Plan Review Notes
Plan Review Notes For Permit 05091686
Permit Number 05091686
Review Stop P
Sequence Number 3
Notes
Date Text
2007-11-15 14:43:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW. THE COMMENT NUMBER
 SHALL STAY THE SAME AS THE FIRST REVIEW:
  
 ******FROM PREVIOUS REVIEWS: (3RD REVIEW)
  
 A. OK
 B. OK
 1. OK
 2. OK
  
 3. SHT AP/A5.12 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS. SHOW SF DRAINED FOR EACH
 AREA ALONG WITH 1/2 AREA OF ALL VERTICAL
 WALLS, INCLUDING PARAPETS, AND THE AREA
 OF ANY ROOFS THAT DRAIN ONTO THE ROOF
 AREAS FROM ABOVE. - SHOW THE LOCATION OF
 ALL SECONDARY ROOF DRAINS OR SCUPPERS.
 IF SCUPPERS ARE USED, SUBMIT A DETAIL
 SHOWING HEIGHT, WIDTH, AND DISTANCE TO
 FLOW LINE OFF THE ROOF. SECTION 1503.4.2 ****RESPONSE
 NOTED, BUT SHEETS A5.05,
 A5.13, A5.25 WERE NOT SUBMITTED, AND NO CALCULATIONS
 WITH INFORMATION REQUESTED
 HAS BEEN LOCATED.
 ******RESPONSE NOTED, BUT THE SECONDARY ROOF DRAINAGE
 HAS NOT BEEN PROPERLY ADDRESSED. WHEN THE DOWNSPOUT HAS
 A BLOCKAGE, AND WHILE IT IS TRUE THAT THE STORM WATER
 CAN DRAIN OVER THE TOP OF THE COLLECTOR HEAD, THE
 CONCERN IS THAT WHEN THE SCUPPER OPENING IS BLOCKED
 THEN NEITHER THE PRIMARY NOR THE SECONDARY ROOF DRAIN
 WILL BE ABLE TO WORK. SECTION 1107.2 SEPARATE SYSTEMS
 ARE REQUIRED AND THE OVERFLOW SCUPPER SHALL BE SIZED
 PER SECTION 1107.3.
  
 4. SHTS AP/A5.61 & AP/A5.62 INDICATE
 SPECIFICATION "A" OR "B" FOR EACH UNIT
 OR BATHROOM AS REQUIRED IN FHA DESIGN
 MANUAL PAGES 7.34 & 7.35. - LAVS SHALL
 BE A MINIMUM OF 2' OFF THE WALL IN ORDER
 TO BE CENTERED ON THE 48" LENGTH OF THE
 CLEAR FLOOR SPACE. PLEASE INDICATE ON
 PLANS. FHA DESIGN MANUAL PAGES 7.47 AND
 7.48. - WATER CLOSET OPENING SHALL BE A
 MINIMUM OF 33" WITH THE WATER CLOSET 18"
 OFF ONE FIXTURE AND 15" OFF THE OTHER
 FIXTURE TO THE CENTER OF THE W/C. FHA
 DESIGN MANUAL PAGES 7.43, 7.44, & 7.45. ****RESPONSE
 NOTED, BUT SPECIFICATION
 "A" OR "B" HAS NOT BEEN INDICATED. ALSO
 THE WATER CLOSET OPENING MEASUREMENTS
 HAS NOT BEEN SHOWN ON THE FLOOR PLAN. ******RESPONSE
 NOTED, BUT SPECIFICATION "A" OR "B" HAS NOT BEEN
 INDICATED.
  
 5. OK
 6. OK
 7. OK
 8. OK - N/A
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
  
 14. AN RPZV BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE BUILDING. SECTION
 608.13.2.
 ****RESPONSE NOTED, BUT COMMENT NOT
 ADDRESSED. EACH BUILDING IS REQUIRED TO
 HAVE ITS OWN RPZV BACKFLOW. INDICATE ON
 PLANS AT THE WATER SERVICE TO THE
 BUILDING.
 ******RESPONSE NOTED, BUT THERPZV BACKFLOW FOR THIS
 BUILDING IS NOT INDICATED ON SHEET 10 OF THE CIVIL
 PLANS.
  
 15. SUBMIT A WATER LAYOUT FOR BUILDING
 AND WATER RISER DIAGRAMS. SHOW ALL PIPE
 SIZES, VALVES, WATER HAMMER ARRESTORS,
 (INSTALLED IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING). SECTIONS 104.3.1.1,
 606.1, 606.2, 608.13.2 & PDI-WH 201.
 ****RESPONSE NOTED, BUT THE WATER RISER
 DIAGRAM SHALL BE SUBMITTED IN ISOMETRIC
 FORM. WATER HAMMER ARRESTORS AND
 REQUIRED VALVES CAN NOT BE SHOWN ON A
 FLAT PIPING LAYOUT.
 ******RESPONSE NOTED, BUT THE VERTICAL RISER DIAGRAMS
 FROM THE FIRST FLOOR THUR THE 5TH FLOOR HAVE NOT BEEN
 SUBMITTED.
  
  
 16. OK
 17. OK
 18. OK
  
 **************NEW COMMENTS**************
  
 1B. ALL ARCHITECTURAL SHEETS. THE TITLE
 BLOCK SHALL CONTAIN THE PRINTED NAME OF
 THE PERSON SEALING THE DOCUMENT. FAC 61G1-16.004(6) &
 FS F81.2055.
 ******RESPONSE NOTED, BUT THE PRINTED NAME IS NOT
 INDICATED ON SHEET GN/A1.04.
  
 2B. SHT AP P14.04 PIPING FOR THE
 FIXTURES ON THE SECOND THRU 4TH FLOORS
 SHALL BE SHOWN ON THE FLOOR PLAN WITH
 THE FIXTURES, (SHT P14.05). SECTION
 104.2.1.3.
 ******RESPONSE NOTED, BUT PIPING NOT SHOWN FOR ALL
 RISERS.
  
 3B. OK N/A
  
 4B. SUBMIT A DETAIL FOR THE DOWNSPOUTS
 AND THE COLLECTOR HEAD AT THE TOP.
 INDICATE SIZE OF DOWNSPOUT, LENGTH,
 WIDTH & HEIGHT OF COLLECTOR HEAD.
 INDICATE ON ROOF PLAN SQUARE FOOTAGE
 DRAINING INTO EACH DOWNSPOUT.
 ******RESPONSE NOTED, BUT THE DETAIL DOES NOT SHOW
 LENGHT, WIDTH OR HEIGHT. SUBMIT AN ELEVATION DETAIL
 SHOWING THESE MEASUREMENTS AS WELL AS A CUT SECTION.
 SECTION 1106.3.
  
 5B. SECONDARY DRAINAGE AND SEPARATE
 SYSTEMS ARE REQUIRED FOR THE ROOF
 DRAINAGE PER SECTIONS 1107.1 & 1107.2.
 PLEASE INDICATE THE LOCATION AND SIZE OF
 THE SECONDARY ROOF DRAINAGE. SUBMIT A
 DETAIL FOR THE SECONDARY ROOF DRAINS. ******RESPONSE
 NOTED, BUT THE INTENT OF THE CODE SECTION HAS NOT BEEN
 ADDRESSED. WHEN THE DOWNSPOUT HAS A BLOCKAGE, AND WHILE
 IT IS TRUE THAT THE STORM WATER CAN DRAIN OVER THE TOP
 OF THE COLLECTOR HEAD, THE CONCERN IS THAT WHEN THE
 SCUPPER OPENING IS BLOCKED THEN NEITHER THE PRIMARY NOR
 THE SECONDARY ROOF DRAIN WILL BE ABLE TO WORK. SECTION
 1107.2 SEPARATE SYSTEMS ARE REQUIRED AND THE OVERFLOW
 SCUPPER SHALL BE SIZED PER SECTION 1107.3. SHOW THE
 LOCATION OF THE EMERGENCY OVERFLOW SCUPPERS.
  
 6B. OK
  
 ********NEW COMMENTS 3RD REVIEW********
  
 1C. SHT AP/P14.01 ALL WATER RISERS. WATER HAMMER
 ARRESTORS ARE REQUIRED ON THE WATER LINE TO THE DISH
 WASHER. SECTION 604.9.--UNIT A3 PLUMBING PLAN NOTE
 STATES "1/2 IN. CW/HW DN", BUT ONLY SHOWS CW LINE.
 PLEASE CORRELATE.--REVISION 1 DELETED FROM THE
 TITLE BLOCK REVISION INDEX. PLEASE SHOW THE COMPLETE
 HISTORY OF REVISIONS ON THE REVISION INDEX FOR ACCURATE
 RECORD KEEPING. SECTION 104.2.1.3.
  
 2C. SHT AP/P14.02 REVISION 1 DELETED FROM THE TITLE
 BLOCK REVISION INDEX. PLEASE SHOW THE COMPLETE HISTORY
 OF REVISIONS ON THE REVISION INDEX FOR ACCURATE RECORD
 KEEPING. SECTION 104.2.1.3.
  
 3C. SHT AP/P14.03 SHOW ALL PIPING ON EACH TYPICAL FLOOR
 PLAN. (2ND - 4TH & 5TH FLOORS) . SHOW ALL RISER NUMBERS
 AS THEY APPEAR ON THE BUILDING DRAIN ISOMETRIC RISER
 DIAGRAM AS THEY COME UP TO THE 2ND FLOOR. S7 THRU S-15
 NOT SHOWN ON THE 2ND FLOOR. INDICATE WHERE THESE RISERS
 COME THRU THE 2ND FLOOR.SECTION 104.2.1.--MANY
 PLAN KEY NOTES 1 & 2 DO NOT SHOW RISERS OR RISER
 NUMBERS.--WHERE DOES THE PIPING IN THE ELEVATOR
 CORRIDOR PIPE TO?SECTION 104.2.1.--REVISION 1
 DELETED FROM THE TITLE BLOCK REVISION INDEX. PLEASE
 SHOW THE COMPLETE HISTORY OF REVISIONS ON THE REVISION
 INDEX FOR ACCURATE RECORD KEEPING. SECTION 104.2.1.3.
  
 4C. SHT AP/P14.04 SANITARY RISER DIAGRAM S-5 SHOULD BE
 28 DFU'S, NOT 20 DFU'S. (EXTRA TUB OR SHOWER). TABLE
 709.1.--CLEANOUTS REQUIRED BY SECTION 1101.8 ARE
 REQUIRED ON THE STORM RISER DIAGRAM. PLEASE SHOW
 LOCATION OF ALL REQUIRED C/O'S.--CLEANOUTS REQUIRED
 BY SECTION 708.3 ARE REQUIRED ON THE SANITARY RISER
 DIAGRAM. PLEASE SHOW LOCATION OF ALL REQUIRED C/O'S.
 (CHANGE OF DIRECTION GREATER THAN 45 DEGREES).--
 REVISION 1 DELETED FROM THE TITLE BLOCK REVISION INDEX.
 PLEASE SHOW THE COMPLETE HISTORY OF REVISIONS ON THE
 REVISION INDEX FOR ACCURATE RECORD KEEPING. REVISION #4
 NOT SHOWN. SECTION 104.2.1.3.
  
 5C. SHT AP/P14.05 WATER HEATER DETAIL. A FULL OPEN
 VALVE IS REQUIRED ON THE SUPPLY LINE TO THE WATER
 HEATER. SECTION 606.1(7). PLEASE SHOW COMPLIANCE ON THE
 W/H DETAIL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6713
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved