| 2007-02-09 15:10:07 | |
| | |
| | |
| | PERMIT: 05091687 BLDG# 3 |
| | ADD:XXX N CONGRESS |
| | 74-43-43-20-00-000-3010 |
| | CONT: E. A. LANDERS |
| | TEL: (305)823-3938 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | COURTNEY LAKES APARTMENTS, LLC |
| | |
| | ARCH: FORUM ARCHITECTURE & INTERIOR DESIGN |
| | (407)830-1400 |
| | STRUC: ROBERT PLOWFIELD & ASSOC |
| | (407)657-6657 |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | ***IMPORTANT*** |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | NOTE NOC WILL BE NULL & VOID 90 DAYS |
| | AFTER RECORDING AT THE CLERK OF THE |
| | COURTS OFFICE IF WORK HAS NOT STARTED. |
| | FL S S 713.13(2). |
| | |
| | 2) THIS COMMENT WAS PARTIALLY SATISFIED, FOR THE WHOLE |
| | OF THE PROJECT (3 BUILDINGS) |
| | THREE SIGNED & SEALED REPORTS WERE SUBMITTED TO THE |
| | CITY. THIS WILL SATISFY THE REQUIREMENT |
| | TO HAVE (1 ) REPORT WITH EACH PERMIT OR BUILDING. THE |
| | NEED STILL ARISES TO HAVE AT LEAST ONE SIGNED/ SEALED |
| | ORIGINAL FOR THE CONTRACTOR AS WELL AS THE THRESHOLD |
| | INSPECTOR. |
| | AN ADDITIONAL 2 ORIGINAL SOILS REPORTS SIGNED & SEALED |
| | SHALL BE REQUIRED. |
| | FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | WHERE THE BEARING CAPACITY OF THE SOIL |
| | IS NOT DEFINITLY KNOWN OR IS IN QUESTION |
| | THE BUILDING OFFICIAL MAY REQUIRE EXPLOR |
| | ATIONS, TEST OR OTHER ADEQUATE PROOF AS |
| | TO THE PERMISSIBLE SAFE BEARING |
| | CAPACITY. REQUIRED TEST AND RECOMMENDA- |
| | TIONS SUBMITTED TO VERIFY BEARING CAPA- |
| | CITY SHALL BE CERTIFIED BY A GEOTECH- |
| | NICALREPORT FROM A DESIGN PROFESSIONAL |
| | PROPERLY LICENSED IN THE STATE OF |
| | FLORIDA. |
| | |
| | 3-4) COMPLIED. |
| | |
| | 5)BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 6)FL S. S. 553.71(7) " THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY |
| | CLASSIFICATION AS DENIED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS |
| | 5,000 SQ FT IN AREA AND AN OCCUPANT |
| | CONTENT OF GREATER THAN 500 PERSONS. |
| | |
| | 105.13.1 THE ENFORCING AGENCY SHALL |
| | REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| | STRUCTURAL INSPECTIONS ON A THRESHOLD |
| | BUILDING PURSUANT TO A STRUCTURAL INSPECTION PLAN |
| | PREPARED BY THE ENGINEER OF |
| | RECORD. THE STRUCTURAL INSPECTION PLAN |
| | MUST BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE |
| | ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESH- |
| | OLD BUILDING. THE PURPOSE OF THE STRUCTURAL INSPECTION |
| | PLAN IS TO PROVIDE SPECIFIC INSPECTION PROCEDURES AND |
| | SCHEDULES |
| | SO THAT THE BUILDING CAN BE ADEQUATELY |
| | INSPECTED FOR COMPLIANCE WITH THE |
| | PERMITTED DOCUMENTS. |
| | |
| | 7) WPB AMENDMENT 105.13.6. W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A |
| | SPECIAL INSPECTOR AS REQUIRED BY S. |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. |
| | CONTACT HAROLD PISKURA MANAGER OF THE |
| | SPECIAL INSPECTOR PROGRAM AT (561) |
| | 805-6711 FOR FURTHER INFORMATION BEFORE |
| | THE PERMIT MAY BE ISSUED. |
| | |
| | 8) COMPLIED. |
| | |
| | 9A) 2ND REQUEST, CONTACT LILI URSA FOR ADDRESSING |
| | REQUIREMENTS @ (561)822-1239 |
| | |
| | 9B) 2ND REQUEST, PLEASE PROVIDE A COPY OF THE NEW PLAT, |
| | LOT |
| | HAS BEEN SUBDIVIDED. |
| | |
| | 9C) 2ND REQUEST, ON ALL (3) PERMIT APPLICATIONS CORRECT |
| | THE PROPERTY CONTROL NUMBER TO |
| | THE NEW LOT. |
| | |
| | 9D) PROVIDE A SITE PLAN WITH LOCATION OF THE PROPOSED |
| | STRUCTURES WITH DIMENSIONS |
| | FOR TABLE 600 ISSUES.A2.01 HAS NO DIMENSIONS! RESPONSE |
| | COMMENTS ARETO SEE CIVIL PLANS ,NO CIVIL PLANS PROVIDED |
| | IN THIS SET OF PLANS. |
| | |
| | 10A-K) COMPLIED. |
| | |
| | 11) SHEET A1.05 |
| | |
| | 11A & B) COMPLIED. |
| | |
| | 12)SITE PLAN A2.01 |
| | NEW COMMENT THAT DEALS WITH THE OVER ALL PARKING SPACES |
| | AND THE REQUIRED NUMBER OF ACCESSIBLE SPACES. THE PLANS |
| | INDICATE A TOTAL OF 912 SPACES WHERE AS IT APPEARS TO |
| | BE 1008 PARKING SPACES IF THIS IS TRUE THE REQUIRED |
| | NUMBER OF ACCESSIBLE SPACES WOULD BE 21. |
| | CHAPTER 11 PART B- 4PARKING AND PASSENGER LOADING: |
| | ACCESSIBLE PARKING ON A ROUTE ACCESSIBLE TO WHEELCHAIRS |
| | FOR AT LEAST 2% OF THE COVERED DWELLING UNITS: |
| | ACCESSIBLE VISITOR PARKING SUFFICIENT TO PROVIDE ACCESS |
| | TO GRADE LEVEL ENTRANCES OF COVERED MULTIFAMILY |
| | DWELLINGS; AND ACCESSIBLE PARKING AT FACILITIES (E.G., |
| | SWIMMING POOLS) THAT SERVE ACCESSIBLE BUILDINGS. |
| | |
| | 12A) 2ND REQUEST, THERE ARE NO CIVIL PLANS INCORPORATED |
| | INTO THIS SET OF PLANS TO REVIEW FOR ACCESSIBILITY. |
| | ACCESSIBLE ROUTE: FAIR HOUSING AT LEAST ONE ACCESSIBLE |
| | ROUTE SHALL BE |
| | PROVIDED WITHIN THE BOUNDARY OF THE SITE FROM PUBLIC |
| | TRANSPORTATION STOPS, |
| | ACCESSIBLE PARKING SPACES, PASSENGER LOADING ZONES IF |
| | PROVIDED, AND PUBLIC |
| | STREETS OR SIDEWALKS, TO AN ACCESSIBLE BUILDING |
| | ENTRANCE. |
| | |
| | 12B)2ND REQUEST, THERE ARE NO CIVIL PLANS INCORPORATED |
| | INTO THIS SET OF PLANS TO REVIEW FOR ACCESSIBILITY. |
| | THE SITE PLAN DOES NOT PROVIDE ANY INFORMATION AS TO |
| | CURB CUTS, PEDESTRIAN |
| | CROSS WALKS, ETC. RESPONSE IS THE CIVIL ENGINEER IS TO |
| | RESPOND? WHERE? |
| | |
| | 12B)(1) PLEASE PROVIDE INFORMATION WHICH ACCESSIBLE |
| | PARKING SPACES WILL BE THE VAN ACCESSIBLE SPACES? |
| | CHAPTER 11 PART B ANSI A117-1 502.5 PARKING SPACESFOR |
| | VANS SHALL HAVE A VERTICAL CLEARANCE OF 98" MINIMUM AT |
| | THE SPACE AND ALONG THE VEHICULAR ROUTE THERETO. |
| | |
| | 12B)(2) PLEASE PROVIDE SIGNAGE FOR ALL ACCESSIBLE |
| | PARKING SPACES . CHAPTER 11 PART B ANSI A117.1502.6. |
| | |
| | 13) SHEET A5.40: |
| | |
| | 13A-C) COMPLIED. |
| | |
| | 13D) TRASH TERMINATION ROOM NO RATING, THE IS NO WALL |
| | TAG IDENTIFYING THE HOURLY WALL RATING OF THE WALL? |
| | TABLE 705.1.2. |
| | |
| | 13E) FIRE PUMP ROOM NO RATING OF WALL, NFPA |
| | 20:5.1.12.1.1REQUIRES A 2 HR WALL RATING, DOOR |
| | PROTECTIVE OF1 ? HR. |
| | |
| | 13F-I) COMPLIED. |
| | |
| | 14) COMPLIED. |
| | |
| | 15) SHEET A5.41: |
| | |
| | 15A) 2ND REQUEST, TRASH ROOM DETAIL 1& 2 OF A8.20 THE |
| | DETAIL IS MISSING THE ENCLOSURE TO THE BOTTOM OF THE |
| | CHUTE ENCLOSURE .705.2.4.2ALL OPENINGS INTO THE SHAFT |
| | ENCLOSURE, |
| | INCLUDING THOSE FROM ACCESS ROOMS AND TERMINATION |
| | ROOMS, SHALL BE PROTECTED IN ACCORDANCE WITH TABLE |
| | 705.1.2.SUCH OPENING PROTECTIVE SHALL BE SELF-CLOSING |
| | OR AUTOMATIC-CLOSING UPON DETECTION OF SMOKE, EXCEPT |
| | THAT THE OPENING PROTECTIVE BETWEEN THE SHAFT AND THE |
| | TERMINATION ROOM MAY BE CLOSED BY A HEAT-ACTIVATED |
| | DEVICE. |
| | PLEASE PROVIDE INFORMATION ON THE TRASH CHUTE SHOP |
| | DRAWINGS, WALL THICKNESS OF CHUTE, THE |
| | SELF CLOSING DEVICES, LOCATION OF SPRINKLER HEADS IN |
| | THE CHUTE. |
| | |
| | 15B) THE TRASH REFUSE ROOM DETAIL 4 / A8.20 INDICATES |
| | THE 2 HR RATING ON THE FRONT & BACK WALL NOT THE SIDE |
| | WALLS? NOR RATING OF THE ACCESS ROOM WALLS? TABLE |
| | 705.1.2 & 705.2.4.3. |
| | |
| | 15C) NEW COMMENT:SHEET A5.43 INDICATES AN ELEVATOR |
| | DETAIL 2 /A8.10 , THIS ELEVATOR MACHINE ROOM DOES NOT |
| | INDICATE WALL OR DOOR RATINGS? |
| | |
| | 15D) NEW COMMENT: SHEET A5.44 ROOF ACCESS FROM |
| | STAIRWELL# 2 PLANS DO NOT IDENTIFY THIS DOORWAY NOR |
| | RATING. |
| | |
| | 15E) NEW COMMENT: SHEET A5.44 STAIRWELL ACCESS TO ROOF. |
| | SEE 1008 SUCH STAIRWAY SHALL BE MARKED AT STREET AND |
| | FLOOR LEVELS WITH A SIGN INDICATING THAT IT CONTINUES |
| | TO THE ROOF. |
| | |
| | 15F) NEW COMMENT: SHEET A7.01WALL SECTION# 2& A7.02 |
| | WALL SECTION# 3, DETAIL# 12/ A7.10 INDICATES THE USE OF |
| | WHAT APPEARS TO BE EFIS WALL SYSTEMS, THERE IS A WALL |
| | IDENTITY TAG W1-14 , NO SUCH TAG ON SHEET A1.04? |
| | |
| | 15G) NEW COMMENT: SHEET A7.02 KEY NOTE # 10 NOTES SEE |
| | STRUCTURAL DRAWINGS FOR ROOF TRUSS ANCHORAGE, NO |
| | TRUSSES NEAR THE NOTE, WHY IS THE BATT INSULATION ON |
| | THE FLOOR? |
| | |
| | 15H) NEW COMMENT SHEET A7.02NOTE # 29 INDICATES THE USE |
| | OF FOAM BAND TRIM ON THE EXTERIOR OF THE BUILDING. SEE |
| | 1404.1.1.ARCHITECTURAL TRIM ON BUILDINGS OF TYPE I, |
| | II AND IV |
| | CONSTRUCTION NOT MORE THAN THREE STORIES OR 40 FT |
| | (12.2 M) HIGH MAY BE OF |
| | TYPE VI CONSTRUCTION, AND MAY BE OF TYPE VI |
| | CONSTRUCTION ON ALL BUILDINGS |
| | OF TYPE III, V AND VI CONSTRUCTION.TRIM SHALL BE |
| | SECURED TO THE WALL |
| | WITH METAL OR OTHER APPROVED BRACKETS OR FASTENERS. |
| | WHEN ARCHITECTURAL |
| | TRIM IS LOCATED ALONG THE TOP OF EXTERIOR WALLS, IT |
| | SHALL BE COMPLETELY |
| | BACKED BY THE EXTERIOR WALL AND SHALL NOT EXTEND OVER |
| | THE TOP OF EXTERIOR |
| | WALLS. |
| | |
| | 15I) NOTE# 39 DEALS WITH ROOF TILE RIDGE AND EDGE CAPS, |
| | IT APPEARS TO BE MISPLACED. PLEASE PROVIDE RIDGE AND |
| | HIP ATTACHMENT METHODS, IF NOT COVERED UNDER THE |
| | PRODUCT APPROVALS SEE ROOFING STANDARD FRSA/RTI |
| | 07320.. |
| | |
| | |
| | 16) SHEET A7.10. |
| | |
| | 16A) COMPLIED. |
| | |
| | 16B) SEE 15E & 15F. |
| | |
| | 16C) COMMENT# 15H . 2ND REQUEST, |
| | THIS SAME SECTION INDICATES USE OF |
| | FOAM TRIM ON THE EXTERIOR OF THE |
| | BUILDING ABOVE 40'.1404.1.1 |
| | ARCHITECTURAL TRIM ON BUILDINGS OF TYPE |
| | I, II AND IV CONSTRUCTION NOT MORE THAN |
| | THREE STORIES OR 40 FT (12.2 M) HIGH MAY |
| | BE OFTYPE VI CONSTRUCTION, AND MAY BE |
| | OF TYPE VI CONSTRUCTION ON ALL BUILDINGS |
| | OF TYPE III, V AND VI CONSTRUCTION. |
| | TRIM SHALL BE SECURED TO THE WALL WITH |
| | METAL OR OTHER APPROVED BRACKETS OR |
| | FASTENERS.WHEN ARCHITECTURAL TRIM IS |
| | LOCATED ALONG THE TOP OF EXTERIOR WALLS, |
| | IT SHALL BE COMPLETELY BACKED BY THE |
| | EXTERIOR WALL AND SHALL NOT EXTEND OVER |
| | THE TOP OF EXTERIOR WALLS. |
| | |
| | |
| | 17) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 18) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) OPERABLE WINDOWS |
| | FL 3485TRACO TR-6800 -OK |
| | FL 3044.3TRACO HS-HC 65 NON-IMPACT WINDOW |
| | REQUIRED 0-30'LARGE MISSILE, 30'-60'SMALL MISSILE - |
| | DENIED |
| | FL 3044.4TRACO HS-AW 55NON-IMPACT WINDOW |
| | REQUIRED 0-30'LARGE MISSILE, 30'-60'SMALL MISSILE - |
| | DENIED |
| | FL 3044.5TRACO HS-AW55 NON-IMPACT WINDOW |
| | REQUIRED 0-30'LARGE MISSILE, 30'-60'SMALL MISSILE - |
| | DENIED |
| | |
| | B) FIXED WINDOWS |
| | FL 3487TRACOTR-3800 - OK |
| | FL 632KAWNEER EXPIRED NOA NON-IMPACT |
| | REQUIRED 0-30'LARGE MISSILE, 30'-60'SMALL MISSILE - |
| | DENIED |
| | |
| | C) MULLIONS MAY OR MAY NOT BE INCLUDED IN THE PRODUCT |
| | APPROVALS |
| | |
| | D) EXTERIOR HOLLOW METAL DOORS |
| | FL3078 AMWELD DENIED LOW PRESSURES SINGLE & |
| | PAIRS |
| | |
| | E) EXTERIOR GLAZED DOORS |
| | FL 3038TRACO 03-0829.06 SMALL MISSILE ONLY, NO |
| | PRESSURE TEST - DENIED |
| | FL 3038.3TRACO 03-0422.04 TR-8910 SMALL |
| | MISSILE TEST NO PRESSURE TEST - DENIED |
| | FL 3038.4TRACO 03-0422.04 TR-8910 LARGE |
| | MISSILE HIGHLIGHT ANCHOR FASTENING SCHEDULE MAY COMPLY |
| | FL3477TRACO TR-8300SLIDING GLASS DOOR |
| | NON-IMPACTREQUIRES 0-30' LARGE MISSILE, 30'-60' SMALL |
| | MISSILE - DENIED |
| | |
| | F) EXTERIOR LOUVERED DOORS NO REPORT SUBMITTED |
| | |
| | G) EXTERIOR RAILINGS- WILL ONLY NEED ENGINEERING NOT A |
| | PRODUCT APPROVAL |
| | |
| | H) LOUVERS NO REPORT SUBMITTED. |
| | |
| | I) TRUSS ANCHORS NO REPORT SUBMITTED. |
| | |
| | J) ROOF ASSEMBLIES INCLUDING DENSE DECK, INSULATION, |
| | UNDERLAYMENT, ROOF TILE AND ATTACHMENT METHODS. FL 1559 |
| | SINGLE PLY ROOF SYSTEMS- HIGHLIGHT WHICH SUB-SYSTEM TO |
| | BE USED. |
| | NOTE ZONES 2 & 3 MAY REQUIRE ENHANCED FASTENING |
| | PROVIDE RATIONAL ANALYSIS BY QUALIFIED PROFESSIONAL |
| | |
| | K) EFIS WALL SYSTEMS IF USED |
| | |
| | L)5/8" FIBER TOUGH AQUA ROCK SHEATHING |
| | |
| | M ) PRE-MANUFACTURED ROOF A/C STANDS- OK |
| | |
| | N) ROLL UP DOOR - NO REPORT SUBMITTED |
| | |
| | O) DENSE DECK- MAY BE INCORPORATED IN A PRODUCT |
| | APPROVAL |
| | |
| | P) ROOF TILE - NO REPORT SUBMITTED- CIRCLE OR HIGHLIGHT |
| | WHAT ANCHOR METHOD TO INSTALLROOF TILE |
| | |
| | 19) IMPACT GLASS IS SPECIFIED, COMPLIED. |
| | |
| | 20)IMPACT GLASS IS SPECIFIED, COMPLIED. |
| | |
| | |
| | 21)IMPACT GLASS IS SPECIFIED, COMPLIED. |
| | |
| | |
| | 22- 29) COMPLIED |
| | |
| | NOTE: CALCULATED VALUE: $ 10,848,462.00/144,666 SQ |
| | FT |
| | |
| | ADDITIONAL COMMENTS MAY APPEAR ON THE |
| | NEXT REVIEW NOT COVERED FROM THE FIRST |
| | REVIEW DUE TO THE COMMENT RESPONSE OR |
| | ADDITIONAL INFORMATION NOT PROVIDED |
| | UNDER THE FIRST REVIEW. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | COURTNEY LAKES BLD.# 3 REV. (2).DOC |