| 2005-12-28 00:00:00 | ******DENIED****** |
| | |
| | 1) NFPA 101 AND NFPA 1, 2003 EDITION |
| | SHALL BE REFERENCED. |
| | |
| | 2) SEPARATE SHOP DRAWINGS AND PERMITS |
| | ARE REQUIRED FOR FIRE SPRINKLER SYSTEM |
| | WHICH SHALL BE UL CERTIFIED FOR CENTRAL |
| | STATION SERVICE. |
| | |
| | 3) PLEASE NOTE THAT INTENDED SCOPE OF |
| | WORK FOR THIS PROJECT IN RELATION TO THE |
| | PERMIT APPLICATIONS IS CONFUSING. |
| | |
| | 4) WHENS PLANS ARE RESUBMITTED, PLEASE |
| | ASSURE THAT ALL SHEETS ARE BOUND |
| | TOGETHER AND ORGANIZED. |
| | |
| | 5) CONSTRUCTION, ALTERATION AND |
| | DEMOLITION TO COMPLY WITH NFPA 241. |
| | |
| | 6) STAIRS ARE TO BE KEPT UP WITH |
| | CONSTRUCTION. |
| | |
| | 7) TEMPORARY STANDPIPES ARE REQUIRED |
| | WHEN THE BUILDING REACHES 3 STORIES OR |
| | 30' IN HEIGHT. |
| | |
| | 8) IN REGARDS TO PHASING, PLEASE BE |
| | ADVISED THAT ALL LIFE SAFETY COMPONENTS |
| | MUST BE INSPECTED, TESTED AND APPROVED |
| | PRIOR TO OCCUPANCY OF BUILDINGS. |
| | |
| | 9) PARKING AREAS MUST BE IN COMPLIANCE |
| | WITH APPLICABLE BUILDING CODES AND NFPA |
| | 88A. MINIMUM TWO HOUR SEPARATION TO |
| | OTHER PARTS OF BUILDING IS REQUIRED. |
| | |
| | 10) WET FIRE HYDRANTS TO BE OPERATION |
| | PRIOR TO, DURING AND AFTER CONSTRUCTION. |
| | |
| | 11) PLEASE NOTE THAT ALL LIFE SAFETY |
| | EQUIPMENT, FIRE SPRINKLER AND FIRE ALARM |
| | AND ALL OTHER BUILDING SERVICES SHALL BE |
| | SEPARATE IF BUILDINGS MEET THE CRITERIA |
| | FOR SEPARATE STRUCTURES. |
| | |
| | 12) ALL ACCESS ROADS SHALL BE AT LEAST |
| | 20' IN CLEAR , UNOBSTRUCTED WIDTH FOR |
| | EMERGENCY VEHICLES, AND SHALL MEET ALL |
| | OTHER REQUIREMENTS OF NFPA 1. |
| | |
| | 13) PLEASE INDICATE ALL LOCATION OF FIRE |
| | HYDRANTS. |
| | |
| | 14) NFPA 13, 2002 EDITION SHALL BE |
| | REFERENCED. SHT. A5.01. |
| | |
| | 15) LOCKING KNOX BOX CAPS ARE REQUIRED |
| | ON FIRE DEPARTMENT CONNECTIONS. |
| | |
| | 16) IN ADDITION TO ELECTRONIC SWITCHES, |
| | THE DOUBLE CHECK DETECTOR ASSEMBLIES |
| | SHALL BE SECURED WITH A CHAIN AND LOCK. |
| | |
| | 17) AS NOTED ON SHT, A5.02, FIRE |
| | EXTINGUISHERS SHALL BE MOUNTED AT |
| | DISTANCES TO SATISFY THE 75' TRAVEL |
| | DISTANCE REQUIREMENT. |
| | |
| | 18) ALL DOORS SHALL SWING IN THE |
| | DIRECTION OF TRAVEL WHEN SERVING AREAS |
| | WITH OCCUPANT LOADS OF GREATER THAN 50. |
| | |
| | 19) ELEVATORS TO COMPLY WITH ASME A17.1. |
| | |
| | 20) PENETRATIONS INTO , AND OPENINGS |
| | THROUGH STAIRWELLS SHALL BE LIMITED TO |
| | AND IN COMPLIANCE WITH NFPA 101, SECTION |
| | 7.1.3.2.1 (6). |
| | |
| | 21) PLEASE CLARIFY ALL EXIT DISCHARGING |
| | FROM STAIRWELLS THAT LEAD DIRECTLY TO |
| | THE OUTSIDE. |
| | |
| | 22) SOME ACHITECTUAL DRAWINGS SHOW |
| | STAIRWELL DOORS, AND OTHERS DON'T.??? |
| | |
| | 23) THIS PERMIT APPLICATION PROCESS |
| | ILLUSTRATES 3 BUILDINGS AND OTHER |
| | BUILDINGS, 4&5 ARE SHOWN ON PLANS. |
| | PLEASE CLARIFY. |
| | |
| | 24) PLEASE ILLUSTRATE THE TOTAL OCCUPANT |
| | LOAD FOR THE CLUBHOUSE. |
| | |
| | 25) IN ADDITION TO THE ALREADY NOTED |
| | REQUIREMENTS FOR ADDRESSING, PLEASE NOTE |
| | THAT THE HEIGHT OF THE ADDRESS SHALL BE |
| | AT LEAST 3" IN HEIGHT FOR RESIDENTIAL |
| | BUILDINGS. |
| | |
| | 26) PLEASE REFER TO DOOR SCHEDULE AND |
| | VERIFY CORRECT AMOUNT OF FIRE RATED |
| | DOORS. DOORS SERVINGS AREAS WITH |
| | OCCUPANT LOADS GREATER THAN 100 SHALL |
| | HAVE PANIC HARDWARE. |
| | |
| | 27) FIRE PROTECTION SITE PLAN DOESN'T |
| | APPEAR COMPLETE ON SHT FP13.01. |
| | |
| | 28) FIRE DEPARTMENT VALVES SHALL BE 2 |
| | 1/2" TO 1 1/2" REDUCER WITH CHAINS. |
| | |
| | 29) MORE INFORMATION AND MANUFACTURER |
| | SPEC SHEETS REQUIRED FOR FIRE PUMP AND |
| | ASSOCIATED EQUIPMENT. |
| | |
| | 30) FIRE PROTECTION SHEETS DON'T SHOW |
| | ANY FIRE SPRINKLER SYSTEM. ???? FIRE |
| | SPRINKLER DESIGN AND LAY OUT MUST BE |
| | ILLUSTRATED. |
| | |
| | 31) IF A FIRE HYDRANT FLOW TEST HASN'T |
| | BEEN DONE WITHIN ONE YEAR, ANOTHER TEST |
| | WILL BE REQUIRED FOR FIRE SPRINKLER |
| | CALC. PLEASE CONTACT THE BUREAU OF FIRE |
| | PREVENTION AT (561) 805-4724. |
| | |
| | 32) PLEASE INDICATE ALL SMOKE DETECTOR |
| | LOCATIONS IN ACCORDANCE WITH NFPA 101, |
| | SECTION 30.3.4.5. |
| | |
| | 33) EXIT LIGHTS TO BE MOUNTED AT |
| | DISTANCES NOT TO EXCEED 100'. IT APPEARS |
| | THAT MORE EXIT SIGNS ARE NEEDED IN |
| | CORRIDORS. |
| | |
| | 34) FIRE ALARM SHALL BE CLASS A, STYLE D |
| | OR FULLY ADDRESSABLE. |
| | |
| | 35) ARE SMOKE DETECTORS TIED INTO THE |
| | FIRE ALARM SYSTEM PLANNED FOR CORRIDORS? |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLAN REVIEW (561) 805-6722 |
| | |
| | |
| | |
| | |