Plan Review Notes
Plan Review Notes For Permit 05091687
Permit Number 05091687
Review Stop E
Sequence Number 1
Notes
Date Text
2005-12-26 00:00:00************ UNSAT ************
  
 COURTNEY LAKES
 N. CONGRESS.
  
  
 1)NOTE: PLEASE SUBMIT COMPLETED PLANS
 BOUND TOGETHER IN APPROPRIATE FASHION.
 PLEASE SEE ALL SHEETS WERE SUBMITTED
 LOOSELY AND NOT IN BOUND STES.
  
 2)NOTE: PLEASE BE SURE ALL PLANS ARE
 SIGNED, DATED AND SEALED BY ALL DESIGN PROFESSIONALS AS
 REQUIRED UDNER FS
 481.221 AND 471.025.
 (PLEASE SEE A-SHEETS, ONLY SIGNED).
  
 3)NOTE: PLEASE BE SURE TO CORRECT THE
 CURRENT NEC/ NFPA-70 IN EFFECT.
 PLEASE KNOW, AS OF JULY 1ST, 2003 THE
 STATE OF FLORIDA ADOPTED THE 2002
 NFPA-70 (NEC). PLANS REFERENCE 1999.
 PLEASE SEE SOME ELECTRICAL COMMENTS
 WHICH WILL AFFECT THIS.
 PLEASE SEE NEXT COMMENT WITH RESPECT TO
 PERMITS APPLIED FOR UNDER THE 2001 FBC
 BEFORE OCT 1ST, 2005 AND PERMITS ON OCT
 1ST, 2005.
  
 4)NOTE: PLEASESEE THAT THREE SEPARATE
 PERMIT APPLICATIONS WERE SUBMITTED AND
 NOTED FOR BLDG'S 1,2 AND 3, HOWEVER
 PLANS SHOWS BLDG TYPES 1.2&3 STRUCTUALLY
 ONLY ONE BUILDING.
 PLEASE SEE PERMIT APPLICATIONS ALL
 REFLECT THIS ONE 450 UNIT BLDG.
 PLEASE SEE THIS CONTRADICTS THE "PHASING
 PLAN" SUBMITTED ON A1.04 AS THIS PHASING
 PLAN INDICATES WORK ON BLDGS 4 AND 5
 BEFORE COMPLETION OF BLDGS 1, 2 AND 3.
 PLEASE SEE COMMENTS FROM BLDG, FIRE AND
 OTHER REVIEWERS, ASCERTIFICATES OF
 OCCUPANCY(CO'S) FOR THESE CAN NOT BE
 GRANTED IN THIS ORDER AS THE FIRST
 "STRUCTURED BLDG"(1,2&3) WOULD NOT BE
 COMPLETE.
 PLEASE ALSO SEE COMMENTS WITH RESPECT TO "TEMPORARY
 CO'S" WHICH MAY ALLOW
 OCCUPANCY OF SOME PARTS OF BLDGS,
 HOWEVER THESE TCO'S ARE ONLY GOOD FOR 30
 DAYS AND A MAX OF 3 TCO'S MAY ONLY BE
 GRANTED BY THE BLDG OFFICAL.
 PLEASE KNOW, IN ANY CASE, ALL LIFE
 SAFTEY, FIRE PROTECTION SYSTEMS, FIRE
 SPRINKLERS (FULLY CHARGED),ELECTRICAL
 SYSTEMS ETC SHALL BE COMPLETE IN THE
 BASE BLDG FOR BLDG TYPE 1, 2& 3 BEFORE A
 TCO,/CO CAN BE GRANTED.
 *************************************
 ALSO NOTED THAT BLDG'S TYPE 4 AND 5
 WHICH ARE SEPARATE STRUCTURES AND
 INDEPENDANT OF EACH OTHER WERE NOT
 SUBMITTED FOR PERMIT.
 PLEASE SEE ALL PERMITS SUBMITTED AFTER
 OCT. 1ST, 2005 SHALL FALL UNDER THE
 2004 FBC, WITH ALL OTHER CODES ADOPTED
 BY SAID CODE AND STATE OF FLORIDA.
 ************************************
 PLEASE SEE COMMENTS FROM OTHER
 REVIEWER(S) WITH RESPECT TO THIS.
 *************************************
 PLEASE ALSO SEE NEXT COMMENT WITH
 RESPECT TO THE MAINS, SERVICES, AND
 METER RMS AS PROPOSED.
 ** SEE ALL NOTES FROM ALL REVIEWERS
 WHICH MAY ALSO AFFECT THIS SEQUENCE OF CONSTUCTION.
  
 5)NOTE: PLEASE SEE METER RMS AS SHOWN
 WOULD BE OK, HOWEVER STRUCTURE AS SHOWN
 FOR BLDG TYPE 1,2 AND 3 (ONE BLDG) WOULD
 REQUIRE MAINS TO BE GROUPED.
 90.4,230.2,230.70,230.72,230.76,230.79
 ETC.
 BLDG'S LARGE ENOUGH TO CONTAIN MORE THAN
 ONE SERVICE AT SEPARATE LOCATIONS SHALL
 BE DIVIDED INTO SECTIONS AND SHALL HAVE
 THOSE SECTIONS DIVIDED BY "FIRE WALLS".
 PLEASE SEE FBC FOR DEFINITION OF "FIRE
 WALLS".
 PLEASE KNOW, STRUCTURE CONSTRUCTED AS
 SHOWN IN PLANS, WOULD REQUIRE MAIN
 DISCONNECTS GROUPED, WHICH WOULD THEN
 IN-TURN FEED METER ROOMS.
 OTHER DESIGN CHANGES IN THE "ONE BLDG"
 MAY ALSO PERMIT INDIVIDUAL SERVICES.
 PLEASE SEE BLDG TYPE #4 AND #5 ARE SHOWN
 AS SEPARATE BLDGS WITH STAND ALONE
 SERVICES AND ALL MAINS ARE GROUPED.
 PLEASE KNOW THAT BLDGS 4 AND 5 WILL HAVE
 REVIEWS DONE UNDER THOSE PERMIT
 APPLICATIONS.
 ** PLEASE SEE SOME OF THESE COMMENTS
 WOULD ALSO APPLY.
  
 6)NOTE: PLEASE COMPLETE ALL CIRCUITING
 ON PLANS IN ORDER TO REVIEW CODE
 COMPLIANCEFOR AREAS OF UNITS AND
 COMMON AREAS.
  
 7)NOTE: PLEASE PROVIDE ROOM AND AREA
 DESIGNATIONS ON PLANS, INCLUSIVE OF ALL
 UNITS AND COMMON AREAS.
 REVIEW FOR SOME CODE COMPLIANCE ITEMS
 CAN NOT BE DONE AT THIS TIME.
  
 8)NOTE: PLEASE PROVIDE COMPLETE
 PHOTOMETRICS FOR ALL COMMON AREAS,
 GARAGE AREA,COMMON AREA CORRIDORS,
 STAIR TOWERS ETC.
 PLEASE SEE 2003 NFPA-101 7.8.1.3 AND
 7.9.2 WHICH REQUIRES A MIN OF 10FT
 CANDLES FOR STAIR TOWERS UNDER NORMAL
 OPERATION AS WALK SURFACE AND A MIN OF
 1FT CANDLE AT WALK SURFACE UNDER
 EMERGENCY CONDTIONS. PLEASE ALSO SEE
 OTHER WALK AREAS, GARAGE, CORRIDORS ETC
 AND THE MIN OF 1FT CANDLE.
 **PLEASE SEE PALM BEACH COUNTY SECURITY
 CODE ORDIANCE WITH RESPECT TO MIN DESIGN
 OF PARKING LOT LIGHTING LEVELS UNDER
 NORMAL CONDITIONS. (ONLY NOTED FOR
 DESIGN)NOT REQUIRED. PLEASE SEE ANY
 REQUIREMENTS FROM INS CARRIER WHICH
 REQUIE A MIN LEVEL OF LIGHTING.
 ** PLEASE SEE PHOTOMETRICS OR SITE PLAN
 WAS NOT SUBMITTED FOR PROPOSED POOL
 AREA. THE POOL STRUCTURE IS REQUIRED TO
 BE UNDER A SEPARATE PERMIT. PLEASE KNOW,
 THE PHOTOMETRICS FOR POOL AREA WILL BE
 REQUIRED AND WILL ALSO BE REQUIRED TO BE
 REVIEWED AND STAMPED BY THE PALM BEACH
 COUNTY HEALTH DEPT FOR ANY PROPOSED
 NIGHT-TIME SWIMMING.
  
 7)NOTE: PLEASE SEE NO "ELECTRICAL
 SITE-PLAN" WAS SUBMITTED FOR ANY SITE
 LIGHTING, LANDSCAPE LIGHTING ETC.
 PLEASE KNOW, IF NOT SUBMITTED UNDER THIS
 PERMIT AND VALUES ADJUSTED ACCORDINGLY,
 SSEPARATE PERMIT , PLANS AND FEES WILL
 BE REQUIRED FOR ALL SITE LIGHTING,
 LANDSCAPE LIGHTING WORK.
 ** ALSO NOTE: IN THAT COMPLETE WIND
 LOADING CALCULATIONS FOR LT POLES
 INCLUSIVE FO THE ATTACHMENT OF LT
 FIXTURES WILL BE REQUIRED TO BE
 SUBMITTED WITH PLANS AND PERMIT
 APPLICATION FOR REVIEW.
  
 8)NOTE: PLEASE INCLUDE AN EMERGENCY
 BATTERY BACK UP LT OF SOME SORT IN ALL
 ELECTRICAL ROOMS, FIRE PUMP ROOM,
 ELEVATOR MACHINE RMS. SOME ARE SHOWN,
 BUT NOT ALL.
 7.8,7.9,700.16 ETC
  
 9)NOTE: PLEASE SEE 620.23, AND 620.24
 FOR REQUIRED DEDICATED BRANCH CIRCUITS
 FOR ELEVATOR PITS, AND ELEVATOR MACHINE RMS/EQUIPMENT
 AREAS.
 PLEASE ADJUST HOUSE PANELS AS NEEDED.
  
 10)NOTE: PLEASE SEE ELECTRICAL RISER
 SHOULD "NOTE" FIRE PUMP AS DIESEL AS
 NOTED ON FP SHEETS.
 PLEASE SUBMIT ALL MANUAFCTURES SPEC/CUT
 SHEETS FOR FIRE PUMP CONTROLLER AS
 REVIEW FOR CODE COMPLIANCE UNDER 2002
 NFPA-20 IS REQUIRED.
 PLEASE ALSO SUBMIT ALL MANUFACTURES
 SPECS/CUT SHEETS FOR FUEL TANK.
 PLEASE SEE NFPA-20 9.6.2.2 AS THE FUEL
 CAPACITY IS REQUIRED TO BE SIZED BASE ON
 THE 100% RATED LOAD FOR A MIN OF 8HRS,
 OT TIME SO DETERMIND BY THE FIRE
 MARSHAL'S OFFICE DEPENDING ON OCCUPANCY.
 FUEL SYSTEMS WILL BE UNDER OTHER TRADE
 REVIEW(S). (FIRE AND MECH).
  
 11)NOTE: PLEASE INCLUDE ALL MIN
 CONDUCTOR SIZES ON ALL PANELS,UNITS AND
 HOUSE PANELS. REVIEW FOR THESE ITEMS OF
 CODE COMPLIANCE CAN NOT BE DONE AT THIS
 TIME. 310.16,240.4,215.5
  
 12)NOTE: PLEASE SEE GARAGE/HOUSE
 LIGHTING BEING INDICATED ON 30A AND 50A
 CIRCUITS.
 PLEASE SEE CODE DOES LIMIT THE OCP FOR
 UNIT FIXTURES FOR PROTECTION OF FIXTURES
 ON A BRANCH CIRCUIT.
 PLEASE ADJUST CIRCUITING AS NEEDED.
 PLEASE ALSO SEE A FIXTURE SCHEDULE
 CONTAINING WATTAGES, VOLTAGES ETC WAS
 NOT SUBMITTED.
 PLEASE VERIFY IF THESE UNIT FIXTURES ARE
 RATED TO HAVE OCP AT ABOVE MENTIONED.
 240.4, 310.16 ETC
  
 13)NOTE: PLEASE CORRELATE ALL OCP
 DEVICES FOR UNITS AND FEEDERS BEING
 LISTED IN "RISER NOTES".
 PLEASE SEE SOME FEEDERS SHOWN AS #4'S ON
 125A BREAKER?
 SEE 310.16,240.4
 PLEASE SEE OCP FOR ALL UNITS IS LISTED
 AS 125A'S.
 SEE NEXT COMMENT.
  
 14)NOTE: PLEASE SEE MAX OCP TO BE SIZED
 FOR PANELS/EQUIPMNET BEING FED BY SAID
 OCP.
 PLEASE SEE MANY UNIT PANELS ARE SHOWN AS
 100A MLO, WITH 125A OCP AS LISTED ON
 RISER ETC.
 PLEASE ALSO SEE RISER NOTE #4 WHICH
 INDICATES 125A 2-POLE ETC, HOWEVER
 PLEASE SEE RISER AS THIS NOTE #4 COULD
 NOT BE LOCATED. (APPEARS TO BE
 MISPRINTED FOR "NOTE#7" ON RISER)
 240.4,408,310.16,215.5 ETC.
  
 15)NOTE: PLEASE SEE 16.26 AND 16.27
 WHICH CONTAIN THE SAME EXACT "HOUSE
 PANELS" ?? H1, H1A , H2, AND H2A.
 PLEASE SEE SHEET 16.27 MAY BE DELETED IF
 PANELSCHEDULES FOR "CA" AND"CB" ARE
 MOVED TO 16.26.
  
 16)NOTE: PLEASE CORRELATE LOADS SHOWN
 FOR H1A WITH LOAD SHOWN ON H1.
 THIS DOES NOT MATCH.
  
 17)NOTE: PLEASE CORRELATE LOADS ON PANEL
 H2A WITH LOADS SHOWN ON H2>
 THESE ALSO DO NOT MATCH.
  
 18)NOTE: PLEASE SEE THESE SHEETS ALSO
 REFERENCE "ARC FAULT" PROTECTION FROM
 THE 1999 NEC, WHICH ONLY REQUIRED
 PROTECTION OF RECEPTS.
 PLEASE SEE 2002 NEC WHICH REQUIRES
 PROTECTION FOR ALL "OUTLETS" IN BEDRMS.
 THIS IS INCLUSIVE OF RECEPTS, LTS, FANS,
 SMOKE DETECTORS ETC.
 PLEASE SEE NOTE ON UNIT PLANS AND
 ADJUST.
  
 19)NOTE: PLEASE CORRELATE LOADS , UNITS,
 PANELS, AND BUILDING/METER LOAD
 CALCULATIONS:
 A) PLEASE SEE PANEL SCHEDULE/LOAD
 CALCULATIONS FOR UNIT "B-3" SHOWN ON
 16.26, HOWEVER THIS UNIT TYPE OR LOADS
 COULD NOT BE LOCATED ON BLDG LOAD
 CALCULATIONS ON 16.25?
 B)PLEASE ALSO SEE THE SAME COMMENT ABOVE
 FOR UNIT "C-2" WHICH IS ALSO SHOWN ON
 16.26 BUT NOT IN CALCS ON 16.25??
 ** PLEASE ADJUST ALL AS NEEDED.
  
 20)NOTE: PLEASE INCLUDE THE REQUIRED
 FOOTER STEEL ON THE GROUNDING ELECTRODE
 RISER DETAIL.
 PLEASE ALSO SHOW ON RISER.
 250.50.
  
 21)NOTE: PLEASE PROVIDE A DETAIL/NOTE
 FOR ALL RACEWAY SEALS AS REQUIRED PER
 230.8
  
 22)NOTE: PLEASE SEE RISER WHICH SHOWS A
 POOL PANEL BEING FED FROM PANEL "CA",
 HOWEVER PANEL "CA" , DOES NOT SHOW SUCH
 PANEL.
 215.5
  
 23)NOTE: PLEASE PROVIDE "FUTURE" POOL
 PANEL ON RISER AND PANEL SCHEDULE.
 215.5
  
 24)NOTE: PLEASE SEE RISER NOTE #12 WHICH
 IS SHOWN FOR FEED FROM PANEL "CA" TO
 PANEL "CB". THIS IS SHOWN AS 500MCM'S,
 ALTHOUGH OCP ON CA IS ONLY SHOWN AS
 200A'S? THIS IS PERMITTED, HOWEVER THE
 200A DEVICE MAY NOT ACCEPT 500MCM'S.
 215.5
  
 25)NOTE: PLEASE SEE REDLINED ITEMS ON
 PLANS FOR "EQUIPMENT GROUNDING
 CONDUCTORS" BEING SHOWN BEFORE THE FIRST
 MEANS OF DISCONNECT.
 PLEASE SEE 250.6, 250.24.
 PLEASE SEE HOUSE METER #2, SEE RISER
 NOTE #12 AND #13 SHOWS AN "EQUIPMENT
 GROUNDING" CONDUCTOR WHICH IS
 PARALLELING THE NEUTRAL.
  
 26)NOTE: PLEASE SEE MIN OCP FOR WATER
 HEATERS TO BE SIZED AT 125%.424.13
 PLEASE SEE UNITS CONTAINING 5KW WH @
 208V'S WOULD INCREASE THIS BRKR TO A
 2-P35A. PLEASE ALSO ADJUST ANY AWG PER 310.16,240.4
  
 27)NOTE: PLEASE SEE UNIT LOAD
 CALCULATIONS SHOWS THE LOADS FOR A/C'S
 AFTER THE PERMITTED DERATING, HOWEVER
 PLEASE SHOWLOADS FOR THESE BEFORE
 DERATING.
 PLEASE BE SURE TO CORRELATE WITH LOADS
 FOR COOLING AND HEAT ON MECHANICAL PLAN.
 215.5
  
 28)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 PLEASE SEE 2002 NFPA-72 11.5.3.1
 PLEASE ADJUST NOTE FOR SD'S ON PLANS AS
 SD'S ARE REQUIRED 3' FROM BATH/KTICHEN
 DOORS, 3' FROM SUPPLY AIR DIFFUSERS, 5'
 FROM R/A GRILLES AND 20' FROM KITCHEN
 COOKING APPLIANCES. W/ EXCEPTIONS FOR
 DISTANCES FROM COOKING APPLIANCES.
 (PHOTOELECTRIC AND RESETTING TYPE)
 ** PLEASE SEE PRIVIOUS NOTES WITH
 RESPECT TO ARC FAULT PROTECTION OF SD'S
 AND CIRCUTING.
  
 29)NOTE: PLEASE SEE ALL RECEPTS IN
 CLUBHOUSE KITCHEN PER 210.8B3 WHICH
 REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT RECEPTACLES IN
 NONDWELLING-TYPE KITCHENS
 TO BE GFCI PROTECTED. THIS REQUIREMENT
 APPLIES TO EACH AND EVERY 15- AND
 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE,
 WHETHER OR NOT THE RECEPTACLE SERVES
 COUNTERTOP APPLIANCES.
  
 30)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF ALL EM/EXT LTS, WHICH
 REQUIRES THE BRANCH CIRCUIT FEEDING THE
 UNIT EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 THIS IS NOTED ON SOME SHEETS, HOWEVER
 CIRCUITING FOR THESE IS NOT SHOWN.
 215.5
  
 31)NOTE: PLEASE CLARIFY THE "CT" AS
 LABLED ALONG KITCHEN RECEPTS. THIS
 ABBREVIATION COULD NOT BE LOCATED ON
 SYMBOL LEGEND?
  
 32)NOTE: PLEASE SEE 210.52C1-C5 FOR
 REQUIRED GFI RECEPTS ALONG KTICHEN
 COUNTERSPACE. PLEASE SEE SOME ARE SHOWN
 ON WHAT APPEARS TO BE A WALL ON THE
 OTHER SIDE OF THE COUNTERSPACE.
 PLEASE SEE B-2, B-4ETC.
 PLEASE SEE OTHER WHICH ARE REQUIRED TO
 BE WITHIN 2' OF THE END OF THE
 COUNTERSPACE/FROM SINK EDGE ETC.
 PLEASE SEE THESE AREAS REDLINED ON
 SHEETS.
  
 33)NOTE: PLEASE SEE WHAT APPEARS TO BE A
 RECEPT LOCATED IN THE CLOTHES CLOSET FOR
 PERHAPS A LV PLUG-IN TYPE TRANSFORMER?
 PLEASE KNOW, THE ONLY LOCATION A RECEPT
 IS PERMITTED IN A CLOTHES CLOSET FOR
 THIS PURPOSE, MUST BE LOCATED DIRECTLY
 ABOVE DOOR AWAY FROM COMBUSTIBLES.
 MANY PLUG-IN TYPE TRANSFORMERS BECOME
 VERY HOT AND HAVE MELTED OR CAUSED FIRES
 IN THIS JURISTICTION. PLEASE KNOW, MANY
 ITEMS IN A CLOTHES CLOSET ARE AN
 ACCELERANT.
 THESE RECEPTS MAY BE MOVED TO UTILITY RM
 IS SO DESIRED.
 110.26, 240.24, 90.4 ETC
  
 34)NOTE: PLEASE SEE RELDINED PLANS FOR
 ANY RECEPTS WHICH MAY BE REQUIRED PER
 210.52 (A-2). MOST ALL SPACING IS OK.
  
 35)NOTE: PLEASE MAKE NOTE FOR ALL MIN
 FAIR HOUSING ACT REQUIREMENTS FOR DEVICE
 HEIGHTS.
 24 CFR 100.205
  
 ** PLEASE KNOW, SOME REVIEW OF CODE
 COMPLIANT ITEMS MAY NOT BE DONE AT THIS
 TIME DUE TO SOME INFORMATION NOT ON
 PLANS.
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY HAVE AN AFFETC ON
 ELECTRICAL PLANS.
  
 ** PLEASE KNOW, A TYPE WRITTEN RESPONSE
 LETTER FROM DESIGN PROFESSIONL(S) FOR
 EACH COMMENT ON HOW/WHERE CORRECTIONS
 ARE MADE OR IF COMMENTS ON REVIEW WILL
 HELP IN EXPEDITING THE PLAN REVIEW
 PROCESS.
  
 ** PLEASE KNOW THAT A MEETING TO GO OVER
 FIRST COMMENTS FOR DESIGN/PHASING OF
 BLDGWITH ALL REVIEWERS IS SUGGESTED
 BEFORE PERHAPS SUBMITTING PLANS BACK FOR
 REVIEW.
 PLEASE KNOW, ALL REVIEWS AFTER THE 1ST
 FREE "RE-SUB" IS SUBJECT TO A 10% RESUB
 FEE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
2005-12-25 00:00:00ONE ROLL IN ELECTRIC FOR REVIEW.