OPERATION UNDER THE AMOUNT OF FUEL ETC. PLEASE SEE THE |
| | SPECS/CUT SHEETS SUBMITTED CONTAIN MULTIPLE UNITS AND |
| | NO REVIEW FOR CODE COMPLIANCE OF THE UNIT FOR EACH |
| | BUILDING BASED ON THE NUMEROUS PUMPS SUBMITTED. PLEASE |
| | ALSO SEE MISSING FIRE PUMP CONTROLLER SPECS. PLEASE |
| | ALSO SEE MISSING THE RELEVANT CODES ON FP SHEETS. |
| | PLEASE KNOW BASED ON THE PLANS SUBMITTED AND SPEC/CUT |
| | SHEETS SUBMITTED, REVIEW FOR COMPLIANCE CAN NOT BE DONE |
| | AT THIS TIME. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE ELECTRICAL RISER SHOULD "NOTE" FIRE PUMP |
| | AS DIESEL AS NOTED ON FP SHEETS. |
| | PLEASE SUBMIT ALL MANUFACTURES SPEC/CUT SHEETS FOR FIRE |
| | PUMP CONTROLLER AS REVIEW FOR CODE COMPLIANCE UNDER |
| | 2003 NFPA-20 IS REQUIRED. |
| | PLEASE ALSO SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS |
| | FOR FUEL TANK. |
| | PLEASE SEE NFPA-20 9.6.2.2 AS THE FUEL CAPACITY IS |
| | REQUIRED TO BE SIZED BASE ON THE 100% RATED LOAD FOR A |
| | MIN OF 8HRS, OR TIME SO DETERMINED BY THE FIRE |
| | MARSHAL'S OFFICE DEPENDING ON OCCUPANCY. |
| | FUEL SYSTEMS WILL BE UNDER OTHER TRADE REVIEW(S). (FIRE |
| | AND MECH). |
| | |
| | 11) NOTE: NO, RESPONSE MENTIONS THIS WAS DONE, HOWEVER |
| | PLEASE SEE UNIT PANEL SCHEDULES AND HOUSE PANEL |
| | SCHEDULE DOES NOT CONTAIN AND CONDUCTOR SIZES. PLEASE |
| | KNOW BASED ON COMMENTS ABOVE WITH RESPECT TO AREA |
| | DESIGNATIONS, CIRCUITING MISSING ON PLANS, REVIEW OF |
| | THIS CAN NOT BE DONE AT THIS TIME.408.4 , FBC 104.1.2 |
| | ADMINSECTION. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INCLUDE ALL MINIMUM CONDUCTOR SIZES ON ALL |
| | PANELS, UNITS AND HOUSE PANELS. REVIEW FOR THESE ITEMS |
| | OF CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME. |
| | 310.16, 240.4,215.5 |
| | |
| | 12) NOTE:NO, AS CIRCUITING FOR THIS BUILDING IS NOT |
| | COMPLETE AT THIS TIME, THE OVER CURRENT PROTECTIVE |
| | DEVICES CAN NOT BE VERIFIED AT THIS TIME. THIS COMMENT |
| | WAS MAINLY FOR THE OCP DEVICES WHICH WERE BEING SHOWN |
| | ON BUILDING #1'S PLANS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE GARAGE/HOUSE LIGHTING BEING INDICATED ON 30A |
| | AND 50A CIRCUITS. |
| | PLEASE SEE CODE DOES LIMIT THE OCP FOR UNIT FIXTURES |
| | FOR PROTECTION OF FIXTURES ON A BRANCH CIRCUIT. PLEASE |
| | ADJUST CIRCUITING AS NEEDED. |
| | PLEASE ALSO SEE A FIXTURE SCHEDULE CONTAINING WATTAGES, |
| | VOLTAGES ETC WAS NOT SUBMITTED. |
| | PLEASE VERIFY IF THESE UNIT FIXTURES ARE RATED TO HAVE |
| | OCP AT ABOVE MENTIONED. |
| | 240.4, 310.16 ETC |
| | |
| | 13) NOTE: OK, HOWEVER SEE NOTES. |
| | |
| | 14) NOTE:NO/OK, PLEASE SEE PART OF THIS COMMENT SEEMS |
| | TO HAVE BEEN ADDRESSED, HOWEVER PLEASE SEE NOTES ON |
| | RISER AND RISER NOTES WHICH STILL DO NOT CORRELATE. |
| | PLEASE SEE SEVERAL NOTE #1'S, YET ON RISER NOTES NOT |
| | ALL OF THESE NOTE #1'S CAN POSSIBLY APPLY. PLEASE |
| | ADJUST ALL NOTE SON RISER AND NOTES NOTED AS RISER |
| | NOTES. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | , PLEASE SEE PLEASE SEE MAX OCP TO BE SIZED FOR |
| | PANELS/EQUIPMENT BEING FED BY SAID OCP. |
| | PLEASE SEE MANY UNIT PANELS ARE SHOWN AS 100A MLO, WITH |
| | 125A OCP AS LISTED ON RISER ETC. |
| | PLEASE ALSO SEE RISER NOTE #4 WHICH INDICATES 125A |
| | 2-POLE ETC, HOWEVER PLEASE SEE RISER AS THIS NOTE #4 |
| | COULD NOT BE LOCATED. (APPEARS TO BE MISPRINTED FOR |
| | "NOTE#7" ON RISER) 240.4,408,310.16,215.5 ETC. |
| | |
| | 15) NOTE: N/A, NOT PART OF THESE PLANS FOR THIS |
| | BUILDING. SEE NEW NOTES. |
| | |
| | 16) NOTE: N/A, NOT PART OF THESE PLANS FOR THIS |
| | BUILDING. SEE NEW NOTES. |
| | |
| | 17) NOTE: N/A, NOT PART OF THESE PLANS FOR THIS |
| | BUILDING. SEE NEW NOTES. |
| | |
| | 18) NOTE: NO/OK, SOME SHEETS SHOW NOTE, HOWEVER NOT ALL |
| | FOR UNITS. CIRCUITING IS NOT YET COMPLETE TO REVIEW |
| | THESE FOR CODE COMPLIANCE. PLEASE LABEL ALL CIRCUITS ON |
| | PANEL SCHEDULE WHICH CONTAIN AFCI PROTECTION. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THESE SHEETS ALSO REFERENCE "ARC FAULT" |
| | PROTECTION FROM THE 1999 NEC, WHICH ONLY REQUIRED |
| | PROTECTION OF RECEPTS. |
| | PLEASE SEE THE 2002 NEC WHICH REQUIRES PROTECTION FOR |
| | ALL "OUTLETS" IN BEDRMS. THIS IS INCLUSIVE OF RECEPTS, |
| | LTS, FANS, SMOKE DETECTORS ETC. PLEASE SEE NOTE ON UNIT |
| | PLANS AND ADJUST. |
| | |
| | 19) NOTE:THIS IS UNCLEAR AT THIS TIME, AS PERMIT |
| | APPLICATION FOR BUILDING #3 INDICATES 450 UNITS, YET |
| | METER CALCULATIONS CONTAINS NOTE OF 40 METERS FOR EACH |
| | METER CENTER. PLEASE CORRELATE PLANS, PERMIT |
| | APPLICATIONS AND ADJUST PLANS AS NEEDED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CORRELATE LOADS, UNITS, PANELS, AND |
| | BUILDING/METER LOAD CALCULATIONS: |
| | A) PLEASE SEE PANEL SCHEDULE/LOAD CALCULATIONS FOR UNIT |
| | "B-3" SHOWN ON |
| | 16.26, HOWEVER THIS UNIT TYPE OR LOADS COULD NOT BE |
| | LOCATED ON BLDG LOAD CALCULATIONS ON 16.25? |
| | B) PLEASE ALSO SEE THE SAME COMMENT ABOVE FOR UNIT |
| | "C-2" WHICH IS ALSO SHOWN ON |
| | 16.26 BUT NOT IN CALCS ON 16.25?? |
| | ** PLEASE ADJUST ALL AS NEEDED. |
| | |
| | 20) NOTE: OK, HOWEVER STILL NOT ADDED TO RISER, ONLY |
| | SHOWN IN GROUNDING DETAIL. PLEASE EXPLAIN RATIONAL OF |
| | TWO GROUNDING ELECTRODE SYSTEMS SHOWN? |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INCLUDE THE REQUIRED FOOTER STEEL ON THE |
| | GROUNDING ELECTRODE RISER DETAIL. PLEASE ALSO SHOW ON |
| | RISER. |
| | 250.50. |
| | |
| | 21) NOTE: NO, PREVIOUS NOTE REQUESTED A NOTE/DETAIL |
| | WHICH WOULD ACTUALLY PROVIDE A LITTLE MORE INFORMATION |
| | FOR THIS REQUIREMENT. PLEASE EXPAND ON NOTE. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE PROVIDE A DETAIL/NOTE FOR ALL RACEWAY SEALS AS |
| | REQUIRED PER |
| | 230.8 |
| | |
| | 22) NOTE: N/A. |
| | |
| | 23) NOTE: N/A. |
| | |
| | 24) NOTE: N/A |
| | |
| | 25) NOTE: OK. |
| | |
| | 26) NOTE: OK. |
| | |
| | 27) NOTE: OK. |
| | |
| | 28) NOTE: NO, PLEASE SEE THE 2001 FBC 905.2 WHICH DOES |
| | NOT MENTION THE EXCEPTION AS PERMITTED BY NFPA-72. THE |
| | MORE RESTRICTIVE SHALL APPLY. PLEASE SEE NEW NOTES FOR |
| | THESE DEVICES AND CIRCUITING. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | SMOKE DETECTORS ARE REQUIRED INSIDE AND OUTSIDE ALL |
| | SLEEPING ROOMS. |
| | PLEASE SEE 2002 NFPA-72 11.5.3.1 |
| | PLEASE ADJUST NOTE FOR SD'S ON PLANS AS |
| | SD'S ARE REQUIRED 3' FROM BATH/KITCHEN DOORS, 3' FROM |
| | SUPPLY AIR DIFFUSERS, 5' FROM R/A GRILLES AND 20' FROM |
| | KITCHEN COOKING APPLIANCES. W/ EXCEPTIONS FOR DISTANCES |
| | FROM COOKING APPLIANCES. (PHOTO-ELECTRIC AND RESETTING |
| | TYPE) |
| | ** PLEASE SEE PREVIOUS NOTES WITH RESPECT TO ARC FAULT |
| | PROTECTION OF SD'S AND CIRCUITING. |
| | |
| | 29) NOTE: N/A PER THIS BUILDING REVIEW. |
| | |
| | 30) NOTE: NO, AS CIRCUITING IS NOT YET COMPLETE FOR ALL |
| | COMMON AREAS THIS CAN NOT BE VERIFIED. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SEE 700.12E FOR CIRCUITING OF ALL EM/EXT LTS, |
| | WHICH REQUIRES THE BRANCH CIRCUIT FEEDING THE UNIT |
| | EQUIPMENT, SHALL BE THE SAME BRANCH CIRCUIT AS THAT |
| | SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED |
| | AHEAD OF ANY LOCAL SWITCHES. |
| | THIS IS NOTED ON SOME SHEETS, HOWEVER CIRCUITING FOR |
| | THESE IS NOT SHOWN. |
| | 215.5 |
| | |
| | 31) NOTE: OK. |
| | |
| | 32) NOTE:NO, PLEASE SE SOME UNITS ARE STILL MISSING |
| | GFI RECEPTS TO SERVE KITCHEN COUNTER SPACE AS |
| | REQUIRED. |
| | UNIT(S) A 1, A-2 ETC. PLEASE GO THROUGH ALL. |
| | |
| | **PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 210.52C1-C5 FOR REQUIRED GFI RECEPTS ALONG |
| | KITCHEN COUNTER SPACE. PLEASE SEE SOME ARE SHOWN ON |
| | WHAT APPEARS TO BE A WALL ON THE OTHER SIDE OF THE |
| | COUNTER SPACE. |
| | PLEASE SEE B-2, B-4ETC. |
| | PLEASE SEE OTHER WHICH ARE REQUIRED TO BE WITHIN 2' OF |
| | THE END OF THE COUNTER SPACE/FROM SINK EDGE ETC. PLEASE |
| | SEE THESE AREAS REDLINED ON SHEETS. |
| | |
| | 33) NOTE:NO, PLEASE SEE RESPONSE MENTIONS THIS IS FOR |
| | SECURITY AND IT IS NOT A PLUG-IN TYPE TRANSFORMER. IF |
| | THIS IS NOT A PLU-IN TYPE, PLEASE INDICATE ON PLANS |
| | WHAT TYPE IT IS AND/OR WILL BE. PLEASESUBMIT OR |
| | RELOCATE THE RECEPTACLES LOCATED ABOVE CLOTHES CLOSET |
| | SHELVING OR IN THE NEAR VICINITY AS PREVIOUSLY STATED |
| | THIS AHJ HAS SEEN TOO MANY INSTANCE WHERE FIRES HAVE |
| | STARTED BASED ON SOME TYPES OF THESE UNITS AND IN THE |
| | INTEREST OF LIFE SAFETY AND PROPERTY DAMAGE, THESE WILL |
| | NOT BE PERMITTED AS SHOWN IN SOME UNITS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE WHAT APPEARS TO BE A RECEPT LOCATED IN THE |
| | CLOTHES CLOSET FOR PERHAPS A LV PLUG-IN TYPE |
| | TRANSFORMER? |
| | PLEASE KNOW, THE ONLY LOCATION A RECEPT IS PERMITTED IN |
| | A CLOTHES CLOSET FOR THIS PURPOSE, MUST BE LOCATED |
| | DIRECTLY ABOVE DOOR AWAY FROM COMBUSTIBLES. |
| | MANY PLUG-IN TYPE TRANSFORMERS BECOME VERY HOT AND |
| | HAVE MELTED OR CAUSED FIRES IN THIS JURISDICTION. |
| | PLEASE KNOW, MANY ITEMS IN A CLOTHES CLOSET ARE AN |
| | ACCELERANT. |
| | THESE RECEPTS MAY BE MOVED TO UTILITY RM IF SO |
| | DESIRED. |
| | 110.26, 240.24, 90.4 ETC |
| | |
| | 34) NOTE: OK. |
| | |
| | 35) NOTE: OK. |
| | |
| | ** NEW NOTES FOR THIS REVIEW ** |
| | |
| | 1) NOTE: PLEASE CORRELATE LAYOUT OF THE BUILDING FOR |
| | ALL ROOMS AND AREAS. PLEASE SEE THE ELECTRICAL PLANS DO |
| | NOT CORRELATE WITH THE ARCHITECTURAL SHEETS AND THE |
| | FIRE SPRINKLER SHEETS ALSO HAVE SOME AREAS WHICH DO NOT |
| | CORRELATE WITH EITHER. PLEASE SEE FOR INSTANCE THE FIRE |
| | PUMP ROOM LAYOUT. |
| | |
| | 2) NOTE: PLEASE CORRELATE HOUSE PANEL DESIGNATION ON |
| | PLANS WITH THE ACTUAL HOUSE PANEL DESIGNATION ON PANEL |
| | SCHEDULE. |
| | 408.4. |
| | |
| | 3) NOTE: PLEASE SEE THE THRESHOLD INSPECTION PLANS |
| | SUBMITTED ALL CONTAIN A RAISED SEAL OVER A PHOTO-COPIED |
| | SIGNATURE FROM THE ENGINEER. PLEASE SEE FLORIDA |
| | ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA STATUTES |
| | 471.025 AS AN ORIGINAL SIGNATURE IS REQUIRED. PLEASE |
| | KNOW THESE MAY BE RETAINED BY THIS OFFICE FOR POSSIBLE |
| | REVIEW FROM THEFLORIDA BOARD OF PROFESSIONAL |
| | ENGINEERS. IF THERE ARE ANY QUESTIONS ON THIS PLEASE |
| | CONTACTTHIS OFFICE ORTHE BOARD. |
| | **THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | ANY OTHER TRADE. |
| | |
| | 4) NOTE: PLEASE SEE NFPA-72 DEFINITIONS FOR SMOKE |
| | DEVICES. IF THESE ARE INDEED (SD) FOR SMOKE DETECTORS |
| | THEN THEY WOULD DETECT AND CAUSE AN ALARM TO HORN/SIREN |
| | DEVICE OF SOME TYPE. PLEASE SEE PLANS CALL FOR THESE AS |
| | 120V UNITS, WHICH IF (SA) SMOKE ALARMS WHICH WOULD |
| | DETECT AND SOUND, THEN THE DESIGNATIONS NEED TO BE |
| | ADJUSTED ALONE WITH ALL NOTES WHICH CURRENTLY STATE |
| | SMOKE DETECTORS. PLEASE KNOW THIS WAS NOT A COMMENT ON |
| | THE PREVIOUS REVIEW, HOWEVER AS INFORMATION WAS GIVEN |
| | FROM NFPA DIRECTLY, PLANS MUST CONTAIN THE CORRECT |
| | DESIGNATIONS. |
| | |
| | 5) NOTE: PLEASE SEE THE BASE FA SYSTEM SHALL BE SHOWN |
| | AND ALL HORN/STROBE DEVICES SHALL STATE THE MINIMUM |
| | LEVELS AS REQUIRED PER FBC 11-4.28.1, .2, AND .3(4). |
| | THIS WAS NOT PART OF THE ELECTRICAL REVIEWERS REVIEW |
| | WHEN PLANS WERE SUBMITTED PREVIOUSLY HOWEVER THIS HAS |
| | NOW BECOME PART OF THE ELECTRICAL REVIEWERS REVIEW. |
| | PLEASE SHOW. |
| | |
| | 6) NOTE: PLEASE CLARIFY STAIRS SHOWN ON SOME UNITS. |
| | PLEASE SEE MISSING WHAT WOULD BE EGRESS LIGHTING AND |
| | CONTROLS IF INSIDE UNIT AND/OR OUTSIDE UNIT. PLEASE SEE |
| | NEC 210.70, LS 101 7.8, (7.9 WHERE APPLICABLE). |
| | |
| | 7) NOTE: PLEASE SEE SEVERAL HOUSE CIRCUITS AS NOTED |
| | ABOVE WITH RESPECT TO CORRELATION OF CIRCUITING SEEM TO |
| | BE INDICATE ON THESE PLANS TO PANELS WHICH WOULD BE ON |
| | OTHER BUILDINGS? PLEASE SEE MISSING TRASH COMPACTOR AS |
| | ONE ITEM ALONE. |
| | 240.4, 310.16, 408.4, ETC |
| | |
| | 8) NOTE: PLEASE SEE NOTES ABOVE ON PREVIOUS REVIEW AND |
| | SECOND REVIEW NOTES WITH RESPECT TO ROOM/AREA |
| | DESIGNATIONS. PLEASE SEE 210.52B1, 210.11C1 AND 220.16 |
| | FOR DINING ROOMS, DINING AREAS, BREAKFAST AREAS, |
| | KITCHEN AREAS AND THE LIKE. PLEASE SEE THAT SOME |
| | RECEPTS ARE BEING SHOWN IN AREAS WHICH WOULD APPEAR TO |
| | BE AREAS OF THE LIKE AS REFERENCED ABOVE, HOWEVER SOME |
| | OF THESE RECEPTS ARE BEING SHOWN ON LIGHTING CIRCUITS |
| | OF 15A'S ETC. |
| | PLEASE ADJUST PLANS FOR PREVIOUS NOTE AND THIS NOTE. |
| | |
| | 9) NOTE: PLEASE SEE SHEET FOR ELECTRICAL FOR 3RD AND |
| | 4TH FLOORS WHICH ARE SHEETS LABELED AS AP P16.06 FOR |
| | PLUMBING. PLEASE CORRECT FBC 104.2.1.2 |
| | |
| | 10) NOTE: PLEASE PROVIDE NOTE ON FIRST FLOOR MAIN |
| | ELECTRICAL ROOM PLANS WHICH WILL REQUIRE DOOR TO |
| | CONTAIN PANIC HARDWARE. |
| | 110.26/90.4 |
| | |
| | 11) NOTE: PLEASE SEE THE VOLTAGE DROP FOR 30A CU'S, AT |
| | THIS TIME CAN NOT BE VERIFIED. PLEASE SEE SOME UNITS |
| | INDICATE #10 ALREADY YET THESE WILL BE OVER 75FT AND |
| | THERE IS NO NOTE FOR THESE UNITS TO UPGRADE TO #8 OR ? |
| | PLEASE ADJUST AND PROVIDE ADDITIONAL INFORMATION. FBC |
| | 104.2.1.2, NEC 310.16, 240.4 ETC. |
| | |
| | 12) NOTE: PLEASE SEE NOTES ABOVE WHICH REQUESTS FOR THE |
| | RISER NOTES TO CORRELATE WITH THE DESIGNATIONS ON |
| | RISER. PLEASE SEE NOTE #1. |
| | 104.2.1.2 FBC ADMIN SECTION. |
| | |
| | 13) NOTE: PLEASE PROVIDE A DETAIL FOR THE ROOF TOP |
| | DISCONNECT AS BEING NOTED AND HOW THIS WILL BE MOUNTED? |
| | (NOT TO UNIT) |
| | 440.11. THIS CAN BE A TYPICAL DETAIL. |
| | |
| | 14) NOTE: PLEASE SEE ATTACHED COPY OF FLORIDA STATUTES |
| | 553.80(2)(B) WITH RESPECT TO REPEAT CODE COMPLIANCE |
| | COMMENTS. THIS IS ONLY A NOTICE GIVEN AT THIS TIME. |
| | |
| | 15) NOTE: PLEASE SEE MISSING FIRST FLOORELECTRICAL |
| | FOR UNITS WITH STAIRS. 210.70,210.52 ETC |
| | |
| | *** PLEASE KNOW THAT THERE MAY BE NEW COMMENTS ON THE |
| | NEXT REVIEW DUE TO INFORMATION NOT SUBMITTED OR |
| | COORDINATION OF PLANS/INFORMATION SUBMITTED FOR REVIEW |
| | |
| | |
| | ** PLEASE SEE ANY COMMENTS FROM OTHER REVIEWER(S) WHICH |
| | MAY HAVE AN AFFECT ON ELECTRICAL PLANS. |
| | |
| | ** PLEASE KNOW, A TYPE WRITTEN RESPONSE LETTER FROM |
| | DESIGN PROFESSIONAL(S) FOR EACH COMMENT ON HOW/WHERE |
| | CORRECTIONS ARE MADE OR IF COMMENTS ON REVIEW WILL HELP |
| | IN EXPEDITING THE PLAN REVIEW PROCESS. THIS WAS DONE, |
| | AND SHOULD BE DONE FOR THIS REVIEW AS WELL. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |