| 2005-12-26 00:00:00 | ************ UNSAT ************ |
| | |
| | COURTNEY LAKES |
| | N. CONGRESS. |
| | |
| | |
| | 1)NOTE: PLEASE SUBMIT COMPLETED PLANS |
| | BOUND TOGETHER IN APPROPRIATE FASHION. |
| | PLEASE SEE ALL SHEETS WERE SUBMITTED |
| | LOOSELY AND NOT IN BOUND STES. |
| | |
| | 2)NOTE: PLEASE BE SURE ALL PLANS ARE |
| | SIGNED, DATED AND SEALED BY ALL DESIGN PROFESSIONALS AS |
| | REQUIRED UDNER FS |
| | 481.221 AND 471.025. |
| | (PLEASE SEE A-SHEETS, ONLY SIGNED). |
| | |
| | 3)NOTE: PLEASE BE SURE TO CORRECT THE |
| | CURRENT NEC/ NFPA-70 IN EFFECT. |
| | PLEASE KNOW, AS OF JULY 1ST, 2003 THE |
| | STATE OF FLORIDA ADOPTED THE 2002 |
| | NFPA-70 (NEC). PLANS REFERENCE 1999. |
| | PLEASE SEE SOME ELECTRICAL COMMENTS |
| | WHICH WILL AFFECT THIS. |
| | PLEASE SEE NEXT COMMENT WITH RESPECT TO |
| | PERMITS APPLIED FOR UNDER THE 2001 FBC |
| | BEFORE OCT 1ST, 2005 AND PERMITS ON OCT |
| | 1ST, 2005. |
| | |
| | 4)NOTE: PLEASESEE THAT THREE SEPARATE |
| | PERMIT APPLICATIONS WERE SUBMITTED AND |
| | NOTED FOR BLDG'S 1,2 AND 3, HOWEVER |
| | PLANS SHOWS BLDG TYPES 1.2&3 STRUCTUALLY |
| | ONLY ONE BUILDING. |
| | PLEASE SEE PERMIT APPLICATIONS ALL |
| | REFLECT THIS ONE 450 UNIT BLDG. |
| | PLEASE SEE THIS CONTRADICTS THE "PHASING |
| | PLAN" SUBMITTED ON A1.04 AS THIS PHASING |
| | PLAN INDICATES WORK ON BLDGS 4 AND 5 |
| | BEFORE COMPLETION OF BLDGS 1, 2 AND 3. |
| | PLEASE SEE COMMENTS FROM BLDG, FIRE AND |
| | OTHER REVIEWERS, ASCERTIFICATES OF |
| | OCCUPANCY(CO'S) FOR THESE CAN NOT BE |
| | GRANTED IN THIS ORDER AS THE FIRST |
| | "STRUCTURED BLDG"(1,2&3) WOULD NOT BE |
| | COMPLETE. |
| | PLEASE ALSO SEE COMMENTS WITH RESPECT TO "TEMPORARY |
| | CO'S" WHICH MAY ALLOW |
| | OCCUPANCY OF SOME PARTS OF BLDGS, |
| | HOWEVER THESE TCO'S ARE ONLY GOOD FOR 30 |
| | DAYS AND A MAX OF 3 TCO'S MAY ONLY BE |
| | GRANTED BY THE BLDG OFFICAL. |
| | PLEASE KNOW, IN ANY CASE, ALL LIFE |
| | SAFTEY, FIRE PROTECTION SYSTEMS, FIRE |
| | SPRINKLERS (FULLY CHARGED),ELECTRICAL |
| | SYSTEMS ETC SHALL BE COMPLETE IN THE |
| | BASE BLDG FOR BLDG TYPE 1, 2& 3 BEFORE A |
| | TCO,/CO CAN BE GRANTED. |
| | ************************************* |
| | ALSO NOTED THAT BLDG'S TYPE 4 AND 5 |
| | WHICH ARE SEPARATE STRUCTURES AND |
| | INDEPENDANT OF EACH OTHER WERE NOT |
| | SUBMITTED FOR PERMIT. |
| | PLEASE SEE ALL PERMITS SUBMITTED AFTER |
| | OCT. 1ST, 2005 SHALL FALL UNDER THE |
| | 2004 FBC, WITH ALL OTHER CODES ADOPTED |
| | BY SAID CODE AND STATE OF FLORIDA. |
| | ************************************ |
| | PLEASE SEE COMMENTS FROM OTHER |
| | REVIEWER(S) WITH RESPECT TO THIS. |
| | ************************************* |
| | PLEASE ALSO SEE NEXT COMMENT WITH |
| | RESPECT TO THE MAINS, SERVICES, AND |
| | METER RMS AS PROPOSED. |
| | ** SEE ALL NOTES FROM ALL REVIEWERS |
| | WHICH MAY ALSO AFFECT THIS SEQUENCE OF CONSTUCTION. |
| | |
| | 5)NOTE: PLEASE SEE METER RMS AS SHOWN |
| | WOULD BE OK, HOWEVER STRUCTURE AS SHOWN |
| | FOR BLDG TYPE 1,2 AND 3 (ONE BLDG) WOULD |
| | REQUIRE MAINS TO BE GROUPED. |
| | 90.4,230.2,230.70,230.72,230.76,230.79 |
| | ETC. |
| | BLDG'S LARGE ENOUGH TO CONTAIN MORE THAN |
| | ONE SERVICE AT SEPARATE LOCATIONS SHALL |
| | BE DIVIDED INTO SECTIONS AND SHALL HAVE |
| | THOSE SECTIONS DIVIDED BY "FIRE WALLS". |
| | PLEASE SEE FBC FOR DEFINITION OF "FIRE |
| | WALLS". |
| | PLEASE KNOW, STRUCTURE CONSTRUCTED AS |
| | SHOWN IN PLANS, WOULD REQUIRE MAIN |
| | DISCONNECTS GROUPED, WHICH WOULD THEN |
| | IN-TURN FEED METER ROOMS. |
| | OTHER DESIGN CHANGES IN THE "ONE BLDG" |
| | MAY ALSO PERMIT INDIVIDUAL SERVICES. |
| | PLEASE SEE BLDG TYPE #4 AND #5 ARE SHOWN |
| | AS SEPARATE BLDGS WITH STAND ALONE |
| | SERVICES AND ALL MAINS ARE GROUPED. |
| | PLEASE KNOW THAT BLDGS 4 AND 5 WILL HAVE |
| | REVIEWS DONE UNDER THOSE PERMIT |
| | APPLICATIONS. |
| | ** PLEASE SEE SOME OF THESE COMMENTS |
| | WOULD ALSO APPLY. |
| | |
| | 6)NOTE: PLEASE COMPLETE ALL CIRCUITING |
| | ON PLANS IN ORDER TO REVIEW CODE |
| | COMPLIANCEFOR AREAS OF UNITS AND |
| | COMMON AREAS. |
| | |
| | 7)NOTE: PLEASE PROVIDE ROOM AND AREA |
| | DESIGNATIONS ON PLANS, INCLUSIVE OF ALL |
| | UNITS AND COMMON AREAS. |
| | REVIEW FOR SOME CODE COMPLIANCE ITEMS |
| | CAN NOT BE DONE AT THIS TIME. |
| | |
| | 8)NOTE: PLEASE PROVIDE COMPLETE |
| | PHOTOMETRICS FOR ALL COMMON AREAS, |
| | GARAGE AREA,COMMON AREA CORRIDORS, |
| | STAIR TOWERS ETC. |
| | PLEASE SEE 2003 NFPA-101 7.8.1.3 AND |
| | 7.9.2 WHICH REQUIRES A MIN OF 10FT |
| | CANDLES FOR STAIR TOWERS UNDER NORMAL |
| | OPERATION AS WALK SURFACE AND A MIN OF |
| | 1FT CANDLE AT WALK SURFACE UNDER |
| | EMERGENCY CONDTIONS. PLEASE ALSO SEE |
| | OTHER WALK AREAS, GARAGE, CORRIDORS ETC |
| | AND THE MIN OF 1FT CANDLE. |
| | **PLEASE SEE PALM BEACH COUNTY SECURITY |
| | CODE ORDIANCE WITH RESPECT TO MIN DESIGN |
| | OF PARKING LOT LIGHTING LEVELS UNDER |
| | NORMAL CONDITIONS. (ONLY NOTED FOR |
| | DESIGN)NOT REQUIRED. PLEASE SEE ANY |
| | REQUIREMENTS FROM INS CARRIER WHICH |
| | REQUIE A MIN LEVEL OF LIGHTING. |
| | ** PLEASE SEE PHOTOMETRICS OR SITE PLAN |
| | WAS NOT SUBMITTED FOR PROPOSED POOL |
| | AREA. THE POOL STRUCTURE IS REQUIRED TO |
| | BE UNDER A SEPARATE PERMIT. PLEASE KNOW, |
| | THE PHOTOMETRICS FOR POOL AREA WILL BE |
| | REQUIRED AND WILL ALSO BE REQUIRED TO BE |
| | REVIEWED AND STAMPED BY THE PALM BEACH |
| | COUNTY HEALTH DEPT FOR ANY PROPOSED |
| | NIGHT-TIME SWIMMING. |
| | |
| | 7)NOTE: PLEASE SEE NO "ELECTRICAL |
| | SITE-PLAN" WAS SUBMITTED FOR ANY SITE |
| | LIGHTING, LANDSCAPE LIGHTING ETC. |
| | PLEASE KNOW, IF NOT SUBMITTED UNDER THIS |
| | PERMIT AND VALUES ADJUSTED ACCORDINGLY, |
| | SSEPARATE PERMIT , PLANS AND FEES WILL |
| | BE REQUIRED FOR ALL SITE LIGHTING, |
| | LANDSCAPE LIGHTING WORK. |
| | ** ALSO NOTE: IN THAT COMPLETE WIND |
| | LOADING CALCULATIONS FOR LT POLES |
| | INCLUSIVE FO THE ATTACHMENT OF LT |
| | FIXTURES WILL BE REQUIRED TO BE |
| | SUBMITTED WITH PLANS AND PERMIT |
| | APPLICATION FOR REVIEW. |
| | |
| | 8)NOTE: PLEASE INCLUDE AN EMERGENCY |
| | BATTERY BACK UP LT OF SOME SORT IN ALL |
| | ELECTRICAL ROOMS, FIRE PUMP ROOM, |
| | ELEVATOR MACHINE RMS. SOME ARE SHOWN, |
| | BUT NOT ALL. |
| | 7.8,7.9,700.16 ETC |
| | |
| | 9)NOTE: PLEASE SEE 620.23, AND 620.24 |
| | FOR REQUIRED DEDICATED BRANCH CIRCUITS |
| | FOR ELEVATOR PITS, AND ELEVATOR MACHINE RMS/EQUIPMENT |
| | AREAS. |
| | PLEASE ADJUST HOUSE PANELS AS NEEDED. |
| | |
| | 10)NOTE: PLEASE SEE ELECTRICAL RISER |
| | SHOULD "NOTE" FIRE PUMP AS DIESEL AS |
| | NOTED ON FP SHEETS. |
| | PLEASE SUBMIT ALL MANUAFCTURES SPEC/CUT |
| | SHEETS FOR FIRE PUMP CONTROLLER AS |
| | REVIEW FOR CODE COMPLIANCE UNDER 2002 |
| | NFPA-20 IS REQUIRED. |
| | PLEASE ALSO SUBMIT ALL MANUFACTURES |
| | SPECS/CUT SHEETS FOR FUEL TANK. |
| | PLEASE SEE NFPA-20 9.6.2.2 AS THE FUEL |
| | CAPACITY IS REQUIRED TO BE SIZED BASE ON |
| | THE 100% RATED LOAD FOR A MIN OF 8HRS, |
| | OT TIME SO DETERMIND BY THE FIRE |
| | MARSHAL'S OFFICE DEPENDING ON OCCUPANCY. |
| | FUEL SYSTEMS WILL BE UNDER OTHER TRADE |
| | REVIEW(S). (FIRE AND MECH). |
| | |
| | 11)NOTE: PLEASE INCLUDE ALL MIN |
| | CONDUCTOR SIZES ON ALL PANELS,UNITS AND |
| | HOUSE PANELS. REVIEW FOR THESE ITEMS OF |
| | CODE COMPLIANCE CAN NOT BE DONE AT THIS |
| | TIME. 310.16,240.4,215.5 |
| | |
| | 12)NOTE: PLEASE SEE GARAGE/HOUSE |
| | LIGHTING BEING INDICATED ON 30A AND 50A |
| | CIRCUITS. |
| | PLEASE SEE CODE DOES LIMIT THE OCP FOR |
| | UNIT FIXTURES FOR PROTECTION OF FIXTURES |
| | ON A BRANCH CIRCUIT. |
| | PLEASE ADJUST CIRCUITING AS NEEDED. |
| | PLEASE ALSO SEE A FIXTURE SCHEDULE |
| | CONTAINING WATTAGES, VOLTAGES ETC WAS |
| | NOT SUBMITTED. |
| | PLEASE VERIFY IF THESE UNIT FIXTURES ARE |
| | RATED TO HAVE OCP AT ABOVE MENTIONED. |
| | 240.4, 310.16 ETC |
| | |
| | 13)NOTE: PLEASE CORRELATE ALL OCP |
| | DEVICES FOR UNITS AND FEEDERS BEING |
| | LISTED IN "RISER NOTES". |
| | PLEASE SEE SOME FEEDERS SHOWN AS #4'S ON |
| | 125A BREAKER? |
| | SEE 310.16,240.4 |
| | PLEASE SEE OCP FOR ALL UNITS IS LISTED |
| | AS 125A'S. |
| | SEE NEXT COMMENT. |
| | |
| | 14)NOTE: PLEASE SEE MAX OCP TO BE SIZED |
| | FOR PANELS/EQUIPMNET BEING FED BY SAID |
| | OCP. |
| | PLEASE SEE MANY UNIT PANELS ARE SHOWN AS |
| | 100A MLO, WITH 125A OCP AS LISTED ON |
| | RISER ETC. |
| | PLEASE ALSO SEE RISER NOTE #4 WHICH |
| | INDICATES 125A 2-POLE ETC, HOWEVER |
| | PLEASE SEE RISER AS THIS NOTE #4 COULD |
| | NOT BE LOCATED. (APPEARS TO BE |
| | MISPRINTED FOR "NOTE#7" ON RISER) |
| | 240.4,408,310.16,215.5 ETC. |
| | |
| | 15)NOTE: PLEASE SEE 16.26 AND 16.27 |
| | WHICH CONTAIN THE SAME EXACT "HOUSE |
| | PANELS" ?? H1, H1A , H2, AND H2A. |
| | PLEASE SEE SHEET 16.27 MAY BE DELETED IF |
| | PANELSCHEDULES FOR "CA" AND"CB" ARE |
| | MOVED TO 16.26. |
| | |
| | 16)NOTE: PLEASE CORRELATE LOADS SHOWN |
| | FOR H1A WITH LOAD SHOWN ON H1. |
| | THIS DOES NOT MATCH. |
| | |
| | 17)NOTE: PLEASE CORRELATE LOADS ON PANEL |
| | H2A WITH LOADS SHOWN ON H2> |
| | THESE ALSO DO NOT MATCH. |
| | |
| | 18)NOTE: PLEASE SEE THESE SHEETS ALSO |
| | REFERENCE "ARC FAULT" PROTECTION FROM |
| | THE 1999 NEC, WHICH ONLY REQUIRED |
| | PROTECTION OF RECEPTS. |
| | PLEASE SEE 2002 NEC WHICH REQUIRES |
| | PROTECTION FOR ALL "OUTLETS" IN BEDRMS. |
| | THIS IS INCLUSIVE OF RECEPTS, LTS, FANS, |
| | SMOKE DETECTORS ETC. |
| | PLEASE SEE NOTE ON UNIT PLANS AND |
| | ADJUST. |
| | |
| | 19)NOTE: PLEASE CORRELATE LOADS , UNITS, |
| | PANELS, AND BUILDING/METER LOAD |
| | CALCULATIONS: |
| | A) PLEASE SEE PANEL SCHEDULE/LOAD |
| | CALCULATIONS FOR UNIT "B-3" SHOWN ON |
| | 16.26, HOWEVER THIS UNIT TYPE OR LOADS |
| | COULD NOT BE LOCATED ON BLDG LOAD |
| | CALCULATIONS ON 16.25? |
| | B)PLEASE ALSO SEE THE SAME COMMENT ABOVE |
| | FOR UNIT "C-2" WHICH IS ALSO SHOWN ON |
| | 16.26 BUT NOT IN CALCS ON 16.25?? |
| | ** PLEASE ADJUST ALL AS NEEDED. |
| | |
| | 20)NOTE: PLEASE INCLUDE THE REQUIRED |
| | FOOTER STEEL ON THE GROUNDING ELECTRODE |
| | RISER DETAIL. |
| | PLEASE ALSO SHOW ON RISER. |
| | 250.50. |
| | |
| | 21)NOTE: PLEASE PROVIDE A DETAIL/NOTE |
| | FOR ALL RACEWAY SEALS AS REQUIRED PER |
| | 230.8 |
| | |
| | 22)NOTE: PLEASE SEE RISER WHICH SHOWS A |
| | POOL PANEL BEING FED FROM PANEL "CA", |
| | HOWEVER PANEL "CA" , DOES NOT SHOW SUCH |
| | PANEL. |
| | 215.5 |
| | |
| | 23)NOTE: PLEASE PROVIDE "FUTURE" POOL |
| | PANEL ON RISER AND PANEL SCHEDULE. |
| | 215.5 |
| | |
| | 24)NOTE: PLEASE SEE RISER NOTE #12 WHICH |
| | IS SHOWN FOR FEED FROM PANEL "CA" TO |
| | PANEL "CB". THIS IS SHOWN AS 500MCM'S, |
| | ALTHOUGH OCP ON CA IS ONLY SHOWN AS |
| | 200A'S? THIS IS PERMITTED, HOWEVER THE |
| | 200A DEVICE MAY NOT ACCEPT 500MCM'S. |
| | 215.5 |
| | |
| | 25)NOTE: PLEASE SEE REDLINED ITEMS ON |
| | PLANS FOR "EQUIPMENT GROUNDING |
| | CONDUCTORS" BEING SHOWN BEFORE THE FIRST |
| | MEANS OF DISCONNECT. |
| | PLEASE SEE 250.6, 250.24. |
| | PLEASE SEE HOUSE METER #2, SEE RISER |
| | NOTE #12 AND #13 SHOWS AN "EQUIPMENT |
| | GROUNDING" CONDUCTOR WHICH IS |
| | PARALLELING THE NEUTRAL. |
| | |
| | 26)NOTE: PLEASE SEE MIN OCP FOR WATER |
| | HEATERS TO BE SIZED AT 125%.424.13 |
| | PLEASE SEE UNITS CONTAINING 5KW WH @ |
| | 208V'S WOULD INCREASE THIS BRKR TO A |
| | 2-P35A. PLEASE ALSO ADJUST ANY AWG PER 310.16,240.4 |
| | |
| | 27)NOTE: PLEASE SEE UNIT LOAD |
| | CALCULATIONS SHOWS THE LOADS FOR A/C'S |
| | AFTER THE PERMITTED DERATING, HOWEVER |
| | PLEASE SHOWLOADS FOR THESE BEFORE |
| | DERATING. |
| | PLEASE BE SURE TO CORRELATE WITH LOADS |
| | FOR COOLING AND HEAT ON MECHANICAL PLAN. |
| | 215.5 |
| | |
| | 28)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | PLEASE SEE 2002 NFPA-72 11.5.3.1 |
| | PLEASE ADJUST NOTE FOR SD'S ON PLANS AS |
| | SD'S ARE REQUIRED 3' FROM BATH/KTICHEN |
| | DOORS, 3' FROM SUPPLY AIR DIFFUSERS, 5' |
| | FROM R/A GRILLES AND 20' FROM KITCHEN |
| | COOKING APPLIANCES. W/ EXCEPTIONS FOR |
| | DISTANCES FROM COOKING APPLIANCES. |
| | (PHOTOELECTRIC AND RESETTING TYPE) |
| | ** PLEASE SEE PRIVIOUS NOTES WITH |
| | RESPECT TO ARC FAULT PROTECTION OF SD'S |
| | AND CIRCUTING. |
| | |
| | 29)NOTE: PLEASE SEE ALL RECEPTS IN |
| | CLUBHOUSE KITCHEN PER 210.8B3 WHICH |
| | REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT RECEPTACLES IN |
| | NONDWELLING-TYPE KITCHENS |
| | TO BE GFCI PROTECTED. THIS REQUIREMENT |
| | APPLIES TO EACH AND EVERY 15- AND |
| | 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE, |
| | WHETHER OR NOT THE RECEPTACLE SERVES |
| | COUNTERTOP APPLIANCES. |
| | |
| | 30)NOTE: PLEASE SEE 700.12E FOR |
| | CIRCUITING OF ALL EM/EXT LTS, WHICH |
| | REQUIRES THE BRANCH CIRCUIT FEEDING THE |
| | UNIT EQUIPMENT SHALL BE THE SAME BRANCH |
| | CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD |
| | OF ANY LOCAL SWITCHES. |
| | THIS IS NOTED ON SOME SHEETS, HOWEVER |
| | CIRCUITING FOR THESE IS NOT SHOWN. |
| | 215.5 |
| | |
| | 31)NOTE: PLEASE CLARIFY THE "CT" AS |
| | LABLED ALONG KITCHEN RECEPTS. THIS |
| | ABBREVIATION COULD NOT BE LOCATED ON |
| | SYMBOL LEGEND? |
| | |
| | 32)NOTE: PLEASE SEE 210.52C1-C5 FOR |
| | REQUIRED GFI RECEPTS ALONG KTICHEN |
| | COUNTERSPACE. PLEASE SEE SOME ARE SHOWN |
| | ON WHAT APPEARS TO BE A WALL ON THE |
| | OTHER SIDE OF THE COUNTERSPACE. |
| | PLEASE SEE B-2, B-4ETC. |
| | PLEASE SEE OTHER WHICH ARE REQUIRED TO |
| | BE WITHIN 2' OF THE END OF THE |
| | COUNTERSPACE/FROM SINK EDGE ETC. |
| | PLEASE SEE THESE AREAS REDLINED ON |
| | SHEETS. |
| | |
| | 33)NOTE: PLEASE SEE WHAT APPEARS TO BE A |
| | RECEPT LOCATED IN THE CLOTHES CLOSET FOR |
| | PERHAPS A LV PLUG-IN TYPE TRANSFORMER? |
| | PLEASE KNOW, THE ONLY LOCATION A RECEPT |
| | IS PERMITTED IN A CLOTHES CLOSET FOR |
| | THIS PURPOSE, MUST BE LOCATED DIRECTLY |
| | ABOVE DOOR AWAY FROM COMBUSTIBLES. |
| | MANY PLUG-IN TYPE TRANSFORMERS BECOME |
| | VERY HOT AND HAVE MELTED OR CAUSED FIRES |
| | IN THIS JURISTICTION. PLEASE KNOW, MANY |
| | ITEMS IN A CLOTHES CLOSET ARE AN |
| | ACCELERANT. |
| | THESE RECEPTS MAY BE MOVED TO UTILITY RM |
| | IS SO DESIRED. |
| | 110.26, 240.24, 90.4 ETC |
| | |
| | 34)NOTE: PLEASE SEE RELDINED PLANS FOR |
| | ANY RECEPTS WHICH MAY BE REQUIRED PER |
| | 210.52 (A-2). MOST ALL SPACING IS OK. |
| | |
| | 35)NOTE: PLEASE MAKE NOTE FOR ALL MIN |
| | FAIR HOUSING ACT REQUIREMENTS FOR DEVICE |
| | HEIGHTS. |
| | 24 CFR 100.205 |
| | |
| | ** PLEASE KNOW, SOME REVIEW OF CODE |
| | COMPLIANT ITEMS MAY NOT BE DONE AT THIS |
| | TIME DUE TO SOME INFORMATION NOT ON |
| | PLANS. |
| | |
| | ** PLEASE SEE ANY COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH MAY HAVE AN AFFETC ON |
| | ELECTRICAL PLANS. |
| | |
| | ** PLEASE KNOW, A TYPE WRITTEN RESPONSE |
| | LETTER FROM DESIGN PROFESSIONL(S) FOR |
| | EACH COMMENT ON HOW/WHERE CORRECTIONS |
| | ARE MADE OR IF COMMENTS ON REVIEW WILL |
| | HELP IN EXPEDITING THE PLAN REVIEW |
| | PROCESS. |
| | |
| | ** PLEASE KNOW THAT A MEETING TO GO OVER |
| | FIRST COMMENTS FOR DESIGN/PHASING OF |
| | BLDGWITH ALL REVIEWERS IS SUGGESTED |
| | BEFORE PERHAPS SUBMITTING PLANS BACK FOR |
| | REVIEW. |
| | PLEASE KNOW, ALL REVIEWS AFTER THE 1ST |
| | FREE "RE-SUB" IS SUBJECT TO A 10% RESUB |
| | FEE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| 2005-12-25 00:00:00 | ONE ROLL IN ELECTRIC FOR REVIEW. |