Plan Review Notes
Plan Review Notes For Permit 05091687
Permit Number 05091687
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-12-28 00:00:00******DENIED******
  
 1) NFPA 101 AND NFPA 1, 2003 EDITION
 SHALL BE REFERENCED.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER SYSTEM
 WHICH SHALL BE UL CERTIFIED FOR CENTRAL
 STATION SERVICE.
  
 3) PLEASE NOTE THAT INTENDED SCOPE OF
 WORK FOR THIS PROJECT IN RELATION TO THE
 PERMIT APPLICATIONS IS CONFUSING.
  
 4) WHENS PLANS ARE RESUBMITTED, PLEASE
 ASSURE THAT ALL SHEETS ARE BOUND
 TOGETHER AND ORGANIZED.
  
 5) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 6) STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 7) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHES 3 STORIES OR
 30' IN HEIGHT.
  
 8) IN REGARDS TO PHASING, PLEASE BE
 ADVISED THAT ALL LIFE SAFETY COMPONENTS
 MUST BE INSPECTED, TESTED AND APPROVED
 PRIOR TO OCCUPANCY OF BUILDINGS.
  
 9) PARKING AREAS MUST BE IN COMPLIANCE
 WITH APPLICABLE BUILDING CODES AND NFPA
 88A. MINIMUM TWO HOUR SEPARATION TO
 OTHER PARTS OF BUILDING IS REQUIRED.
  
 10) WET FIRE HYDRANTS TO BE OPERATION
 PRIOR TO, DURING AND AFTER CONSTRUCTION.
  
 11) PLEASE NOTE THAT ALL LIFE SAFETY
 EQUIPMENT, FIRE SPRINKLER AND FIRE ALARM
 AND ALL OTHER BUILDING SERVICES SHALL BE
 SEPARATE IF BUILDINGS MEET THE CRITERIA
 FOR SEPARATE STRUCTURES.
  
 12) ALL ACCESS ROADS SHALL BE AT LEAST
 20' IN CLEAR , UNOBSTRUCTED WIDTH FOR
 EMERGENCY VEHICLES, AND SHALL MEET ALL
 OTHER REQUIREMENTS OF NFPA 1.
  
 13) PLEASE INDICATE ALL LOCATION OF FIRE
 HYDRANTS.
  
 14) NFPA 13, 2002 EDITION SHALL BE
 REFERENCED. SHT. A5.01.
  
 15) LOCKING KNOX BOX CAPS ARE REQUIRED
 ON FIRE DEPARTMENT CONNECTIONS.
  
 16) IN ADDITION TO ELECTRONIC SWITCHES,
 THE DOUBLE CHECK DETECTOR ASSEMBLIES
 SHALL BE SECURED WITH A CHAIN AND LOCK.
  
 17) AS NOTED ON SHT, A5.02, FIRE
 EXTINGUISHERS SHALL BE MOUNTED AT
 DISTANCES TO SATISFY THE 75' TRAVEL
 DISTANCE REQUIREMENT.
  
 18) ALL DOORS SHALL SWING IN THE
 DIRECTION OF TRAVEL WHEN SERVING AREAS
 WITH OCCUPANT LOADS OF GREATER THAN 50.
  
 19) ELEVATORS TO COMPLY WITH ASME A17.1.
  
 20) PENETRATIONS INTO , AND OPENINGS
 THROUGH STAIRWELLS SHALL BE LIMITED TO
 AND IN COMPLIANCE WITH NFPA 101, SECTION
 7.1.3.2.1 (6).
  
 21) PLEASE CLARIFY ALL EXIT DISCHARGING
 FROM STAIRWELLS THAT LEAD DIRECTLY TO
 THE OUTSIDE.
  
 22) SOME ACHITECTUAL DRAWINGS SHOW
 STAIRWELL DOORS, AND OTHERS DON'T.???
  
 23) THIS PERMIT APPLICATION PROCESS
 ILLUSTRATES 3 BUILDINGS AND OTHER
 BUILDINGS, 4&5 ARE SHOWN ON PLANS.
 PLEASE CLARIFY.
  
 24) PLEASE ILLUSTRATE THE TOTAL OCCUPANT
 LOAD FOR THE CLUBHOUSE.
  
 25) IN ADDITION TO THE ALREADY NOTED
 REQUIREMENTS FOR ADDRESSING, PLEASE NOTE
 THAT THE HEIGHT OF THE ADDRESS SHALL BE
 AT LEAST 3" IN HEIGHT FOR RESIDENTIAL
 BUILDINGS.
  
 26) PLEASE REFER TO DOOR SCHEDULE AND
 VERIFY CORRECT AMOUNT OF FIRE RATED
 DOORS. DOORS SERVINGS AREAS WITH
 OCCUPANT LOADS GREATER THAN 100 SHALL
 HAVE PANIC HARDWARE.
  
 27) FIRE PROTECTION SITE PLAN DOESN'T
 APPEAR COMPLETE ON SHT FP13.01.
  
 28) FIRE DEPARTMENT VALVES SHALL BE 2
 1/2" TO 1 1/2" REDUCER WITH CHAINS.
  
 29) MORE INFORMATION AND MANUFACTURER
 SPEC SHEETS REQUIRED FOR FIRE PUMP AND
 ASSOCIATED EQUIPMENT.
  
 30) FIRE PROTECTION SHEETS DON'T SHOW
 ANY FIRE SPRINKLER SYSTEM. ???? FIRE
 SPRINKLER DESIGN AND LAY OUT MUST BE
 ILLUSTRATED.
  
 31) IF A FIRE HYDRANT FLOW TEST HASN'T
 BEEN DONE WITHIN ONE YEAR, ANOTHER TEST
 WILL BE REQUIRED FOR FIRE SPRINKLER
 CALC. PLEASE CONTACT THE BUREAU OF FIRE
 PREVENTION AT (561) 805-4724.
  
 32) PLEASE INDICATE ALL SMOKE DETECTOR
 LOCATIONS IN ACCORDANCE WITH NFPA 101,
 SECTION 30.3.4.5.
  
 33) EXIT LIGHTS TO BE MOUNTED AT
 DISTANCES NOT TO EXCEED 100'. IT APPEARS
 THAT MORE EXIT SIGNS ARE NEEDED IN
 CORRIDORS.
  
 34) FIRE ALARM SHALL BE CLASS A, STYLE D
 OR FULLY ADDRESSABLE.
  
 35) ARE SMOKE DETECTORS TIED INTO THE
 FIRE ALARM SYSTEM PLANNED FOR CORRIDORS?
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  