| Plan Review Notes For Permit 05091686 |
| Permit Number |
05091686 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-11-07 13:33:39 | ***PROVISO*** | | | | | | COMMENTS HAVE BEEN ADDRESSED FROM THE PREVIOUS REVIEW. | | | PLEASE SEE ADDITIONAL COMMENTS: | | | | | | 1) DESIGN CRITERIA REFERS TO NFPA 13 AND SHEET FP 13.02 | | | REFERS TO NFPA 13R IN SHEET NOTES. PLEASE CORRELATE OR | | | EXPLAIN. | | | | | | 2) PLEASE SEE CORRECTION FROM PREVIOUS REVIEW COMMENTS. | | | MULTI-FAMILY RESIDENTIAL BUILDINGS TO COMPLY WITH | | | COMMERCIAL REQUIREMENTS FOR ADDRESSING. MINIMUM OF 6" | | | IN HEIGHT AND 1" IN WIDTH. SEPARATE UNIT CHARACTERS TO | | | COMPLY WITH 3" REQUIREMENT. | | | | | | 3) PLANS DON'T SEEM TO ILLUSTRATE ANY POST INDICATING | | | VALVE DETAIL. A NOTE DOES REFERENCE PIV TAMPER SWITCHES | | | ON SHEET FP 13.06. WHAT MEANS WILL BE PROVIDED WHERE | | | THE STATUS OF (1) BUILDING WON'T IMPACT OTHER | | | BUILDINGS? PLEASE PROVIDE DETAIL AND ILLUSTRATE ON FP | | | SITE PLAN. | | | | | | 4) PLEASE INDICATE IF ANY ELEVATORS WILL MEET | | | REQUIREMENTS FOR STRETCHER ACCESSIBILITY. | | | | | | | | | PLANS WILL BE STAMPED WHEN RETURNED AND ADDRESSED FOR | | | FIRE COMMENTS IN ADDITION TO OTHER REVIEW NOTES. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|