| 2006-01-31 00:00:00 | DENIED:2001 FLORIDA BUILDING CODE |
| | |
| | 1.PLAN SHEET AP A6.01 THROUGH A701, IT |
| | APPEARS THE COORIDORS HAVE OPENINGS AT |
| | CERTAIN POINTS.PLEASE INDICATE TOTAL |
| | SQUARE FOOTAGE AS REQUIRED FOR 'NATURAL |
| | VENTILATION'.THE OUTSIDE AIR |
| | CALCULATIONS INDICATED ON PLAN SHEET |
| | M15.13 DO NOT SHOW TOTAL SQUARE FOOTAGE. |
| | |
| | 2.PLANS INDICATE RETURN AIR JUMPERS |
| | FROM THE BEDROOM AREAS.PLEASE NOTE, |
| | THE RETURN AIR JUMPERS ARE TO BE SIZED |
| | IN ACCORDANCE WITH 2001 FMC 601.4 |
| | EXCEPTION 1 & 3.PLEASE REVISE RETURN |
| | TO INCREASE TO THE REQUIRED MINIMUM. |
| | |
| | 3.PLANS INDICATE LOUVERED DOOR.THE |
| | DOOR SCHEDULE INDICATES THIS AS BEING A |
| | WOOD DOOR.THE AHU CLOSET IS CONSIDERED |
| | A RETURN AIR PLENUM.THE DOOR MUST ALSO |
| | MEET THE REQUIREMENT OF NON-COMBUSTIBLE |
| | OR SHALL HAVE A FLAME SPREAD INDEX OF |
| | NOT MORE THAN 25 AND A SMIKE DEVELOPED |
| | INDEX OF NOT MORE THAN 50 WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E 84.PLEASE |
| | PROVIDE DOCUMENTATION ON THE DOORS. |
| | |
| | 4.PLEASE NOTE, PER 2001 FMC 603.1.3 4" |
| | CLEARANCE AROUND THE AIR HANDLER IS |
| | REQUIRED. |
| | |
| | 5.PLAN SHEET M15.12 DETAILS FOR THE |
| | AHUDOES NOT INDICATE AN AUXILIARY |
| | DRAIN PAN WITH OVERFLOW PROTECTION AS |
| | REQUIRED BY 2001 FMC 307.2.3.PLEASE |
| | REVISE. |
| | |
| | 6.CONDENSING UNIT STANDS SHALL COMPLY |
| | WITH 2001 FBC 1511.7 FOR HEIGHT |
| | REQUIREMENT ABOVE FINISHED ROOF. |
| | |
| | 7.CONDENSING UNIT STANDS SHALL COMPLY |
| | WITH 2001 FMC 301.13 & CHAPTER 15 OF THE |
| | FBC FOR WIND PRESSURES. |
| | |
| | 8.PLEASE PROVIDE LINE SIZES FOR THE |
| | REFRIGERANT LINES AS WELL AS THE |
| | CONDENSATE. |
| | |
| | 9.PLEASE INDICATE TERMINATION OF THE |
| | CONDENSATE. |
| | |
| | 10. PLEASE PROVIDE ENERGY AND MANUAL J |
| | CALCULATIONS IN ACCORDANCE WITH 2001 FBC |
| | CHAPTER 13. |
| | |