2006-01-31 00:00:00DENIED:2001 FLORIDA BUILDING CODE
  
 1.PLAN SHEET AP A6.01 THROUGH A701, IT
 APPEARS THE COORIDORS HAVE OPENINGS AT
 CERTAIN POINTS.PLEASE INDICATE TOTAL
 SQUARE FOOTAGE AS REQUIRED FOR 'NATURAL
 VENTILATION'.THE OUTSIDE AIR
 CALCULATIONS INDICATED ON PLAN SHEET
 M15.13 DO NOT SHOW TOTAL SQUARE FOOTAGE.
  
 2.PLANS INDICATE RETURN AIR JUMPERS
 FROM THE BEDROOM AREAS.PLEASE NOTE,
 THE RETURN AIR JUMPERS ARE TO BE SIZED
 IN ACCORDANCE WITH 2001 FMC 601.4
 EXCEPTION 1 & 3.PLEASE REVISE RETURN
 TO INCREASE TO THE REQUIRED MINIMUM.
  
 3.PLANS INDICATE LOUVERED DOOR.THE
 DOOR SCHEDULE INDICATES THIS AS BEING A
 WOOD DOOR.THE AHU CLOSET IS CONSIDERED
 A RETURN AIR PLENUM.THE DOOR MUST ALSO
 MEET THE REQUIREMENT OF NON-COMBUSTIBLE
 OR SHALL HAVE A FLAME SPREAD INDEX OF
 NOT MORE THAN 25 AND A SMIKE DEVELOPED
 INDEX OF NOT MORE THAN 50 WHEN TESTED IN
 ACCORDANCE WITH ASTM E 84.PLEASE
 PROVIDE DOCUMENTATION ON THE DOORS.
  
 4.PLEASE NOTE, PER 2001 FMC 603.1.3 4"
 CLEARANCE AROUND THE AIR HANDLER IS
 REQUIRED.
  
 5.PLAN SHEET M15.12 DETAILS FOR THE
 AHUDOES NOT INDICATE AN AUXILIARY
 DRAIN PAN WITH OVERFLOW PROTECTION AS
 REQUIRED BY 2001 FMC 307.2.3.PLEASE
 REVISE.
  
 6.CONDENSING UNIT STANDS SHALL COMPLY
 WITH 2001 FBC 1511.7 FOR HEIGHT
 REQUIREMENT ABOVE FINISHED ROOF.
  
 7.CONDENSING UNIT STANDS SHALL COMPLY
 WITH 2001 FMC 301.13 & CHAPTER 15 OF THE
 FBC FOR WIND PRESSURES.
  
 8.PLEASE PROVIDE LINE SIZES FOR THE
 REFRIGERANT LINES AS WELL AS THE
 CONDENSATE.
  
 9.PLEASE INDICATE TERMINATION OF THE
 CONDENSATE.
  
 10. PLEASE PROVIDE ENERGY AND MANUAL J
 CALCULATIONS IN ACCORDANCE WITH 2001 FBC
 CHAPTER 13.
  