Plan Review Notes For Permit 05091687
Permit Number 05091687
Review Stop B
Sequence Number 2
Notes
Date Text
2007-02-09 15:10:07 
  
  
 PERMIT: 05091687 BLDG# 3
 ADD:XXX N CONGRESS
 74-43-43-20-00-000-3010
 CONT: E. A. LANDERS
 TEL: (305)823-3938
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 COURTNEY LAKES APARTMENTS, LLC
  
 ARCH: FORUM ARCHITECTURE & INTERIOR DESIGN
 (407)830-1400
 STRUC: ROBERT PLOWFIELD & ASSOC
 (407)657-6657
 2ND REVIEW
 ACTION: DENIED
  
 ***IMPORTANT***
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 NOTE NOC WILL BE NULL & VOID 90 DAYS
 AFTER RECORDING AT THE CLERK OF THE
 COURTS OFFICE IF WORK HAS NOT STARTED.
 FL S S 713.13(2).
  
 2) THIS COMMENT WAS PARTIALLY SATISFIED, FOR THE WHOLE
 OF THE PROJECT (3 BUILDINGS)
 THREE SIGNED & SEALED REPORTS WERE SUBMITTED TO THE
 CITY. THIS WILL SATISFY THE REQUIREMENT
 TO HAVE (1 ) REPORT WITH EACH PERMIT OR BUILDING. THE
 NEED STILL ARISES TO HAVE AT LEAST ONE SIGNED/ SEALED
 ORIGINAL FOR THE CONTRACTOR AS WELL AS THE THRESHOLD
 INSPECTOR.
 AN ADDITIONAL 2 ORIGINAL SOILS REPORTS SIGNED & SEALED
 SHALL BE REQUIRED.
 FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3-4) COMPLIED.
  
 5)BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6)FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 STRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPECTION PLAN
 PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE
 ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE STRUCTURAL INSPECTION
 PLAN IS TO PROVIDE SPECIFIC INSPECTION PROCEDURES AND
 SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 7) WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 8) COMPLIED.
  
 9A) 2ND REQUEST, CONTACT LILI URSA FOR ADDRESSING
 REQUIREMENTS @ (561)822-1239
  
 9B) 2ND REQUEST, PLEASE PROVIDE A COPY OF THE NEW PLAT,
 LOT
 HAS BEEN SUBDIVIDED.
  
 9C) 2ND REQUEST, ON ALL (3) PERMIT APPLICATIONS CORRECT
 THE PROPERTY CONTROL NUMBER TO
 THE NEW LOT.
  
 9D) PROVIDE A SITE PLAN WITH LOCATION OF THE PROPOSED
 STRUCTURES WITH DIMENSIONS
 FOR TABLE 600 ISSUES.A2.01 HAS NO DIMENSIONS! RESPONSE
 COMMENTS ARETO SEE CIVIL PLANS ,NO CIVIL PLANS PROVIDED
 IN THIS SET OF PLANS.
  
 10A-K) COMPLIED.
  
 11) SHEET A1.05
  
 11A & B) COMPLIED.
  
 12)SITE PLAN A2.01
 NEW COMMENT THAT DEALS WITH THE OVER ALL PARKING SPACES
 AND THE REQUIRED NUMBER OF ACCESSIBLE SPACES. THE PLANS
 INDICATE A TOTAL OF 912 SPACES WHERE AS IT APPEARS TO
 BE 1008 PARKING SPACES IF THIS IS TRUE THE REQUIRED
 NUMBER OF ACCESSIBLE SPACES WOULD BE 21.
 CHAPTER 11 PART B- 4PARKING AND PASSENGER LOADING:
 ACCESSIBLE PARKING ON A ROUTE ACCESSIBLE TO WHEELCHAIRS
 FOR AT LEAST 2% OF THE COVERED DWELLING UNITS:
 ACCESSIBLE VISITOR PARKING SUFFICIENT TO PROVIDE ACCESS
 TO GRADE LEVEL ENTRANCES OF COVERED MULTIFAMILY
 DWELLINGS; AND ACCESSIBLE PARKING AT FACILITIES (E.G.,
 SWIMMING POOLS) THAT SERVE ACCESSIBLE BUILDINGS.
  
 12A) 2ND REQUEST, THERE ARE NO CIVIL PLANS INCORPORATED
 INTO THIS SET OF PLANS TO REVIEW FOR ACCESSIBILITY.
 ACCESSIBLE ROUTE: FAIR HOUSING AT LEAST ONE ACCESSIBLE
 ROUTE SHALL BE
 PROVIDED WITHIN THE BOUNDARY OF THE SITE FROM PUBLIC
 TRANSPORTATION STOPS,
 ACCESSIBLE PARKING SPACES, PASSENGER LOADING ZONES IF
 PROVIDED, AND PUBLIC
 STREETS OR SIDEWALKS, TO AN ACCESSIBLE BUILDING
 ENTRANCE.
  
 12B)2ND REQUEST, THERE ARE NO CIVIL PLANS INCORPORATED
 INTO THIS SET OF PLANS TO REVIEW FOR ACCESSIBILITY.
 THE SITE PLAN DOES NOT PROVIDE ANY INFORMATION AS TO
 CURB CUTS, PEDESTRIAN
 CROSS WALKS, ETC. RESPONSE IS THE CIVIL ENGINEER IS TO
 RESPOND? WHERE?
  
 12B)(1) PLEASE PROVIDE INFORMATION WHICH ACCESSIBLE
 PARKING SPACES WILL BE THE VAN ACCESSIBLE SPACES?
 CHAPTER 11 PART B ANSI A117-1 502.5 PARKING SPACESFOR
 VANS SHALL HAVE A VERTICAL CLEARANCE OF 98" MINIMUM AT
 THE SPACE AND ALONG THE VEHICULAR ROUTE THERETO.
  
 12B)(2) PLEASE PROVIDE SIGNAGE FOR ALL ACCESSIBLE
 PARKING SPACES . CHAPTER 11 PART B ANSI A117.1502.6.
  
 13) SHEET A5.40:
  
 13A-C) COMPLIED.
  
 13D) TRASH TERMINATION ROOM NO RATING, THE IS NO WALL
 TAG IDENTIFYING THE HOURLY WALL RATING OF THE WALL?
 TABLE 705.1.2.
  
 13E) FIRE PUMP ROOM NO RATING OF WALL, NFPA
 20:5.1.12.1.1REQUIRES A 2 HR WALL RATING, DOOR
 PROTECTIVE OF1 ? HR.
  
 13F-I) COMPLIED.
  
 14) COMPLIED.
  
 15) SHEET A5.41:
  
 15A) 2ND REQUEST, TRASH ROOM DETAIL 1& 2 OF A8.20 THE
 DETAIL IS MISSING THE ENCLOSURE TO THE BOTTOM OF THE
 CHUTE ENCLOSURE .705.2.4.2ALL OPENINGS INTO THE SHAFT
 ENCLOSURE,
 INCLUDING THOSE FROM ACCESS ROOMS AND TERMINATION
 ROOMS, SHALL BE PROTECTED IN ACCORDANCE WITH TABLE
 705.1.2.SUCH OPENING PROTECTIVE SHALL BE SELF-CLOSING
 OR AUTOMATIC-CLOSING UPON DETECTION OF SMOKE, EXCEPT
 THAT THE OPENING PROTECTIVE BETWEEN THE SHAFT AND THE
 TERMINATION ROOM MAY BE CLOSED BY A HEAT-ACTIVATED
 DEVICE.
 PLEASE PROVIDE INFORMATION ON THE TRASH CHUTE SHOP
 DRAWINGS, WALL THICKNESS OF CHUTE, THE
 SELF CLOSING DEVICES, LOCATION OF SPRINKLER HEADS IN
 THE CHUTE.
  
 15B) THE TRASH REFUSE ROOM DETAIL 4 / A8.20 INDICATES
 THE 2 HR RATING ON THE FRONT & BACK WALL NOT THE SIDE
 WALLS? NOR RATING OF THE ACCESS ROOM WALLS? TABLE
 705.1.2 & 705.2.4.3.
  
 15C) NEW COMMENT:SHEET A5.43 INDICATES AN ELEVATOR
 DETAIL 2 /A8.10 , THIS ELEVATOR MACHINE ROOM DOES NOT
 INDICATE WALL OR DOOR RATINGS?
  
 15D) NEW COMMENT: SHEET A5.44 ROOF ACCESS FROM
 STAIRWELL# 2 PLANS DO NOT IDENTIFY THIS DOORWAY NOR
 RATING.
  
 15E) NEW COMMENT: SHEET A5.44 STAIRWELL ACCESS TO ROOF.
 SEE 1008 SUCH STAIRWAY SHALL BE MARKED AT STREET AND
 FLOOR LEVELS WITH A SIGN INDICATING THAT IT CONTINUES
 TO THE ROOF.
  
 15F) NEW COMMENT: SHEET A7.01WALL SECTION# 2& A7.02
 WALL SECTION# 3, DETAIL# 12/ A7.10 INDICATES THE USE OF
 WHAT APPEARS TO BE EFIS WALL SYSTEMS, THERE IS A WALL
 IDENTITY TAG W1-14 , NO SUCH TAG ON SHEET A1.04?
  
 15G) NEW COMMENT: SHEET A7.02 KEY NOTE # 10 NOTES SEE
 STRUCTURAL DRAWINGS FOR ROOF TRUSS ANCHORAGE, NO
 TRUSSES NEAR THE NOTE, WHY IS THE BATT INSULATION ON
 THE FLOOR?
  
 15H) NEW COMMENT SHEET A7.02NOTE # 29 INDICATES THE USE
 OF FOAM BAND TRIM ON THE EXTERIOR OF THE BUILDING. SEE
 1404.1.1.ARCHITECTURAL TRIM ON BUILDINGS OF TYPE I,
 II AND IV
 CONSTRUCTION NOT MORE THAN THREE STORIES OR 40 FT
 (12.2 M) HIGH MAY BE OF
 TYPE VI CONSTRUCTION, AND MAY BE OF TYPE VI
 CONSTRUCTION ON ALL BUILDINGS
 OF TYPE III, V AND VI CONSTRUCTION.TRIM SHALL BE
 SECURED TO THE WALL
 WITH METAL OR OTHER APPROVED BRACKETS OR FASTENERS.
 WHEN ARCHITECTURAL
 TRIM IS LOCATED ALONG THE TOP OF EXTERIOR WALLS, IT
 SHALL BE COMPLETELY
 BACKED BY THE EXTERIOR WALL AND SHALL NOT EXTEND OVER
 THE TOP OF EXTERIOR
 WALLS.
  
 15I) NOTE# 39 DEALS WITH ROOF TILE RIDGE AND EDGE CAPS,
 IT APPEARS TO BE MISPLACED. PLEASE PROVIDE RIDGE AND
 HIP ATTACHMENT METHODS, IF NOT COVERED UNDER THE
 PRODUCT APPROVALS SEE ROOFING STANDARD FRSA/RTI
 07320..
  
  
 16) SHEET A7.10.
  
 16A) COMPLIED.
  
 16B) SEE 15E & 15F.
  
 16C) COMMENT# 15H . 2ND REQUEST,
 THIS SAME SECTION INDICATES USE OF
 FOAM TRIM ON THE EXTERIOR OF THE
 BUILDING ABOVE 40'.1404.1.1
 ARCHITECTURAL TRIM ON BUILDINGS OF TYPE
 I, II AND IV CONSTRUCTION NOT MORE THAN
 THREE STORIES OR 40 FT (12.2 M) HIGH MAY
 BE OFTYPE VI CONSTRUCTION, AND MAY BE
 OF TYPE VI CONSTRUCTION ON ALL BUILDINGS
 OF TYPE III, V AND VI CONSTRUCTION.
 TRIM SHALL BE SECURED TO THE WALL WITH
 METAL OR OTHER APPROVED BRACKETS OR
 FASTENERS.WHEN ARCHITECTURAL TRIM IS
 LOCATED ALONG THE TOP OF EXTERIOR WALLS,
 IT SHALL BE COMPLETELY BACKED BY THE
 EXTERIOR WALL AND SHALL NOT EXTEND OVER
 THE TOP OF EXTERIOR WALLS.
  
  
 17) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 18) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) OPERABLE WINDOWS
 FL 3485TRACO TR-6800 -OK
 FL 3044.3TRACO HS-HC 65 NON-IMPACT WINDOW
 REQUIRED 0-30'LARGE MISSILE, 30'-60'SMALL MISSILE -
 DENIED
 FL 3044.4TRACO HS-AW 55NON-IMPACT WINDOW
 REQUIRED 0-30'LARGE MISSILE, 30'-60'SMALL MISSILE -
 DENIED
 FL 3044.5TRACO HS-AW55 NON-IMPACT WINDOW
 REQUIRED 0-30'LARGE MISSILE, 30'-60'SMALL MISSILE -
 DENIED
  
 B) FIXED WINDOWS
 FL 3487TRACOTR-3800 - OK
 FL 632KAWNEER EXPIRED NOA NON-IMPACT
 REQUIRED 0-30'LARGE MISSILE, 30'-60'SMALL MISSILE -
 DENIED
  
 C) MULLIONS MAY OR MAY NOT BE INCLUDED IN THE PRODUCT
 APPROVALS
  
 D) EXTERIOR HOLLOW METAL DOORS
 FL3078 AMWELD DENIED LOW PRESSURES SINGLE &
 PAIRS
  
 E) EXTERIOR GLAZED DOORS
 FL 3038TRACO 03-0829.06 SMALL MISSILE ONLY, NO
 PRESSURE TEST - DENIED
 FL 3038.3TRACO 03-0422.04 TR-8910 SMALL
 MISSILE TEST NO PRESSURE TEST - DENIED
 FL 3038.4TRACO 03-0422.04 TR-8910 LARGE
 MISSILE HIGHLIGHT ANCHOR FASTENING SCHEDULE MAY COMPLY
 FL3477TRACO TR-8300SLIDING GLASS DOOR
 NON-IMPACTREQUIRES 0-30' LARGE MISSILE, 30'-60' SMALL
 MISSILE - DENIED
  
 F) EXTERIOR LOUVERED DOORS NO REPORT SUBMITTED
  
 G) EXTERIOR RAILINGS- WILL ONLY NEED ENGINEERING NOT A
 PRODUCT APPROVAL
  
 H) LOUVERS NO REPORT SUBMITTED.
  
 I) TRUSS ANCHORS NO REPORT SUBMITTED.
  
 J) ROOF ASSEMBLIES INCLUDING DENSE DECK, INSULATION,
 UNDERLAYMENT, ROOF TILE AND ATTACHMENT METHODS. FL 1559
 SINGLE PLY ROOF SYSTEMS- HIGHLIGHT WHICH SUB-SYSTEM TO
 BE USED.
 NOTE ZONES 2 & 3 MAY REQUIRE ENHANCED FASTENING
 PROVIDE RATIONAL ANALYSIS BY QUALIFIED PROFESSIONAL
  
 K) EFIS WALL SYSTEMS IF USED
  
 L)5/8" FIBER TOUGH AQUA ROCK SHEATHING
  
 M ) PRE-MANUFACTURED ROOF A/C STANDS- OK
  
 N) ROLL UP DOOR - NO REPORT SUBMITTED
  
 O) DENSE DECK- MAY BE INCORPORATED IN A PRODUCT
 APPROVAL
  
 P) ROOF TILE - NO REPORT SUBMITTED- CIRCLE OR HIGHLIGHT
 WHAT ANCHOR METHOD TO INSTALLROOF TILE
  
 19) IMPACT GLASS IS SPECIFIED, COMPLIED.
  
 20)IMPACT GLASS IS SPECIFIED, COMPLIED.
  
  
 21)IMPACT GLASS IS SPECIFIED, COMPLIED.
  
  
 22- 29) COMPLIED
  
 NOTE: CALCULATED VALUE: $ 10,848,462.00/144,666 SQ
 FT
  
 ADDITIONAL COMMENTS MAY APPEAR ON THE
 NEXT REVIEW NOT COVERED FROM THE FIRST
 REVIEW DUE TO THE COMMENT RESPONSE OR
 ADDITIONAL INFORMATION NOT PROVIDED
 UNDER THE FIRST REVIEW.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 COURTNEY LAKES BLD.# 3 REV. (2).DOC